Cable testing and maintenance

Using a 2500-Vdc megohmmeter, check the
insulation resistance between both of the
rectangular (power) prongs on the plug and
the round (ground) prong after installing the
heating cable. Minimum reading should be 
1000 megohms.

Record the original values for each circuit, and
compare subsequent readings taken during
regular maintenance schedules to the original
values.

If the readings fall below 1000 megohms,
replace the Gardian W51 cable with a new
unit. Do not attempt to repair the unit.

WARNING! Fire and shock hazard.

Damaged heating cable can cause electrical
shock, arcing, and fire. Do not attempt to
repair or energize damaged heating cable.
Remove it at once and replace with a 
new length.

4. Install thermal insulation.

• A reliable Gardian system depends on properly installed and dry,

weatherproofed thermal insulation.

• Ensure that at least 1/2" of preformed foam or equivalent thermal

insulation is used and that all piping, including valves, joints, and wall
penetrations, has been fully insulated as shown in Figure 3.

• For protection to -20°F (-29°C), use 1" thick insulation.

• Install the insulation on the piping as soon as possible to minimize the

potential for mechanical damage after installation.

• Be sure the Gardian W51 label is visible on the outside of the thermal

insulation.

5. Finishing the installation.

• To prevent damage to the heating cable or cord, secure the 

power cord (cold lead) with a plastic cable tie, glass cloth tape, 
or duct tape as shown in Figure 4.

• Two labels indicating the presence of electric pipe heating cable are

included with the heating cable. Attach the two “Electric Traced” labels
on the outer surface of the pipe insulation at suitable internals to
indicate the presence of Gardian electric heating cable.

Figure 3   Insulation

Figure 4   Strain relief

6. Starting the system.

• Tyco Thermal Controls recommends that the system be tested per the

“Cable testing and maintenance” section below.

• Plug the heating cable into a 120 V ground-fault protected outlet.

• Check the circuit breaker to verify power to the cable.

• Standing water in the pipe should feel warm within an hour.

Note:

Pipes must be fully insulated.

Содержание Gardian W51

Страница 1: ...al device that must be installed correctly to ensure proper operation and to prevent shock or fire Read these important warnings and carefully follow all the installation instructions To minimize the danger of fire from sustained electrical arcing if the heating cable is damaged or improperly installed and to comply with the requirements of Tyco Thermal Controls and national electrical codes groun...

Страница 2: ...onsult Tyco Thermal Controls at 800 545 6258 General requirements for pipe freeze protection Gardian heating cables may be used on metal and plastic water pipes but not on flexible vinyl tubing such as garden hoses Gardian heating cables are not intended for use inside any pipes for freeze protection of liquids other than water or for use in classified hazardous locations Install with a minimum of...

Страница 3: ...cing Figure 1 or spiraling Figure 2 For straight tracing install the heating cable on a lower half of the pipe for example in the 4 o clock or 8 o clock position Be sure to install the additional heating cable required for valves flanges etc as shown in Figures 1 and 2 When the design calls for spiraling begin by suspending a loop every 10 feet as shown in Figure 2 To determine the loop length div...

Страница 4: ...cluding valves joints and wall penetrations has been fully insulated as shown in Figure 3 For protection to 20 F 29 C use 1 thick insulation Install the insulation on the piping as soon as possible to minimize the potential for mechanical damage after installation Be sure the Gardian W51 label is visible on the outside of the thermal insulation 5 Finishing the installation To prevent damage to the...

Страница 5: ...movement For the names of manufacturers of snow guards or snow fences contact Tyco Thermal Controls at 800 545 6258 Gardian heating cables may be used on Roofs made from all types of standard roofing materials including shake shingle rubber tar wood metal and plastic Gutters made from standard materials including metal and plastic Downspouts made from standard materials including metal and plastic...

Страница 6: ... in roof edge None 18 18 2 5 12 18 24 2 8 24 18 36 3 6 36 18 48 4 3 None 24 18 2 0 12 24 24 2 4 24 24 36 2 9 36 24 48 3 6 Gutter required No additional heating cable is required for gutters when tracing standing seam metal roofs Table 3 Typical spacing and layout measurements Length of cable per foot of roof edge feet Standing seam metal roof Eave overhang in Standard roof 18 seam 24 seam None 2 2...

Страница 7: ...tachment of the cable to the gutter bottom is not necessary Loop the heating cable in downspouts Do not leave the end of the Gardian in air at the end of the downspout as shown in Figure 11 Use H915 Hanger Brackets at the gutter downspout transition to protect the heating cable from fraying and from damage from sharp edges and to provide strain relief as shown in Figure 12 Refer to the H915 kit in...

Страница 8: ...ns of Sale for this product and in no case will Tyco Thermal Controls or its distributors be liable for any incidental indirect or consequential damages arising from the sale resale use or misuse of the product Specifications are subject to change without notice In addition Tyco Thermal Controls reserves the right to make changes without notification to Buyer to processing or materials that do not...

Отзывы: