Procedure

Mounting the Bracket

Enclosure mounted on bracket

4.1

 

Pull long bolts through 

inside holes

 in 

bracket, do NOT add washer, lock-washer 

or nut.

4.2 

Attach bracket to the enclosure through  

outer holes

 with short bolts, washer,  

lock-washer and nut using a 9/16" socket 

and/or open end wrench. 

Torque: 23 ft-lbs

4.3 

Place enclosure with bracket up to pole,  

add v-brackets over the long bolts. Secure 

with washer, lock-washer and nut using a  

9/16" socket and/or open end wrench. 

Torque: 23 ft-lbs

QUESTIONS? VISIT WWW.TALLEYCOM.COM OR CONTACT TALLEY AT 800.949. 7079 OR [email protected] TODAY.

Содержание RSCAC-7239 Series

Страница 1: ...RSCAC 7239 P 240 A RSCAC 7239 PS 240 A www raycap com INSTALL INSTRUCTIONS RSCAC 7239 Series RSCAC 7239 P 240 A RSCAC 7239 PS 240 A QUESTIONS VISIT WWW TALLEYCOM COM OR CONTACT TALLEY AT 800 949 7079 OR SALES TALLEYCOM COM TODAY ...

Страница 2: ...QUESTIONS VISIT WWW TALLEYCOM COM OR CONTACT TALLEY AT 800 949 7079 OR SALES TALLEYCOM COM TODAY ...

Страница 3: ...aimer 2 1 2 Warnings 2 2 Introduction 3 3 OVP Package Contents 3 3 1 Prerequisites 3 3 2 Required Tools and Supplies 3 4 Mounting the Bracket 4 5 Port Definitions 5 5 3 Component Definitions 5 6 Wiring Installation 6 7 Closing and Securing Unit 8 QUESTIONS VISIT WWW TALLEYCOM COM OR CONTACT TALLEY AT 800 949 7079 OR SALES TALLEYCOM COM TODAY ...

Страница 4: ...ufacturing Raycap shall have no liability for any error or damage of any kind resulting from the use of this document 1 2 Warnings Please read this manual prior to use to become familiar with the product s numerous features and operating procedures To maintain the maximum degree of safety follow the sequences as outlined Before using the product read all instructions and cautionary markings on the...

Страница 5: ...stand direct lightning currents in order to protect the sensitive equipment Raycap s small cell solutions featuring Strikesorb SPD technology significantly enhance the reliability availability of the site by providing superior electrical protection 3 0 Raycap AC Disconnect Package Contents 1 Enclosure 3 1 Prerequisites This document describes how to install the RSCAC 7239 Series on site and how to...

Страница 6: ...les in bracket do NOT add washer lock washer or nut 4 2 Attach bracket to the enclosure through outer holes with short bolts washer lock washer and nut using a 9 16 socket and or open end wrench Torque 23 ft lbs 4 3 Place enclosure with bracket up to pole add v brackets over the long bolts Secure with washer lock washer and nut using a 9 16 socket and or open end wrench Torque 23 ft lbs QUESTIONS ...

Страница 7: ...ort definitions 5 2 Torque Values for Sealing Cable Glands AC Cables 44 2 in lb 5 0 N m Component Definitions 5 3 Component call outs Power OUT x3 Power IN x9 Power IN x3 Ground Inserts can be replaced with standard conduit fittings Strikesorb Surge Protection Smart Power Meter 120VAC GFCI Courtesy Outlet Branch Circuit Breaker Main Circuit Breaker Shunt Trip for external main power disconnect Add...

Страница 8: ...Procedure Wiring Installation 6 1 Remove dead front by removing the two 2 Phillips head screws and set aside 6 2 Connection call outs Ground Busbar Neutral Busbar Neutral Input L1 IN L2 IN Ground RSCAC 7239 P 240 A QUESTIONS VISIT WWW TALLEYCOM COM OR CONTACT TALLEY AT 800 949 7079 OR SALES TALLEYCOM COM TODAY ...

Страница 9: ...ONS RSCAC 7239 Series 6 3 Install breakers in open slots as needed Ensure CT label orientation is right side up CT s shall be secured in place a minimum of one inch from the breaker terminals QUESTIONS VISIT WWW TALLEYCOM COM OR CONTACT TALLEY AT 800 949 7079 OR SALES TALLEYCOM COM TODAY ...

Страница 10: ...ll Power OUT cables as shown Note Power IN cables not shown for clarity Closing and securing unit 7 1 Replace dead front flip breaker ON to power circuits 7 2 Close cover Secure two 2 cover screws 7 3 Installation Complete QUESTIONS VISIT WWW TALLEYCOM COM OR CONTACT TALLEY AT 800 949 7079 OR SALES TALLEYCOM COM TODAY ...

Страница 11: ...QUESTIONS VISIT WWW TALLEYCOM COM OR CONTACT TALLEY AT 800 949 7079 OR SALES TALLEYCOM COM TODAY ...

Страница 12: ...CAC 7239 Series INSTALL INSTRUCTIONS www raycap com Raycap All rights reserved 320 1391 Rev B Page 10 of 10 QUESTIONS VISIT WWW TALLEYCOM COM OR CONTACT TALLEY AT 800 949 7079 OR SALES TALLEYCOM COM TODAY ...

Отзывы: