20
2)
Enter the existing number code within 15 seconds.
3)
A new code indicator message of "nEu.l " will appear.
4)
Enter the new number code within 15 seconds.
EXAMPLE:
For code number 4321: Depress
and
.
13. ENTER MODE SEQUENCE WITH ACTIVATED DATA-LOCK
1)
Depress the Console key that you wish to enter data into and depress
.
2)
The "codE" message will appear in the display.
a)
Enter your activated code number and depress
.
b)
If code is correct, "E" will appear in display and Console will
allow data entry.
c)
If code is incorrect, Console will cancel out of requested key.
INITIAL SYSTEM SET-UP
1)
Fill tank with water only. (If positive displacement pump is used, fully open
pressure relief valve, PRV).
2)
Place MASTER ON/OFF switch to ON and BOOM ON/OFF switches to OFF.
3)
Place AUTO/MAN/OFF switch to MAN.
4)
Verify that Boom Widths, SPEED CAL, METER CAL, and RATE CAL have been entered
correctly into the Console. In SELF TEST mode enter the normal sprayer operating
speed.
5)
Run pump at normal operating RPM.
6)
If centrifugal pump is used, proceed with Step 8. If positive displacement pump
is used, set pressure relief valve (PRV) to 65 PSI [450 kPa].
7)
Verify that boom valves operate and that no nozzles are plugged by operating the
individual BOOM ON/OFF switches.
8)
Place all BOOM ON/OFF switches to ON.
9)
Hold the FLOW CONTROL switch in INC position until pressure is at its maximum.
This assures that the motorized Control Valve is fully open. Verify maximum
pressure and RATE. (Pressure gauge is not supplied with the system).
NOTE:
A pressure gauge MUST be installed to properly monitor the system.