RE317 SERIES, 

Addressable Photoelectric Smoke And/or ROR & Fixed 
Temperature Heat Detector 

Installation Wiring Diagram

 

TYPICAL WIRING DIAGRAM 

OPTIONAL RETURN WIRING

LOOP

COMPATIBLE

CONTROL

PANEL

RE316 2 WIRE DETECTORS WIRING DIAGRAM

EOL

RESISTOR

OPTIONAL REMOTE LED

OPTIONAL REMOTE LED

5

6

2

4

5

6

2

4

 

 

Note: Don’t install terminal 4 and 6

 for the models without remote LED 

output

.

 

 
THE RE317 SERIES REQUIRE COMPATIBLE  ADDRESSABLE  COMMUNICATIONS  TO 
FUNCTION PROPERLY MOREOVER. 

 

THE  INSTALLATION  MUST  BE  IN  COMPLIANCE  WITH  THE  CONTROL 
PANEL SYSTEM INSTALLATION MANUAL. 
 

Panel Compatibility:    AVANI by Ravel. 

 
 

WARNING 

TO 

PREVENT 

DETECTOR 

CONTAMINATION 

AND 

SUBSEQUENT 

WARRANTY  CANCELLATION,  THE  SMOKE  DETECTOR  MUST  REMAIN 
COVERED UNTIL THE AREA IS CLEAN AND DUST FREE

 

GENERAL DESCRITPTION 

RE317 series are the photo electronic smoke detectors and/or ROR & Fixed 
temperature detectors combined with advanced addressable-analog 
communications. The DIP switches are provided for setting the detector

address that is RE317D series; To models without dip-switch, the detector is 
addressed by RE317A programmer. Please refer to RE317A PROGRAMMER 
USE’S MANUAL

.

 

 

Model 

Dip-switch 

Smoke   

sense 

Heat 

sense 

Remote 

LED 

RE317D-SHL 

 

 

 

 

RE317D-SL 

 

 

 

 

RE317D-HL 

 

 

 

 

RE317D-SH 

 

 

 

 

RE317D-S 

 

 

 

 

RE317D-H 

 

 

 

 

RE317A-SHL 

 

 

 

 

RE317A-SL 

 

 

 

 

RE317A-HL 

 

 

 

 

RE317A-SH 

 

 

 

 

RE317A-S 

 

 

 

 

RE317A-H 

 

 

 

 

 
Note: 1

The base model No. for RE317D(A)-S, RE317D(A)-SH and RE317D(A)-H 

  is P/N RE-312. 

                  The base model No. for RE317D(A)-SL, RE317D(A)-SHL and 

RE317D(A)-HL is P/N RE-314

.

   

 

INSTALLING THE BASE 

1.  To  insure  proper  installation  of  the  detector  head  to  the  base,  all  the  wires 

should be properly addressed at installation: 
(A) Position all the wires flat against terminals. 
(B) Fasten the wires away from connector terminals. 

2.  The  detectors  are  intended  for  mounting  on  a  ceiling  or  a  wall  at  open  area 

must be in accordance with the fire standard in your country

3.  The  base  of  the  smoke  detector  can  be  mounted  directly  onto  an  electrical 

junction box such as an octagonal (75mm, 90mm or 100mm), a round (75mm), 
or a square

 

(100mm) box without using any type of mechanical adapter. 

INSTALLING THE HEAD 

1. Set the desired address via DIP switch on the back of the detector, see 

ADDRESS SETTING section.

RE317A Series have no window on the back of 

the detector

 

2. Align the components as shown in Figure 2. 

3. Mate the detector head onto the base and twist clockwise to secure it. 
4.  After  all  detectors  have  been  installed,  apply  power  to  the  control  unit  and 

activate the communication line.   

5. Test the detector(s) as described in the TESTING section of this manual.

 

Note:

 

Do not install the detector head until the area  is  thoroughly  cleaned 

of  construction  debris,  dusts,  etc.  Please  refer  to  control  panel  technical 
information  to  decide  the  maximum  number  of  detector  installed  in  the 
same loop

 
 
 
 

 

Fig. 2 Mating detector head onto base.

 

TESTING 

All  the  alarm  signal  services,  releasing  device  and  extinguisher  system  should 
be  disengaged  during  the  test  period  and  must  be  re-engaged  immediately  at 

the conclusion of testing

SMOKE SENSOR TESTING 

Allow smoke from a cotton wick or a test smoke aerosol to enter the detector-sensing 
chamber for at least 10 seconds. When sufficient smoke has entered the chamber, the 
detector will signal an alarm, this  being  visible  by  a  continuous  illumination  of  the  red 
LED. Make sure to drive smoke out of the chamber before reset LED in order to keep 
the detector a current sensitivity. If the alarm fails in this step, it indicates a defective unit,   
which require to be returned to the distributor for servicing. 

HEAT SENSOR TESTING 

The detector to be tested should be subject to a flow of warm air at a temperature of between 
65°C and 80°C. (This requirement can be met by some domestic hair dryers). 
Proceed as follows: 
1.  Switch on the warm airflow and check that temperature is correct and stable. 
2.  From a distance  of  several  inches,  direct  the  airflow  at  the  guard  protecting 

the thermistor. The detector should alarm within 30 seconds. 

3.  Upon alarm immediately remove the heat source and check that the red LED 

of the detector is illuminated. 

4.    If detector fails to go into alarm mode within 30 seconds it is too insensitive 

and needs to be returned to the distributor for servicing. 

NOTE:

 

After testing, check that the system is set for normal operation and 

notify the appropriate authorities that the testing operation is complete and 
the system is active again.

 

 

 

Smoke  detectors  are  not  to  be  used  with  detector  guards 
unless  the  combination  has  been  evaluated  and  found 
suitable for that purpose. 

MAINTENANCE 

The  recommended  minimum  requirement  for  detector  maintenance  consists  of 
an  annual  cleaning  of  dust  from  the  detector  head  by  using  a  vacuum  cleaner 
cleaning  program  should  be  agreed  to  the  individual  environment  in 
conformance with the fire standard in your country. 

 

CAUTION:  DO  NOT  ATTEMPT  TO  DISASSEMBLY  OF  THE  FACTORY 
SEALED  SMOKE  DETECTOR.  THIS  ASSEMBLY  IS  SEALED  FOR  YOUR 
PROTECTION AND IS NOT INTENDED TO BE OPENED FOR SERVICING BY 
USERS. OPENING THE DETECTOR HEAD WILL VOID THE WARRANTY.

 

 

ADDRESS SETTING

1.Please refer to fig.3 to via DIP SWITCH to set detector

 

address.

 

 
 
 
 
 
 

 

 

                 

Fig.3: 

the 

location of dip switch

 

2. The definition of address is depicted as follows. 

Dip switch

BRACKET

LED ALIGNMENT MARK

LED

 

DETECTOR HEAD

RECTANGULAR