Photoelectric Smoke And/Or ROR & 
Fixed Temperature Heat Detector 

Installation Wiring Diagram

 

TYPICAL WIRING DIAGRAM 
Figure 1(a)

 shows the typical wiring diagram of the 2-wire 

multiple-station smoke/heat detector system.

   

 

 

Figure 1(b)

 shows the typical wiring diagram of the 4-wire 

multiple-station smoke/heat detector system. 
 

 

 
DO NOT PLACE LINKS BETWEEN THE WIRING POSITIONS OF 
TERMINALS 2 AND 5 TO PROVIDE POWER SUPERVISION. 

 

WARNING 

TO PREVENT DETECTOR CONTAMINATION AND SUBSEQUENT 
WARRANTY CANCELLATION, THE SMOKE DETECTOR MUST 
REMAIN COVERED UNTIL THE AREA IS CLEAN AND DUST 
FREE. 

INSTALLING THE BASE 

1. To insure proper installation of the detector head to the base, all 

the wires should be properly addressed at installation: 
(A) Position all the wires flat against terminals. 
(B) Fasten the wires away from connector terminals. 

2.  If you use a jumper wire to connect the poles of terminal 2 and 5 

when testing the detector loop continuity, be sure to remove the 
jumper wire prior to the installation of the detector head. 

3. The end-of-line device shown in fig. 1(a) and 1(b) should be 

compatible with the control unit.   

4. Open area smoke detectors are intended for mounting on a ceiling 

or a wall in accordance with the fire standard in your country. 

5. The base of the smoke detector can be mounted directly onto an 

electrical junction box such as an octagonal (75mm, 90mm or 
100mm), a round (75mm), or a square (100mm) box without using 
any type of mechanical adapter. 

INSTALLING THE HEAD 

1. Align the components as shown in Figure 2. 
2. Mate the detector head onto the base and twist clockwise to 

secure it. 

3. Do not install the detector head until the area is thoroughly 

cleaned of construction debris, dusts, etc. 

 
 
 

 
 
 
 
 
 
 
 
 
 

 

 

 

 

 

Fig. 2 Mating detector head onto base 

 
ADJUSTING THE RELAY FOR NO/NC 

The default condition of relay output is 

normally open

 (NO). 

1. To adjust the default condition of relay to 

normally closed

 (NC), 

take the screw out located on the side between the front cover and 
base. 

2. Refer to figure 3. There is a jumper head next to the relay on the 
PCB. Remove the jumper head and re-insert it in the NC position. 
 
3. replace the front 
cover. Carefully 
 
Relay contact 
rating:   

1A@30VDC,  
0.5A@125VAC

 

 
 
 
 
 
 
 
 
 
 

 
     
 
 

TESTING 

1. 

All the alarm signal services, releasing device and extinguisher 
system should be disengaged during the test period and must be 
re-engaged immediately at the conclusion of testing. 

2.

After energizing the detector head for approximately 60 seconds, 
check to see the indicator red LED flashing once every 4~5 
seconds. If red LED fails to flash, it indicates the non-functioning of 
the detector or faulty wiring. Re-check the wiring or replace the 
detector if necessary. 

 
 

REED SWITCH TESTING 

Take the magnet against the position of top cover marked in Fig.2. 
the detector will alarm after flashing once every 1.1seconds 
continuously for several times. If the detector fails to alarm, please 
re-check the magnet close to the mark on the toper or replace the 
detector if necessary. 
 

OPTIONAL RETURN WIRING

LOOP

COMPATIBLE

CONTROL

PANEL

RE316 2 WIRE DETECTORS WIRING DIAGRAM

EOL
RESISTOR

OPTIONAL REMOTE LED

OPTIONAL REMOTE LED

5

6

2

4

 

5

 

6

 

2

4

Fig. 3 Schematic of detector structure 
      When front cover is open. 

RECTANGULAR

LED

DETECTOR HEAD

BRACKET

LED ALIGNMENT MARK

MAGNET TEST

MAGNET TEST

JUMPER SETTING

SMOKE CHAMBER

RELAY

LED