Содержание 2524 ChronoCom

Страница 1: ...Cover Signaling Devices and Equipment Correctable Secondary Clocks With Separate Telecenter Systems Turning on the 2524 Functional Descriptions 6 Music Events 6 With Separate Telecenter Systems 6 As...

Страница 2: ...For information on communications functions refer to the following manuals Specifications Programming Capacity Up to 350 Events and 100 Holidays LED Digit Displays Mode Time and Schedule LED Indicator...

Страница 3: ...rs to split the load increases the total load that the output can handle GND A chassis ground which also serves as the circuit common It should be used when connecting a 2417 Correction Adapter Module...

Страница 4: ...a few helpful details Screw Terminal Cover To access the screw terminals remove the shield from the bottom of the electrical box that is attached to the rear of the chassis on the right as viewed fro...

Страница 5: ...mon Notes 1 The MIO is the Main Input Output Board in the Tele center IV 2 The MIO has wire wrap terminals and the 2524 has screw terminals 3 Use 22 AWG tinned cable for all connections 4 Do not conne...

Страница 6: ...and its outputs are connected to a Telecenter system to provide time tone signals Since the 2524 s ribbon cable does not connect to the speaker relay boards it cannot send music to individual rooms o...

Страница 7: ...30 NNE SR 030 NNE SRLV 060 12E SR and 060 12E SRLV NN any two digit number Synchronous Wired Dukane 24BF209 24BF212 707 8 and 707 9 types Synchronous Wired old type Reference Figure 1 or2 3 4 Secondar...

Страница 8: ...anklin Bi Polar Mark 5M Impulse Wiring more than 25 Special digitals for 24 VAC Application Wiring more than 25 Special digitals for 120 VAC Application Rauland Special Wiring for 24 VAC Application S...

Страница 9: ...120 24VAC CORR COIL I I I I I I I I I I I I I I 1 3 I I I I I I L J SECONDARY CLOCK Correction Code Mode A Correction Timing From X 00 00 To X 00 25 From 6 00 00 See Correctable Secondary Clocks unde...

Страница 10: ...C I RUN MOTOR I I I I RESET I 120 24 VAC CORR COIL Correction Code I I I I I I I I I I I I I I I I d SECONDARY CLOCK From X 00 00 To X 00 25 See Correctable Secondary Clocks under Wiring to determine...

Страница 11: ...ly I 12 Hour I Y is activated for 38 seconds every hour X is activated for 14 seconds From X 57 39 every 12 hours To X 58 17 From 5 57 54 X is activated for 8 seconds every hour I To 5 58 08 From X 57...

Страница 12: ...Correction Code Mode A I I f 120 24VAC CORR COIL I I Pam BRAY ea d SECONDARY CLOCK I I T I I I I I I I I I I I I I From X 56 05 From 11 56 00 To X 56 15 See Correctable Secondary Clocks under Wiring P...

Страница 13: ...I I 120 24 VAC I RUN MOTOR I 120 24VAC CORR COIL I I I I I I I I I I I I I I I Correction Code From X 00 00 Not Applicable See Correctable Secondary Clocks under Wiring to determine the output termin...

Страница 14: ...ction Code Correction Timing Hourly Y is activated for 57 seconds every hour From X 57 03 To X 58 00 12 Hour Y is activated in 11 cycles 57 sec onds on 63 seconds off From 5 59 03 TO 6 20 00 See Corre...

Страница 15: ...I I Correction Code Mode A 07 Correction Timing Hourly X is activated for 59 minutes 6 seconds every hour From x 44 59 To x 1 44 05 Y is activated for 54 seconds every hour From X 44 05 To X 44 59 12...

Страница 16: ...n Timing 12 Hour 08 Y is activated for 55 seconds Y is activated on and off 12 times 65 sec every hour onds on and 25 seconds off every 12 hours From X 58 05 From 5 05 00 To X 59 00 To 5 22 35 See Cor...

Страница 17: ...de A 09 I I I I I I I I I I I I I I I aw I SECONDARY CLOCK Correction Timing every hour From X 00 00 From 5 12 00 To X 59 25 Y is activated for 35 seconds every hour From X 59 25 To X 00 00 See Correc...

Страница 18: ...te Impulse I Y is activated for 2 seconds every minute From X XX 58 To X XX 00 X is pulsing at the rate of 1 second on and 1 second off Not Applicable See Correctable Secondary Clocks under Wiring to...

Страница 19: ...I I I I I I I I I I I I I I SECONDARY CLOCK is activated for 59 minutes 6 seconds To X 1 58 05 Y is activated for 54 seconds every hour Not Applicable See Correctable Secondary Clocks under Wiring to...

Страница 20: ...I I I I I I 1 I I I I I I Hourly is activated for 8 seconds every hour From X 57 54 To X 58 02 l2 Hour X is activated for 14 seconds every 12 hours From 5 57 54 To 5 58 08 See Correctable Secondary Cl...

Страница 21: ...48VDC I I I I I I I I D1 I B w 2524 SECONDARY CLOCK D1 AND D2 ARE 1N3210 OR EQUIVALENT i IMPULSE COIL From X XX 58 See Correctable Secondary Clocks under Wiring to determine the output terminals Figur...

Страница 22: ...i SECONDARY CLOCK ICorrection Code Mode A Correction Timing Minute Impulse Hourly minute From X XX 58 To X XX 00 From X 59 02 X is activated for 50 minutes every hour See Correctable Secondary Clocks...

Страница 23: ...dd Arc Suppression 1 Circuit as shown I R 10 c 1F 600 VDC I I SECONDARY CLOCK From X XX 58 To X 59 48 X activates the external relay reversing of the pulses for 50 minutes RY1 is a customer provided24...

Страница 24: ...210 OR EQUIVALENT X is activated for 2 seconds X is activated 16 cycles 1 second on 2 sec From X XX 58 From X 59 02 provides 24 VDC pulses Y is activated for 3 times each hour for 2 seconds on 58 seco...

Страница 25: ...itive pulse to the im pulse coil for 2 seconds every minute From X XX 58 To X XX 00 Hourly Y is activated for 15 cycles 1 second on 2 seconds off From X 58 10 To X 58 55 X activates the external relay...

Страница 26: ...AND D2 ARE lN3210 OR EQUIVALENT Minute Impulse X is activated for 2 seconds every minute Hourly Y is activated 10 seconds every hour From X 59 40 To x 59 50 From X XX 58 To X XX 00 Except for the 59t...

Страница 27: ...CLOCK Hourly Correction Timing Minute Impulse X is activated for 2 seconds every minute From X XX 58 To X XX 00 Except for the 59th minute Y is activated for 10 seconds every hour From X 59 40 To X 5...

Страница 28: ...DED DPDT RELAY WITH 2524 24VDC COlL Code Mode A From X 51 58 To X 1 51 00 then for 19 cycles 2 seconds on 1 second off I I cc 1 x AN 1 4 l See Correctable Secondary Clocks under Wiring to determine th...

Страница 29: ...Correction Timing Minute Impulse X is activated for 2 sec onds every minute From X XX 58 To X XX 00 Hourly is activated for 18 cycles 1 second on 2 seconds off From X 58 04 To X 58 56 Y is activated f...

Страница 30: ...n Code Correction Timing l Correction every 24 hours at 12 0l a m l Correction when the time is set l Correction when power is restored after a power failure See Correctable Secondary Clocks under Wir...

Страница 31: ...TERM B 2 IF11O VAC LINE CONNECT RELAY X TO 2416 TERM C 3 IF 130 VAC LINE CONNECT RELAY X TO 2416 TERM A l Correction every 24 hours at 12 0l a m l Correction when the time is set l Correction when pow...

Страница 32: ...120VAC LINE 6 Note The DIG output is always available regardless of the zone configuration or the Correction Codes used Figure 24 r KM0976...

Страница 33: ...ND DIGITAL BLK DIG 5VDC GND 2524 Z 2 2417 ICorrection Code Mode A Correction Timing None see Note l Correction every 24 hours at 12 0l a m l Correction when the time is set l Correction when power is...

Страница 34: ...ds every even minute 2 seconds on 118 seconds off 30 cycles per hour From X 00 58 To X 58 58 Y is activated 2 seconds every odd minute 2 seconds on 118 seconds off 30 cycles per hour Not Applicable RY...

Страница 35: ...BOTH 2415 S TO A OF 1ST 2415 TO A OF 2ND 2415 TO B OF 1ST 2415 TO B OF 2ND 2415 NOTE THE 2524 IS PROGRAMMEDFOR A CODE 20 CLOCK CORRECTION CONNECTING MORE THAN 25 DIGITAL CLOCKS TO A 2524 MASTER CLOCK...

Страница 36: ...HE 2524 IS PROGRAMMEDFOR A CODE 20 CLOCK CORRECTION TO F OF BOTH 2416 s TO B OF 1ST 2416 TO B OF 2ND 2416 TO D OF 1ST 2416 TO D OF 2ND 2416 CONNECTING MORE THAN 25 DIGITAL CLOCKS TO A 2524 MASTER CLOC...

Страница 37: ...LAY an autoformer NOTES 1 THE 2524 MASTER CLOCK IS PRE PROGRAMMEDTO OUTPUT RAULAND ANALOG CORRECTIONSIGNAL ON RELAY 7 IN THE SIX ZONE MODE OF OPERATION 2 MAXIMUMOF 25 CLOCKS ON THE 2415 POWER SUPPLY 3...

Страница 38: ...2 Each box K represents a load signaling device or equipment Each load s current should be lim ited to 5 amperes resistive at 30 VDC or 125 VAC 3 O u t 7 and O u t 8 are normally used for clock corre...

Страница 39: ...pin NOTES 1 The data transmission settings on the 2524 and device must match The 2524 s factory settings 1200 baud 1stop bit no parity and 8 data bits 2 The pin connections shown here apply only to a...

Страница 40: ...2524 Clock and intercom Controller Jumpers 7 PROGRAMMING J3 r 1 ENABLE I DISABLE JUMPER I BAUD RATE I SELECTOR...