Chapter 6: Using the Web Interface
154
Adding IT Devices for Ping Monitoring
You can have the PXE monitor the accessibility of any IT equipment,
such as DB servers, remote authentication servers or any power
distribution unit (PDU). The PXE supports monitoring a maximum of 8
devices.
The default ping settings may not be suitable for monitoring devices that
require high connection reliability so it is strongly recommended that you
should adjust the ping settings to meet your own needs.
Tip: To make the PXE automatically log, send notifications or perform
other actions for any server accessibility or inaccessibility events, you
can create event rules associated with server monitoring. See
Event
Rules and Actions
(on page 121).
To add IT equipment for ping monitoring:
1. Choose Device Settings > Server Reachability. The Server
Reachability dialog appears.
2. Click New. The Add New Server dialog appears.
3. By default, the "Enable ping monitoring for this server" checkbox is
selected. If not, select it to enable this feature.
4. Provide the information required.
Field
Description
IP address/hostname IP address or host name of the IT
equipment which you want to monitor.
Number of successful
pings to enable
feature
The number of successful pings required to
declare that the monitored equipment is
"Reachable." Valid range is 0 to 200.
Wait time (in
seconds) after
successful ping
The wait time before sending the next ping
if the previous ping was successfully
responded. Valid range is 5 to 600
(seconds).
Wait time (in
seconds) after
unsuccessful ping
The wait time before sending the next ping
if the previous ping was not responded.
Valid range is 3 to 600 (seconds).
Number of
consecutive
unsuccessful pings
for failure
The number of consecutive pings without
any response before the monitored
equipment is declared "Unreachable."
Valid range is 1 to 100.
Содержание PXE
Страница 1: ...Copyright 2014 Raritan Inc PXE 0C v3 0 E August 2014 255 80 0008 00 Raritan PXE User Guide Release 3 0...
Страница 12: ...Contents xii To Assert and Assertion Timeout 352 To De assert and Deassertion Hysteresis 354 Index 357...
Страница 16: ......
Страница 50: ...Chapter 5 Using the PDU 34 4 Pull up the operating handle until the colorful rectangle or triangle turns RED...
Страница 200: ...Chapter 6 Using the Web Interface 184 10 To print the currently selected topic click the Print this page icon...
Страница 339: ...Appendix A Specifications 323 RS 485 Pin signal definition al 4 5 6 D bi direction al Data 7 8...
Страница 353: ...Appendix D LDAP Configuration Illustration 337 5 Click OK The PX_Admin role is created 6 Click Close to quit the dialog...
Страница 380: ...Index 364 Z Zero U Products 1...
Страница 381: ......