Raritan PX Quick Setup Guide 

3

QSG-DPX2-1B-v3.3.10-E 

 255-80-6099-00 RoHS 

 
 
 
 

 

 

Screw each mounting button to each baseplate. The 
recommended torque for the button is 1.96 N·m (20 
kgf·cm). 

       

 

4.

 

Fasten the device to the rack or cabinet using the 
baseplaed-based tools. 

 

Use rack screws to fasten L-brackets or claw-foot 
brackets on the PDU to the rack. 

 

For the buttons, press the PDU forward, pushing the 
mounting buttons through the mounting holes, then 
letting the device drop about 5/8". 

 

Mounting Zero U Models Using Buttons 

1.

 

Turn to the rear of the PDU. 

2.

 

Locate the two screw holes on the rear panel. 

3.

 

Screw a button in each screw hole. The recommended 
torque for the button is 1.96 N·m (20 kgf·cm). 

       

 

4.

 

Press the PDU forward, pushing the mounting buttons 
through the mounting holes, then letting the PDU drop 
slightly. 

 

Mounting Zero U Models Using L-Brackets and 
Buttons 

1.

 

Fasten the L-bracket to each end of the PDU. 

       

 

2.

 

Choose either of the following ways to fasten the PDU to 
the rack. 

 

Attach the rack screws to the two rackmount holes of 
each L-bracket. 

 

Screw a mounting button in the back center of each 
L-bracket and then have both buttons engage the 

mounting holes in the rack. The recommended torque 
for the button is 1.96 N·m (20 kgf·cm). 

       

 

 

QS Rule 

 

Installing Cable Retention Clips on the Inlet 
(Optional) 

If your PX2/PX3 device is designed to use a cable retention 
clip, install the clip before connecting a power cord. A cable 
retention clip prevents the connected power cord from 
coming loose or falling off. 

 

To install and use a cable retention clip on the inlet: 

1.

 

Install the cable retention clip by inserting two ends of the 
clip into the two tiny holes adjacent to the inlet. 

Zero U models 

1U/2U models 

 

 

2.

 

Connect the power cord to the inlet, and press the clip to 
hold the cord. 

Zero U models 

1U/2U models 

 

 

 

 

QS Rule 

 

Connecting the PX3 Locking Line Cord 

A PX3 model is shipped with a locking line cord. Plug that cord 
into the PDU's inlet and the cord is securely locked.   

Note: To remove the cord, press the locking clips or push the 
slide buttons at two sides of the cord's connector. For details, 
see the topic titled "Disconnecting a Locking Line Cord" in the 
PX3 online help. 

 

QS Rule 

 

Содержание PX2

Страница 1: ...t to an AC power source that is current limited by a suitably rated fuse or circuit breaker in accordance with national and local electrical codes WARNING Use this product in a dry location WARNING Co...

Страница 2: ...de down shock stress reduces the trip point by 10 Note If normally the line cord is down upside down means the line cord is up Mounting 1U or 2U Models Using the appropriate brackets and tools fasten...

Страница 3: ...k screws to the two rackmount holes of each L bracket Screw a mounting button in the back center of each L bracket and then have both buttons engage the mounting holes in the rack The recommended torq...

Страница 4: ...h cable to the ETHERNET port on the PX2 PX3 2 Connect the other end of the cable to your LAN Note For PX3 iX7 you can connect either Ethernet port to the LAN but the green port labeled ETH 10 100 1000...

Страница 5: ...to use LDAP authentication Note If you are using Sunbird s Power IQ to manage the PX2 PX3 you must configure Power IQ and the PX2 PX3 to have the same date time or NTP settings 4 To change network set...

Страница 6: ...are Device Manager and locating the Dominion PX2 Serial Console under the Ports group 3 In the communications program press Enter to send a carriage return to the PX2 PX3 4 The PX2 PX3 prompts you to...

Страница 7: ...terAuthentication outer_auth outer_auth PEAP To set or enable Use this command EAP inner authentication network wireless eapInnerAuthentication inner_auth inner_auth MSCHAPv2 EAP identity network wire...

Страница 8: ...ccess point The following is the wireless LAN configuration that the PX2 PX3 supports Network type 802 11 A B G N Protocol WPA2 RSN Key management WPA PSK or WPA EAP with PEAP and MSCHAPv2 authenticat...

Страница 9: ...en Contact Raritan Technical Support when a replacement controller is needed For detailed information on how to remove it see the topic titled Replaceable Controller in the PX3 online help iX7 Specifi...

Отзывы: