Chapter 4: Connecting External Equipment (Optional)
71
You need to enable the modem dial-in support to take advantage of this
feature, see
Configuring the Serial Port
(on page 134).
Connecting an External Beeper
The PX supports the use of an external beeper for audio alarms.
External beepers that are supported include but may not be limited to the
following:
Mallory Sonalert MODEL SNP2R
After having an external beeper connected, you can create event rules
for the PX to switch on or off the external beeper when specific events
occur. See
Creating an Event Rule
To connect an external beeper:
1. Connect a standard network patch cable to the FEATURE port of the
PX.
2. Plug the other end of the cable into the external beeper's RJ-45
socket.
The beeper can be located at a distance up to 330 feet (100 m) away
from the PX.
Connecting a Schroff LHX/SHX Heat Exchanger
Note: Only the PDUs whose model names begin with PX2 or PX3
support the LHX/SHX heat exchangers.
To remotely monitor and administer the Schroff
®
LHX-20, LHX-40 and
SHX-30 heat exchangers through the PX device, you must establish a
connection between the heat exchanger and the PX device.
For more information on the LHX/SHX heat exchanger, see the user
documentation accompanying that product.
To establish a connection between the PDU and LHX/SHX heat
exchanger, an RJ-45 to RS-232 adapter cable provided by Schroff is
required.
To connect an LHX or SHX heat exchanger:
1. Plug the RS-232 DB9 end of the adapter cable into the RS-232 port
on the Schroff LHX/SHX heat exchanger.
2. Plug the RJ-45 end of the cable into the port labeled FEATURE on
your PX device.
Содержание PX2-1000 SERIES
Страница 5: ......
Страница 71: ...Chapter 4 Connecting External Equipment Optional 52...
Страница 231: ...Chapter 6 Using the Web Interface 212 8 Click OK...
Страница 570: ...Appendix G LDAP Configuration Illustration 551 5 Click OK The PX_Admin role is created 6 Click Close to quit the dialog...
Страница 589: ...Appendix I RADIUS Configuration Illustration 570 Note If your PX uses PAP then select PAP...
Страница 590: ...Appendix I RADIUS Configuration Illustration 571 10 Select Standard to the left of the dialog and then click Add...
Страница 591: ...Appendix I RADIUS Configuration Illustration 572 11 Select Filter Id from the list of attributes and click Add...
Страница 594: ...Appendix I RADIUS Configuration Illustration 575 14 The new attribute is added Click OK...
Страница 595: ...Appendix I RADIUS Configuration Illustration 576 15 Click Next to continue...
Страница 627: ...Appendix K Integration 608 3 Click OK...
Страница 647: ...Index 629 Z Zero U Connection Ports 74 Zero U Products 2...