Chapter 6: Using the Web Interface
214
Creating Actions
The PX comes with three built-in actions:
System Event Log Action: This action records the selected event in
the internal log when the event occurs.
System SNMP Notification Action: This action sends SNMP
notifications to one or multiple IP addresses after the selected event
occurs.
System Tamper Alarm: This action causes the PX to show the alarm
for the DX tamper sensor in the Alarms section of the Dashboard
until a person acknowledges it. By default, this action has been
assigned to the built-in tamper detection event rules. For information
on acknowledging an alarm, see
Alarms List
(on page 105).
Note: No IP addresses are specified in the "System SNMP Notification
Action" by default so you must specify IP addresses before applying this
action to any event rule.
The built-in actions cannot be deleted.
To create new actions:
1. Choose Device Settings > Event Rules. The Event Rule Settings
dialog appears.
2. Click the Actions tab.
3. Click
New.
4. In the "Action name" field, type a new name for the action. The
default name is New Action <number>, where <number> is a
sequential number starting at 1.
5. In the Action field, click the drop-down arrow and select the desired
action:
Action
Function
Execute an action
group
Creates a group of actions comprising existing
actions. See
Action Group
(on page 216).
Alarm
Requires the user to acknowledge the alert
when it is generated. If needed, you can have
the alert notifications regularly generated until
a person takes the acknowledgment action.
See
Alarm
External beeper
Enables or disables the connected external
beeper, or causes it to enter an alarm cycle.
See
External Beeper
(on page 218).
Содержание PX2-1000 SERIES
Страница 5: ......
Страница 71: ...Chapter 4 Connecting External Equipment Optional 52...
Страница 231: ...Chapter 6 Using the Web Interface 212 8 Click OK...
Страница 570: ...Appendix G LDAP Configuration Illustration 551 5 Click OK The PX_Admin role is created 6 Click Close to quit the dialog...
Страница 589: ...Appendix I RADIUS Configuration Illustration 570 Note If your PX uses PAP then select PAP...
Страница 590: ...Appendix I RADIUS Configuration Illustration 571 10 Select Standard to the left of the dialog and then click Add...
Страница 591: ...Appendix I RADIUS Configuration Illustration 572 11 Select Filter Id from the list of attributes and click Add...
Страница 594: ...Appendix I RADIUS Configuration Illustration 575 14 The new attribute is added Click OK...
Страница 595: ...Appendix I RADIUS Configuration Illustration 576 15 Click Next to continue...
Страница 627: ...Appendix K Integration 608 3 Click OK...
Страница 647: ...Index 629 Z Zero U Connection Ports 74 Zero U Products 2...