background image

 
 

 

 

Power Meter Quick Setup Guide 

17 

QSG-PMM-1A-v3.3.10-E 

 255-64-0004-00 

 
 
 

 

 

Configure Panel Branch Circuits 

1

 

In the Power Meters 
page, click the panel. 

 

 

The Panel details page 
opens. 

 

2

 

In the Panel Branch 
Circuits section, click the 
circuit position to open 

the pop-up menu. 

 

3

 

Click Create Circuit. The 
Create Circuit dialog 
opens. 

 

5

 

Enter a name for the 
circuit. 

 

6

 

Select the circuit type: 
One-Phase LN, 
One-Phase LL, 
One-Phase LLN, or 
Three-Phase. Circuit 
type cannot be changed 
later. 

7

 

Enter the current rating 
of the circuit in Amps. 

8

 

Enter the rating of the CT 
connected at this circuit 
position in Amps. 

9

 

Click the Phase or CT# to 
edit the automatic labels. 

10

 

Click Create. 

 

Содержание PMB-1960

Страница 1: ...ollution Degree 2 environment must control conductive pollution and the possibility of condensation or high humidity Consider the enclosure the correct use of ventilation thermal properties of the equipment and the relationship with the environment Installation category CAT II or CAT III Provide a disconnect device to disconnect the meter from the supply source Place this device in close proximity...

Страница 2: ... to 70 PMM or 8 PMM PMB Interconnection uses standard shielded CAT 5 cable All modules receive redundant power and continue to function as long as one or more PMM remain powered Raritan PM series power meters are designed for ease of use CTs are available in various ratings and contain built in burden resistors so they can be snapped onto live wires without damage CT orientation is not critical be...

Страница 3: ... 63 Hz Input Impedance 10MΩ Ratings for models with field wiring terminals For models with factory installed line cords rating is limited by plug and ratings are labeled on back on unit Current Measurement Inputs Input Range 0 400mV Input Impedance 10k CT Type Voltage Output 333mV at rated current CT Rated Current 1 1200A Meter Measurement Accuracy Active Power Energy 0 5 IEC 62053 Class 5 EN 5047...

Страница 4: ...0 240V Current 0 2A Overvoltage Category CAT III Pollution Level 2 Frequency 47 63 Hz Mechanical Terminal Block Screw Torque 0 37 ft lb 0 5Nm to 0 44 ft lb 0 6Nm Terminal Block Wire Size 14 24AWG 5 1 6mm Terminal Wire Temperature Rating 75 degree C DIN Rail T35 35mm Environmental Operating Temperature 0 60 C Operating Humidity 5 85 RH Operating Elevation 0 3000m Conformance Safety UL EN 61010 1 EM...

Страница 5: ... Controls TOP A Voltage measurement B Power C Factory use do not connect D Meter Bus Terminator Switch E Meter Bus Connectors Connects PMM to controller F Factory use do not connect G Multi conductor cable CT ABCNE connector H Meter ID configuration switch BOTTOM I Expansion port Connects PMM to PMB ...

Страница 6: ...ble CT 1 connector 2 Multi conductor cable CT 2 connector 3 Multi conductor cable CT 3 connector 4 Multi conductor cable CT 4 connector 5 Multi conductor cable CT 5 connector 6 Multi conductor cable CT 6 connector 7 Multi conductor cable CT 7 connector 8 Multi conductor cable CT 8 connector BOTTOM A Expansion port Connects PMB to PMM ...

Страница 7: ...ed RS 485 B Meter bus connector to PMM C Meter bus terminator switch D 10 100 base t Ethernet E Feature port Raritan asset strip F Sensor port temperature humidity etc G USB A B flash drives WIFI serial port H RS 232 terminal CLI modem I Pin hole access reset button J LCD meter readings settings configuration K Keypad ...

Страница 8: ...sion Connector supplied with PMB Do not hot plug the Expansion Port PMM and PMB must be disconnected from all power source before plugging Expansion Port Snap Expansion Connector to Expansion Ports on bottoms of PMM and PMB TOP B 35mm DIN rail C PMM D PMB E Modules snap into rail Pull white tab here to remove ...

Страница 9: ...ed Do not solder tin wire ends C All CT 333mV output at rated current Do not use current output CT CTs can be connected to live circuits Connect CT in either direction Circuit Type Circuit Description Wiring Connections Voltage CT A B C N A B C Single Phase L N 120V 230V 240V X X X L L 208V 400V X X X Split Phase North American 120 240V Panel 2L N circuit X X X X X Three Phase 3L 3 phase without n...

Страница 10: ...beled connector All CTs 333mV output DO NOT use current output CT CT can be connected to live circuit in either direction Meter auto corrects polarity Branch Circuit Description Current Transformers How Many Connect To Line Neutral LN 120V 230V circuit wired to 1 pole circuit breaker 1 phase line Line Line LL 208 240 400V circuit wired to 2 pole circuit breaker 1 either phase line Line Line Neutra...

Страница 11: ...m an auxiliary AC power source Powering from the voltage measurement inputs minimizes circuitry but the meter may stop functioning if the voltage turns off Powering from an auxiliary single phase circuit is required when the voltage measurement circuit exceeds 240V or when continued operation is required if the voltage measurement inputs turn off ...

Страница 12: ...isy chain wired to a single controller PMC using shielded cat 5 Ethernet cable The wiring order of the modules and controller is not important A All cables shielded Cat 5 each cable 100m max length B Switch MBT terminator ON for devices at ends of daisy chain C Switch MBT OFF for devices in middle of daisy chain D Assign each meter unique ID 01 70 PMM without PMB 01 08 PMM with PMB ...

Страница 13: ...Power Meter Quick Setup Guide 13 QSG PMM 1A v3 3 10 E 255 64 0004 00 Panel Layout ...

Страница 14: ...low 30 seconds for first connection Username admin Password raritan Configuring Power Meters and Branch Circuit Monitors You can configure your product with a spreadsheet or in the product s web interface To configure with a spreadsheet Go to Raritan com and download the configuration spreadsheet from the BCM2 Support page Follow the instructions in the spreadsheet To configure with the product we...

Страница 15: ...out PMB 1 Enter a name 2 Select the circuit type Single Phase Split Phase 3 phase 3 Enter the mains circuit breaker rating 4 Select the checkbox for each CT installed Enter the CT rating Ratings are marked on the CT 5 Click OK The configured power meter displays in the dashboard and Power Meters page ...

Страница 16: ...e Split Phase 3 phase 3 Enter the number of circuit positions in the panel Select the panel layout one or two columns Select the circuit position numbering style sequential or odd even 4 Enter the current rating circuit breaker rating of the circuit 5 Select the checkbox for each CT installed Enter the CT rating Ratings are marked on the CT 6 Click OK ...

Страница 17: ...t position to open the pop up menu 3 Click Create Circuit The Create Circuit dialog opens 5 Enter a name for the circuit 6 Select the circuit type One Phase LN One Phase LL One Phase LLN or Three Phase Circuit type cannot be changed later 7 Enter the current rating of the circuit in Amps 8 Enter the rating of the CT connected at this circuit position in Amps 9 Click the Phase or CT to edit the aut...

Страница 18: ...ith a black bracket around the circuit positions Configure Thresholds 1 In the Power Meters page click the panel or power meter The details page opens 2 In the details page click the actions icon then choose Edit Thresholds 3 The sensor list displays Click a sensor to open the Edit Threshold dialog ...

Страница 19: ...E 255 64 0004 00 4 Select the checkbox for the level and enter the threshold current in amps Click OK This example shows RMS Current thresholds set for upper warning and critical levels for the circuit max current rating and a lower warning set for 1 amp ...

Страница 20: ...y with automatic and manual modes In automatic mode the display scrolls through readings Manual Mode In manual mode you can select readings and settings to view Press or to view the Main Menu To return to automatic mode press once or several times Press to choose a menu item Press to select Power Meters list Power Meter details ...

Отзывы: