Raptor GFM600 Скачать руководство пользователя страница 2

©2011 RLE Technologies. All rights reserved. RLE is a registered trademark, and
SeaHawk, Falcon, and Raptor are trademarks of RLE Technologies. All other trademarks
or registered trademarks are the property of their respective companies. Although the
information contained in this document is believed to be accurate and correct, RLE
Technologies assumes no responsibility, and disclaims all liability, for any damages
resulting from the use of this information or any error or omission in this document. RLE
Technologies does not warrant, guarantee, or make any representations as to the
performance, fitness for use, safety, or reliability of any existing or future wiring,
equipment, additions or modifications to equipment, or any other component of the original
or modified system. Specifications are subject to change without notice.
Part number 120049   Rev. 5.2   1/2011

104 Racquette Drive

Fort Collins, CO 80524

970.484.6510

www.rletech.com

5

Relay Outputs

Note: 

These relays are “picked” relays; they are energized under normal 
operating conditions.

Note: 

All three positions must be open to disconnect high voltage.

6

Ground Fault Test

1

Rotate the two rotary switches to a setting of 00.

2

Verify that the Ground Fault LED is on, the audible alarm is on, the Status 
LED is off, and the Status and Ground Fault relay contacts have been 
transferred.

3

Return the two rotary switches to their original settings.

Note: 

The Reset switch must be pressed each time the system alarms to restore 
it to normal operation.

Status

Relay output is a Form C Relay (NO/NC). The state 
of this relay changes when an internal fault is 
detected, or power is removed from the GFM600-2.

Ground Fault

Relay output is a Form C Relay (NO/NC). This 
relay will change state upon ground fault alarm. 
The GFM600-2 has two ground fault relay outputs.

Relay Output Terminal Blocks

(Duplicate) Ground 
Fault Relay

Status Relay

Ground Fault Relay

Inside the Front Cover

Battery Bus Disconnect Terminal

Open position, 
Insert screwdriver 
here and lift

Bat –

Bat +

Closed 
position

Chassis ground

WARNING

Please use caution. High voltage is used in the 
GFM600-2. A dedicated circuit breaker must be provided 
in the building within close proximity to the GFM600-2 
and be clearly marked as the disconnecting device for 
the GFM600-2. Use copper wire with an insulation rating 
of 600V only.