1.

 

Product Item 

This guide provides user operation and product specification information for the RAPIX PIR Occupancy Sensor, 

item number 

DGOZ-OS-PIR-360

2.

 

Product package contents 

The PIR Occupancy Sensor package includes the following. 

 

1 x PIR Occupancy Sensor 

 

1 x eHub patch lead. 

3.

 

Important notes and safety information 

 

The PIR Occupancy Sensor is 

only suitable for use with the RAPIX eHub

 

 

The PIR Occupancy Sensor 

does not have a mains supply connection

 

 

The PIR Occupancy Sensor is 

powered via a RAPIX eHub (12Vdc)

 

 

There are 

no user serviceable parts

 inside the PIR Occupancy Sensor. Do not attempt to disassemble or 

operate the device with any covers removed 

 

The PIR Occupancy Sensor is intended for 

indoor use only

.  

If you require information or assistance regarding the installation, configuration, or operation of the PIR 
Occupancy Sensor, contact Technical Services at Diginet Control Systems. Contact details are provided on the 
back cover of this guide and also at 

www.diginet.net.au

 

4.

 

Product summary and capabilities  

A compact, low profile 360˚ passive infrared (PIR) occupancy sensor for connection to a RAPIX eHub.  

The sensor includes a detection lens which senses both Minor and Major Movement (as defined by NEMA 

Standard WD 7 - 2011 for Occupancy Motion Sensors).  

Movement is detected via a sensor array with 864 fields of view, ensuring reliable operation to a distance of 7m 

diameter. The device also includes a light sensor for detecting ambient light levels.  

Adjustment sliders for time-out and light level are discreetly hidden in the patented sensor head which pops out 

providing easy configuration after installation, without any tools. 

5.

 

Product Features  

 

Connects directly to a RAPIX eHub (up to 2 sensors per eHub) 

 

High sensitivity 360˚ detection array designed for both minor and major movement applications 

 

Unobtrusive, 60mm diameter, flush-mount design 

 

Integrated light level detector to inhibit switch-on if there is sufficient natural light available 

 

Adjustment controls easy to read and set without a tool  

 

Hidden yet easily accessible sensor head adjustment controls for time-out and light level adjustment. 

 
 

 

Содержание DGOZ-OS-PIR-360

Страница 1: ...Installation Guide DGOZ OS PIR 360 DIGINET NET AU PIR Occupancy Sensor Designed in Australia to meet Australian Standards and installation conditions ...

Страница 2: ...the back cover of this guide and also at www diginet net au 4 Product summary and capabilities A compact low profile 360 passive infrared PIR occupancy sensor for connection to a RAPIX eHub The sensor includes a detection lens which senses both Minor and Major Movement as defined by NEMA Standard WD 7 2011 for Occupancy Motion Sensors Movement is detected via a sensor array with 864 fields of view...

Страница 3: ...te is provided on the sensor box for ease of making the cut out Note Avoid placing the sensor in positions close to hot or cold air vents and where the field of view extends through doorways This will reduce the risk of false triggering of the sensor 7 Connecting the PIR Occupancy Sensor to a RAPIX eHub The PIR Occupancy Sensor is only suitable for use with the RAPIX eHub The PIR Occupancy Sensor ...

Страница 4: ...erating position The tables below detail the parameters for the time delay and ambient light level adjustable settings Settings for adjustable time delay Position Time Delay Typical Application 5 Sec Walk test test light level setting and to confirm effective field of view 5 5 Mins Halls passages 10 10 Mins Store rooms 15 15 Mins Tea rooms 20 20 Mins Enclosed offices meeting rooms bathrooms 25 25 ...

Страница 5: ...vement within a 3 5m diameter circular area of its position when mounted at 2 7m from the floor as shown below 1 Referenced from the NEMA Guide Publication WD 7 2011 Occupancy Motion Sensors Standard National Electrical Manufacturers Association Virginia USA 2012 Note Additional detection outside these areas may be noticed subject to external temperature mounting height and movement activity 10 Pr...

Страница 6: ...Regulation Standard Title EMC AS NZS CISPR 22 2009 CISPR15 Information Technology Equipment Radio Disturbance Characteristics Limits and Methods of Measurement AS NZS CISPR 22 A 2010 The product is in conformity with the essential requirements of the following EC Directives and accordingly carries the CE marking EC Council Directive Title 2004 108 EC Electromagnetic Compatibility EMC 2011 65 EU Re...

Страница 7: ...ccessories instructions specifications or other material supplied with the Goods and a notice in writing 7 2 1 stating the Returned Goods Authorisation Number for the Goods 7 2 2 describing in detail the defect or fault in the Goods 7 2 3 setting out the Owner s contact details including postal address email address and telephone numbers at which the Owner can be contacted during usual business ho...

Страница 8: ...at any time without notice and without liability While every effort is made to ensure that all information in this user and installation guide is correct no warranty of accuracy is given and Gerard Lighting shall not be liable for any error Trademarks The identified trademarks and copyrights are the property of Gerard Lighting unless otherwise noted This product complies with the requirements for ...

Страница 9: ...t Padstow NSW 2211 Contact General Enquiries 1300 95 DALI 3254 or sales diginet net au Technical Services 1300 95 3244 or support diginet net au Fax 1300 95 3257 Diginet is a brand of the Gerard Lighting Group Version Issue 1 January 2016 Item 14 12 008 003 01 Printed on recycled paper ...

Отзывы: