 RAPIX Xi DALI Long Range Occupancy Sensor DGOZ-LRS-PRLLSW 

 

 

Page 1 of 4 

DGOZ-LRS-PRLLSW - RAPIX Xi DALI Long Range Occupancy Sensor 

With Auxiliary Input 

Product summary and capabilities  

The Long Range Occupancy Sensor acts as a motion / occupancy sensor and DALI 
Application Controller. The advanced control functions can be used in any DALI or 
DALI-2 system. 

The sensor is commissioned using the RAPIX Addressing or RAPIX Integrator 
software. These software packages are available at no charge from ozuno.com. 

Important notes and safety information 

 

WARNING

 

 Electric shock may result in serious injury or death. 

Follow all warnings in this guide and on the product. Work in 
accordance with the latest electrical safety practices. 

 

 

This Occupancy Sensor is powered only from DALI line. 

 

DALI system wiring is only single insulated from mains. Treat DALI wiring the same as mains wiring. 

 

The Auxiliary input wiring has no isolation from DALI. Treat the Auxiliary input the same as mains wiring. 

 

The Auxiliary input does not provide any power source. Connect it only to voltage-free contacts or a switch. Do 
not connect any part of the Auxiliary Input to any other power source, or to earth, or to mains line or neutral. 

 

There are 

no user serviceable parts

 inside the Occupancy Sensor. Do not attempt to disassemble or operate the 

device with any covers removed. 

 

This sensor is intended for 

indoor use only

.  

Indicators 

 

DALI Activity: 

A DALI activity indicator is located near the terminal block. This blinks green and can be seen 
through the plastic housing. 

 

During installation and before pushing into the ceiling hole:  If a green glow can be seen with a 
blink about every 1 .. 2 seconds, then DALI is connected and the device has electrical power. 

Discovery: 

The RAPIX commissiong software includes a discovery function. When activated, an indicator 
under the PIR lens will flash. This allows physical location of the sensor after it has been 
installed. 

Terminals 

 

 

Содержание DGOZ-LRS-PRLLSW

Страница 1: ...s wiring The Auxiliary input wiring has no isolation from DALI Treat the Auxiliary input the same as mains wiring The Auxiliary input does not provide any power source Connect it only to voltage free contacts or a switch Do not connect any part of the Auxiliary Input to any other power source or to earth or to mains line or neutral There are no user serviceable parts inside the Occupancy Sensor Do...

Страница 2: ...0 Materials Enclosure Flame retardant Polycarbonate UL 94V 0 Weight 100 g Number of DALI Short addresses used None this sensor does not use a DALI Short Address DALI addressing types supported Short Addresses Group Addresses Scenes Broadcast Number of Xi extended addresses used One Xi occupancy sensors per DALI line Up to 20 per DALI line Additional addressing types RAPIX Zones RAPIX Flags RAPIX O...

Страница 3: ...55015 AS NZS CISPR 15 AS CISPR 15 EN 55032 AS NZS CISPR32 EN 55035 EN 61547 EN 61347 2 11 AS NZS 61347 2 11 EN 61347 1 AS NZS 61347 1 EN 62368 1 DALI Standards and Compliance IEC 62386 101 IEC 62386 102 EC Council Directives 2014 35 EU Low Voltage 2014 30 EU Electromagnetic Compatibility EMC 2015 863 Restriction of Hazardous Substances RoHS in Electrical and Electronic Equipment Separately Availab...

Страница 4: ...lacement or refund for a major failure and for compensation for any other reasonably foreseeable loss or damage You are also entitled to have the goods repaired or replaced if the goods fail to be of acceptable quality and the failure does not amount to a major failure L I G H T I N G CONTROL SYSTEM Ozuno Trading Pty Ltd Ozuno reserves the right to alter the specifications designs or other feature...

Отзывы: