Remote Mounting and Wiring

The MRS 4 remote assembly mounts in a standard U.S. electrical 

box with a minimum depth of 2.5".

Turn the power to the unit 

off 

until all connections are  

made. It is important to ensure that the Remote Ports are not 

subjected to sustained voltages outside the range of 0 to 5 volts 

DC or high levels of static. Inputs are protected, however caution 

is the better part of...you know. It is a good idea to install the 

wiring, connect it to the Remote and then make the final con-

nections at the unit.

When wiring to Euroblocks, a minimum wire gauge of 22 

is preferred for reliability. If the ground or shield wire is left 

shorter, it acts as a strain relief for the other wires. Cable with a 

flexible jacket is easier to use and less likely to damage the con-

nections. Be sure to note the wire color of each input in order 

to facilitate correct wiring to the unit. Make sure wires are free 

of nicks and that the cable jacket is stripped back sufficiently 

to allow it to lie in the electrical box with the remote assembly 

inserted. Connect each wire to the 5-pin connector by fully 

inserting it in the correct socket and tightening the screw.

Use the flat head #6 screws supplied with the kit to mount 

the remote assembly and silkscreened front panel to the electrical 

box. Install the Decora plate of your choice (not included).

Wire Types

You may use 5-conductor unshielded remote control signal cable 

for shorter runs (less than 200 ft.) or 4-conductor (2 pair) shield-

ed remote control signal cable (use the shield as the GND return) 

for longer runs (200 to 1000 ft.). The type of wire required is 

influenced by your installation and local electrical codes.Varia-

tions in wire type do not greatly affect the performance of the 

remote controls. Rane Corporation does 

not 

provide or source 

cable. Please contact your local retail or wholesale outlet, 

not 

the 

factory.

The following is a short list of suitable cable types:

CONSOLIDATED ELECTRONIC WIRE AND CABLE

Plenum cable:

Unshielded remote control signal cable CAT. #9896

Shielded remote control signal cable CAT. #9877 or #9852

WEICO WIRE & CABLE INC.

Communication and control cable:

Multiconductor, unshielded CAT. #7606

ALPHA

Communication and control cable:

Multiconductor, unshielded CAT. #1175C

BELDEN

Unshielded remote control signal cable CAT. #88741

Shielded remote control signal cable CAT. #88723

Block Diagram / Schematic

1

2

3

4

C

1

2

3

4