Installation Instructions

1. Safety Precautions

• To  prevent  an  accident  and/or  injury,  do  not  hoist  the  unit  over

your shoulder. Use a hand truck to transport the unit.

• Do not lay the unit on its side.

• Wear safety glasses and work gloves during installation.

2. Test the Raw Water

• Test the raw water for hardness, iron and/or any other element that

could affect the performance of the system.

3. Check the Water Pressure

• Use a pressure gauge to confirm that the water pressure does not

exceed 120 psi. If the water pressure does exceed this limit, install
a  pressure  regulator  on  the  inlet  pipe  of  the  unit.  The  minimum
water  pressure  for  a  conditioner  is  20  psi.  60  psi  is  the  optimum
operating pressure.

4. Locate a Site for the System

• There are three primary requirements needed for a site: the main

water  source,  a  drain  and  an  electrical  connection.  Locate  the
system as close to these items as practical. Avoid drain lines over
25 feet long. In most applications, bypass any outside faucets.

• Place the system in the desired location. The location should have

a level, smooth, and clean surface.

• If the system is located outdoors, protect the unit from direct sun-

light. Direct sunlight can damage the fiberglass and other system
components. If necessary, build a box or shed.

5. Install the Valve Head

• Remove the cap plug from the tank.

• Lubricate  the  riser  pipe  o-ring  and  tank  o-ring  with  the  proper

silicone lubricant.

• Attach  the  supplied  upper  basket  to  the  bottom  of  the  control

valve; twist to lock in place.

• Align  the  upper  basket  with  the  riser  pipe  and  slowly  lower  the

control valve onto the riser pipe, using a twisting motion.

• Align the control valve with the tank. Push down on the control

valve and continue to turn it clockwise until the valve o-ring seals
against the tank.

6. Turn Off the Water and Drain the Plumbing

• Turn off the water at the meter or the pressure tank.

• To drain the plumbing system, open all faucets in the house and

flush  the  toilets.  The  water  will  drain  out  of  the  lowest  faucet  or
outlet.

• Do  not  sweat  pipes  with  water  in  them  or  while  attached  to  the

system; steam will damage the plastic parts in the valve.

• Do  not  point  the  soldering  torch  directly  at  the  mineral  tank  or

control  valve.  These  composite  materials  will  last  a  lifetime,  but
cannot withstand the intense heat from a torch.

Helpful  Tip: The  drain  may  be  a
floor  drain, a  sewer  trap, utility
sink, vent  stack, dry  well, etc.,
depending  on  local  plumbing
codes.

!

Important Note: The system can
only  be  installed  outdoors  in
climates  that  do  not  reach
freezing levels.

!

Important  Note: Do  not  over-
tighten the valve to the tank.

Helpful  Tip: This  procedure  will
allow  air  to  enter  the  plumbing
system.

!

Important  Note: Not  Applicable
for EC4-CAB and SS Models.

!

Important  Note: Applicable  for
copper plumbing installations.

Содержание EC4 100 V

Страница 1: ...09 06 For use in California RainSoft Division of Aquion Water Treatment Products 2080 East Lunt Avenue Elk Grove Village Illinois 60007 1 847 437 9400 or 1 800 860 7638 www rainsoft com EC4 SERIES WAT...

Страница 2: ...ntenance Requirements 7 Product Certification Information 7 Installation Instructions 8_11 System Start Up 12 Customer Settings 13_14 How to Initiate a Manual Regeneration 14 System Alarms 15 Understa...

Страница 3: ...individual water consumption needs Application Limitations On hardness levels of 60 grains and higher the system may not achieve a hardness of less than 1 grain due to high Total Dissolved Solids some...

Страница 4: ...s system is designed to treat cold water only The installation must be on a cold water supply Data Chart for ION X 2000 V Resin Cation Exchange Media The conditioners are efficiency rated according to...

Страница 5: ...gpm psi Drop High Salting Medium Salting Low Salting Efficiency EC4 50 T 8 x 44 0 5 10 0 1 5 12 0 12 600 7 5 lbs 10 000 5 0 lbs 5 800 2 0 lbs n a EC4 50 CT 8 x 44 0 5 10 0 1 5 13 0 12 600 7 5 lbs 10 0...

Страница 6: ...x 44 1 0 10 0 2 0 10 0 29 400 15 0 lbs 23 900 10 0 lbs 10 900 3 0 lbs 3 630 3 0 lbs EC4 100S D 10 x 35 1 0 10 0 2 0 10 0 29 400 15 0 lbs 23 900 10 0 lbs 10 900 3 0 lbs 3 630 3 0 lbs EC4 100S CD 10 x 3...

Страница 7: ...ication Information The EC4 Series is tested and certified by the WQA to NSF ANSI Standard 44 for the specific performance claims as verified and substantiated by test data Please refer to the perform...

Страница 8: ...ove the cap plug from the tank Lubricate the riser pipe o ring and tank o ring with the proper silicone lubricant Attach the supplied upper basket to the bottom of the control valve twist to lock in p...

Страница 9: ...system the inlet is the pipe connection on the right side of the valve see figure 2 The arrow molded into valve indicates the direction of flow Connect the treated water pipe to the outlet pipe connec...

Страница 10: ...e air gap must be installed between the end of the drain line and the drain to prevent possible back siphoning see figure 5 11 Install the Brine Safety Float Insert the brine well into the brine tank...

Страница 11: ...from the warranty pack Attach the U shaped connectors supplied to the wire with a crimping tool not supplied Connect the wire to the transformer see figure 8 Insert the other end of the wire with the...

Страница 12: ...es see figure 9 Open the bathtub faucet again and allow the system to fill with water for approximately 5 minutes After 5 minutes test for soft water 4 Flush the Hot Water Heater Run hot water in the...

Страница 13: ...he time of day only on the hour that the computer will regenerate the system based on the parameters set To access these programming options please follow the directions listed below If the display is...

Страница 14: ...eration To exit the Customer Settings press the Enter key How to Initiate a Manual Regeneration If the display is not lit press any key to begin When the display is lit press the Manual Regen key The...

Страница 15: ...Use Displays the average water use of the system in gallons per day Avg Weekly Salt Used Displays the average weekly salt used in pounds Current Flow Rate Displays the flow rate through the system wh...

Страница 16: ...ion is complete 2 The system regenerates at the wrong time 1 The raw water has changed 2 The bypass valve is open 3 The power supply is disconnected 3 Plug in the power supply 1 Call your RainSoft Dea...

Страница 17: ...y does not include labor charges and does not cover installation transportation or any other claims or torts Some states do not allow the exclusion or limitation of incidental or consequential damages...

Страница 18: ...18 Valve Exploded View 13 16 17 26 ABCDE 18 20 21 19 30 3 B A 31 12 11 28 15 14 29 32 1 10 2 6 23 ABC 27 25 4 5 7 24 22 9 8...

Страница 19: ...54 Flow control washer 0 25 gpm 21 1 17957 Adapter blfc 0 25 gpm 22 1 17939 1 2 npt x 1 2 barb poly elbow 23 1 17557 Composite bypass valve 24A 1 17560 3 4 coupling adapter assembly 24B 1 17558 Turbin...

Страница 20: ...Control Exploded View 20 7 5A 6 1 2 3 4 8 9 10 8 11 12 8 5B 5C A B...

Страница 21: ...male connector red outdoor 5C 2 19537 Sealed switch C NO female connector brown outdoor 6 2 17548 10 32 x 1 50 screw pan h phil ss 7 2 18135 4 x 1 25 screw slotted hex washer type 25 8 5 17542 4 20 x...

Страница 22: ...E 40 F 100 F 4 4 C 38 C ELECTRICAL 24 VAC 50 60 Hz COMPUTER SALT PER REGENERATION VARIABLE EFFICIENCY 4 470 GRAINS LBS SALT 3 0 LBS DOSAGE LIST OF CONTAMINANTS REDUCED CAPACITY SALT 13 400 GRAINS 3 0...

Страница 23: ...r Treatment Products The water treatment device s listed on this certificate have met the testing requirements pursuant to Section 116830 of the Health and Safety Code for the following health related...

Страница 24: ...E 40 F 100 F 4 4 C 38 C ELECTRICAL 24 VAC 50 60 Hz COMPUTER SALT PER REGENERATION VARIABLE EFFICIENCY 4 970 GRAINS LBS SALT 3 0 LBS DOSAGE LIST OF CONTAMINANTS REDUCED CAPACITY SALT 14 900 GRAINS 3 0...

Страница 25: ...116830 of the Health and Safety Code for the following health related contaminants None Barium Radium 226 228 None Microbiological Contaminants and Turbidity Inorganic Radiological Contaminants Organi...

Страница 26: ...E 40 F 100 F 4 4 C 38 C ELECTRICAL 24 VAC 50 60 Hz COMPUTER SALT PER REGENERATION VARIABLE EFFICIENCY 4 970 GRAINS LBS SALT 4 5 LBS DOSAGE LIST OF CONTAMINANTS REDUCED CAPACITY SALT 22 400 GRAINS 4 5...

Страница 27: ...116830 of the Health and Safety Code for the following health related contaminants None Barium Radium 226 228 None Microbiological Contaminants and Turbidity Inorganic Radiological Contaminants Organi...

Страница 28: ...DOSAGE LIST OF CONTAMINANTS REDUCED CAPACITY SALT 10 700 GRAINS 2 4 LBS OF SALT 19 200 GRAINS 6 0 LBS OF SALT 22 500 GRAINS 9 0 LBS OF SALT HARDNESS WAS USED AS A SURROGATE FOR BARIUM AND RADIUM REDUC...

Страница 29: ...116830 of the Health and Safety Code for the following health related contaminants None Barium Radium 226 228 None Microbiological Contaminants and Turbidity Inorganic Radiological Contaminants Organ...

Страница 30: ...TURE 40 F 100 F 4 4 C 38 C ELECTRICAL 24 VAC 50 60 Hz COMPUTER SALT PER REGENERATION VARIABLE EFFICIENCY 4 970 GRAINS LBS SALT 3 0 LBS DOSAGE LIST OF CONTAMINANTS REDUCED CAPACITY SALT 14 900 GRAINS 3...

Страница 31: ...116830 of the Health and Safety Code for the following health related contaminants None Barium Radium 226 228 None Microbiological Contaminants and Turbidity Inorganic Radiological Contaminants Organi...

Страница 32: ...ision of Aquion Water Treatment Products 2080 East Lunt Avenue Elk Grove Village Illinois 60007 Main Switchboard 1 847 437 9400 Customer Service 1 800 860 7638 www rainsoft com 2006 RAINSOFT DIVISION...

Отзывы: