Resistance Check of Each Station

CAUTION:

TURN CONTROLLER OFF 

Remove cover of controller to expose terminal strip.

1)

Touch (insert) one probe to the terminal labeled 
COM (for common).

2)

Touch the other probe to the terminal of the station 
(or MV) to be checked.

3)

Check the reading on your multimeter.

Acceptable range:

20-60 Ohms

Less than 20 indicates a short or crossed wires, more
than 60 indicates a broken wire, bad splice or bad
solenoid. Note that stations with several valves will have
proportionately lower resistance. For example, a station
with two valves connected will show half the resistance.

- 10 -

SET METER TO    

200

PROBE

CONNECTIONS

BLACK

COM

RED

RB.DM200.TGuide.mech  2/3/03  10:18 AM  Page 10

Содержание TI-DM200

Страница 1: ...TI DM200 Digital Multimeter TROUBLESHOOTING GUIDE...

Страница 2: ...Troubleshooting the System Resistance check of each station 10 Voltage check of each valve 11 Voltage check of pump relay 12 WARNING This booklet is only intended to be a guide for using this product...

Страница 3: ...d to Step 4 If all of the stations are work ing then you don t have any troubleshooting to do at the controller Step 4 Make a list of all of the stations that are not functioning properly Measure the...

Страница 4: ...ons provided Page 7 of this guide If the fuse is good proceed to Step 7 If the fuse is bad replace it and start again at Step 3 Step 7 Check the 120 V power being supplied to the controller according...

Страница 5: ...e wire nuts inside of the controller where the power lines connect to the transformer 3 Make sure the wire nuts are not touching each other or anything else 4 Turn power back on 5 Touch a probe to eac...

Страница 6: ...e to each of the power lines that run into the terminal strip from the transformer Be careful not to touch the probes together 2 Check the reading on your multimeter Acceptable range 24 28V AC SET MET...

Страница 7: ...e each fuse to test it 3 Touch one probe to each side of the fuse 4 Check the reading on your multimeter Acceptable range Very low or zero Ohms OK A high value or Over Range Indication OL indicates a...

Страница 8: ...ing on your multimeter A good 1 5Vdc battery will read above 80 0mA A good 9Vdc battery will read above 22 0mA 6 Replace the battery CAUTION Avoid electrical shock or instrument damage by not exceedin...

Страница 9: ...emove cover of controller to expose terminal strip 3 Turn controller to manual mode and activate the station or master valve MV to be checked 4 Touch insert one probe to the terminal labeled COM for c...

Страница 10: ...he station or MV to be checked 3 Check the reading on your multimeter Acceptable range 20 60 Ohms Less than 20 indicates a short or crossed wires more than 60 indicates a broken wire bad splice or bad...

Страница 11: ...part of each of the two splice wires leading into the solenoid If it is easier disconnect the solenoid and just check the voltage drop across the two wires coming from the controller 3 Check the read...

Страница 12: ...t the pump relay expose a part of each of the two wires coming out of the relay 3 Touch a probe to each of the exposed wires 4 Check the reading on your multimeter Acceptable range 24 28 V AC Rain Bir...

Отзывы: