Specifications
SPECIFICATIONS
Power Supply
Input range: 10…40V DC and 9…28V AC RMS (50…60 Hz)
Maximum power consumption: 8 Watts (power supply must provide 8 watts at
minimum)
Isolated from power ground
Over-voltage, transient and reverse polarity protected
Flow Meter Input
Input Range: 0�3 Hz…10 kHz
One (1) independent channel
Configurable as square wave 0…30V pulse with 2�5V threshold
Configurable as sine wave, zero-centered with 45 mV threshold
Configurable debounce
Excitation
Output
12V DC source
Voltage
Low: –0�3…1�85V DC
High: 2�5…25V DC
Impedance
Pullup to 12V DC
VDC Current
±50 mA, short circuit current
Response
100 µs/3�5 ms min pulse (high/low speed)
Scaled Outputs
Two (2) independent channels
Isolated from power ground
Over-voltage, transient and reverse polarity protected
Output is multiplexed on the process out pins
Analog Output
Configurable to 0…5V, 0…10V or 4…20 mA
Uncertainty: ±0�1% of reading
16-bit resolution (0…10V and 4…20 mA), 15-bit
resolution (0…5V)
200 ms, 90-10% step response
Sourcing analog output signal
Digital I/O
Six (6) independent channels
Isolated from power ground
Over-voltage, transient and reverse polarity protected
0…30 Volts as input
Debounce
0…5V, TTL, 200 ms 90…10% step response, driving < 0�1 uF
Calculations
Flow
Calculation
± 0�01% uncertainty
Adjustable FIR/IIR filtering
Page 37
June 2020