Model 2018E Operations Manual Rev Apr 2020                Page 

14

 of 39 

FYA Childs

: When a child channel is selected, the monitor will determine if the child is permissive or 

conflicting with the parent channel based on the Program Card.  If permissive, the child will have a 
green border or a yellow border based on the setting of FYA 1-4 Uses Yellow and FYA 5-18 Uses 
Yellow.  If conflicting, the child will have a red border.  These settings can only be modified through 
the RaeComM software. 

The testing defaults for these features should be: FYA Enable set to OFF, FYA Ignore Yellow Conflict set to OFF, 
FYA 1-4 Uses Yellow set to OFF, FYA 5-18 Uses Yellow set to OFF, and all FYA Childs disabled. 

Operations Modified:

  

Conflict  Monitoring

: Normal conflict testing checks active Green and Yellow displays for being 

permissive.  With FYA Enable set to yes and FYA Ignore Yellow Conflict set to yes, the monitor will 
ignore a Yellow-Yellow conflict between a channel yellow and its conflicting child yellow (channel 
marked with a red border) if the Yellow is terminating a flashing Yellow arrow display.  With FYA 
Enable set to yes, any channel check box with a green or yellow border for a child channel will have 
the appropriate display (Green or Yellow) of the child channel monitored for a flashing condition.  A 
flashing input is defined as an input that stays ON for at least 200 milliseconds and no longer than 600 
milliseconds and is OFF for at least 200 milliseconds and no longer than 600  milliseconds.  If the 
input does not flash (stays on solid) the monitor will create a conflict with the conflicting child 
(channel marked with a red border) even though the two channels are usually jumpered as permissive. 

Red Fail Monitoring

: Normal red fail testing ensures that at least one display is active for a channel.  

With this feature active, any channel with a checked box with a green or yellow border for a child 
channel will have the appropriate display (Green or Yellow) of the child channel included when 
checking for a red fail of the parent channel. 

Dual Indication Monitoring

: Normal dual indication testing ensures that only one display for a 

channel is active at a time.  With FYA Enable set to yes, any channel with a child with a green or 
yellow border will have the appropriate display (Green or Yellow) of the child channel included when 
checking for a dual indication. 

Short Yellow Monitoring

: When Flashing Yellow Arrow (FYA) Left Turns are enabled and a channel 

has an FYA setting with a green or yellow border for one of its child channels, then the Yellow of the 
parent channel will be used for terminating the Yellow or Green of the child channel and will be 
checked for short yellow and skipped yellow. 

Short Clearance Monitoring

: When Flashing Yellow Arrow (FYA) Left Turns are enabled and a 

channel has an FYA setting with a green or yellow border for one of its child channels, then that child 
will be checked for short clearance. 

Typical Use

See Application Note AN-005 for detailed examples of this feature.

  The intended field wiring 

connections for this feature are the Red, Yellow, and Green arrows connected to the parent channel and the 
flashing Yellow arrow connected to the Green or Yellow of the permissive child channel.  If channel 1 is the 
protected left turn and will have an FYA display driven by the channel 9 green and the yellow of channel 1 will be 
ON at the same time as the yellow of channel 2 to terminate a flashing yellow arrow, the configuration would be:  
FYA Enable should be ON, Channel 1 will have childs of channel 2 and channel 9, FYA 1-4 Uses Yellow should 
be OFF, FYA 5-18 Uses Yellow should be OFF, and FYA Ignore Yellow Conflict should be ON. 

Care should be taken to insure that the possible phase sequencing does not allow the flashing Yellow arrow to 
terminate while its opposing through is still green.  Be sure to check pre-emption sequencing as well. 

2.6.1.3

 

OPTION SWITCH 3 - +24VDC ENHANCED MONITORING – 24V ENH 

Configuration:

  The setting of the +24VDC Enhanced Monitoring Enable (Option Switch 3 –  24V ENH) DIP 

switch determines if this feature is active.  This feature allows for over voltage monitoring and ripple voltage 
monitoring.  The testing default for this feature should be disabled. 

Operations Modified:

  

+24VDC Monitoring

: When +24VDC Enhanced Monitoring is enabled, the voltage on the +24VDC 

input is also monitored for over voltage monitoring with greater than 30V

DC

 being a fault, and ripple 

voltage monitoring with greater than 1V

RMS

 being a fault.  The 

VDC FAILED

 indicator will flash at a 

5 Hz rate when there is an over voltage fault and the indicator will flash at a 1 Hz rate when there is a 
ripple fault. 

Typical Use

:  This feature can be useful for early detection of power supply failures before they may damage 

equipment 

2.6.1.4

 

OPTION SWITCH 4 – SPECIAL FUNCTION 1 INVERT – SF1 INV 

Configuration:

  The setting of the Special Function 1 Invert Enable (Option Switch 4 –  SF1 INV) DIP switch 

determines if this feature is active.  When the switch is OFF, the Special Function 1 input is sensed as active when 
the voltage is greater than 70V

RMS

  for 550 milliseconds or off when the voltage is less than 50V

RMS

  for 550 

Содержание 2018E

Страница 1: ...ntains technical information for the Model 2018E Conflict Monitor pn 889 3809 02 Revision April 2020 Model 2018E Conflict Monitor Firmware Version 01 05 01 Operations Manual Caltrans TEES 2002 Conflic...

Страница 2: ......

Страница 3: ...BLICATION REPRODUCTION OR USE IN WHOLE OR PART IS NOT PERMITTED EXCEPT UNDER TERMS AGREED UPON IN WRITING ALL REGISTERED TRADEMARKS OF EBERLE DESIGN INC ARE UNDER COPYRIGHT MAINTENANCE NOTE IT IS AN E...

Страница 4: ......

Страница 5: ...emperature Sensor 7 2 4 7 Real Time Clock 7 2 4 8 Up Time Accumulator 7 2 4 9 Configuration Monitoring Beeping Monitor 7 2 4 10 Factory Settings 8 2 4 11 User Unit Information 8 2 5 Fault Monitoring 8...

Страница 6: ...2 7 2 Monitor Reset Log 21 2 7 3 Configuration Event Log 21 2 7 4 Prior Faults Log 21 2 7 5 AC Line Log 21 2 7 6 Signal Sequence Log 21 2 8 Diagnostics 22 2 8 1 Memory 22 2 8 2 Microprocessor Monitor...

Страница 7: ...ndicator 33 4 2 5 CONFLICT Indicator 33 4 2 6 RED FAIL Indicator 33 4 2 7 MULTI IND Indicator 33 4 2 8 YELLOW Indicator 33 4 2 9 PC AJAR Indicator 33 4 2 10 DIAG FAIL Indicator 33 4 2 11 COMM Indicato...

Страница 8: ......

Страница 9: ...escent field display thresholds 2010 Monitor timings with 16 Channels using LED field display thresholds 2010 Monitor timings with 18 Channels using LED field display thresholds The differences betwee...

Страница 10: ...nection terminals in the Controller Assembly For the purpose of conflict determination a signal on any of the Green or Yellow inputs associated with a channel shall be considered as that channel being...

Страница 11: ...nal input is measured approximately 13 000 times per second to provide an accurate true RMS root mean square AC voltage regardless of distortions in the waveform or changes in line frequency Both posi...

Страница 12: ...on 2 to function Typical Connection Unterminated or Preemption circuitry 2 1 7 MC COIL INPUT The monitor provides an input to monitor the state of the Mercury Contactor MC Coil Rear Edge Connector Pin...

Страница 13: ...less When operating in the 2010 mode prior to the monitor transferring the Output relay contacts from the Fault state to the No Fault state a transition state with a duration of 250 milliseconds occu...

Страница 14: ...56 0 Hz or greater than 64 0 Hz The hysteresis from the OFF state to the ON state or vice versa is at least 3VRMS and the line frequency hysteresis is at least 1 0 Hz If the factory option for Low AC...

Страница 15: ...Real Time Clock is initialized to local Pacific Standard Time when the unit is undergoing final test In addition the Daylight Saving Time user option is set to Off The Real Time Clock is preprogrammed...

Страница 16: ...utput relay contacts to the fault condition activates the Stop Time output and illuminates the CONFLICT indicator on the front panel The Signal Sequence log and the Prior Faults log will record this f...

Страница 17: ...f a Flashing Yellow Arrow channel the Yellow will still be used in the parent channel s red fail test regardless of the Yellow Disable jumper setting of the child channel 2010 Mode When the 2010 mode...

Страница 18: ...en of the child channel will be included in the dual indication test for that channel If a Channel has an FYA setting with a yellow border for one of its child channels then the Yellow of the child ch...

Страница 19: ...performed on all channels Test Preformed When a channel has a Green that turns off a conflicting channel cannot display a Green or Yellow for at least 2 7 seconds When each Green turns off a 2 7 seco...

Страница 20: ...formed The Watchdog Timer input Rear Edge Connector Pin 22 is monitored A voltage of less than 4VDC is recognized as a low and a voltage greater than 12VDC is recognized as a high The input must chang...

Страница 21: ...m the flashing state to the solid on state and not falsely trip Typical Use This feature is used to provide additional fault checking for Flashing Don t Walk displays on pedestrian channels Without th...

Страница 22: ...ting with a green or yellow border for one of its child channels then the Yellow of the parent channel will be used for terminating the Yellow or Green of the child channel and will be checked for sho...

Страница 23: ...Indication Monitoring The testing default for this feature should be disabled Operations Modified Dual Indication Monitoring When the Dual Enable switch is OFF for a channel and Green Yellow monitori...

Страница 24: ...hort Yellow testing senses Greens Yellows and Walks as ON when their voltage is above 25VRMS and OFF when below 15VRMS Reds are ON when their voltage is above 70VRMS and OFF when below 50VRMS With LED...

Страница 25: ...ADIAN FAST FLASH Configuration This is a factory option and cannot be changed by the user If this function is required but it is not active contact Reno A E Technical Support for assistance This featu...

Страница 26: ...og When Log Field Changes is enabled the Signal Sequence log will change from recording the state and voltage on every input every 33 milliseconds to checking every 33 milliseconds to see if the state...

Страница 27: ...annel 10 Green driving the flashing yellow arrow for the channel 7 left turn 2 6 4 3 FYA FOR CHANNELS 5 18 USE YELLOW DRIVERS FYA 5 18 USES YEL Configuration This feature is only effective if Flashing...

Страница 28: ...e Yellow arrow parent channel Yellow used to terminate a flashing Yellow arrow and the Yellow of the conflicting child normally the opposing through Yellow ball will be ignored If the Yellow arrow is...

Страница 29: ...te historical record of cabinet operation When the date and time are not available through Port 1 the monitor will use its internal Real Time Clock as a date time stamp for events 2 7 1 TIME CHANGE LO...

Страница 30: ...ostic failure is not reset by a monitor Power Failure 2 8 1 MEMORY The monitor verifies all memory elements on power up or upon reset of a Diagnostics failure A failure of any of the memory tests will...

Страница 31: ...mount of time DC Processor Timeout 6 0020h The DC processor did not respond to a request for data in the required amount of time Temperature Timeout 7 0040h The temperature sensor did not respond to a...

Страница 32: ...AC VOLTAGE INPUTS Normal AC Power Thresholds Dropout 98VRMS Restore 103VRMS Low AC Power Thresholds Dropout 92VRMS Restore 98VRMS AC Line Frequency Dropout 56Hz or 64Hz Restore 57 5Hz and 62 5Hz MC C...

Страница 33: ...l 350 ms FLASHING DON T WALK No Fault 1400 ms Respond 1600 ms Typical 1500 ms Flashing if state changes are 200 ms and 600 ms Typical 500 ms 2010 MODE OF OPERATION 24 VDC LOW No Fault 200 ms Detect 50...

Страница 34: ...n I L Channel 7 Yellow I 11 Channel 14 Yellow I M Channel 3 Green I 12 Channel 3 Yellow I N Channel 16 Yellow I 13 Channel 9 Green I P Channel 17 Yellow I 14 Channel 17 Green I R Channel 10 Green I 15...

Страница 35: ...O x x 5 Channel 13 Red I 4 Ground 6 Special Function 2 I 7 Channel 12 Red I 8 Special Function 1 I 9 Channel 10 Red I 10 Channel 11 Red I Ethernet Connector 11 Channel 9 Red I Pin Function 12 Channel...

Страница 36: ...11 Green 12 Channel 13 Green N Channel 12 Green 13 Channel 14 Green P Channel 13 Green 14 Channel 15 Green R Channel 14 Green 15 Channel 16 Green S Channel 15 Green 16 Programming Card Ajar T Program...

Страница 37: ...Mini USB Port Mini USB Port for communications with Laptop or Modem Field Status LEDs One LED for each field input All field status LEDs are latched if a fault occurs Field inputs that caused the fau...

Страница 38: ...t flashing Don t Walk displays to not conflict with other greens or yellows at the intersection In order to use this feature the RaeComM software must be used to set the channels that this feature is...

Страница 39: ...if the RED ENABLE input is not active The GY Dual Indication Monitoring enable can be used in conjunction with the DUAL ENABLE switches on the circuit board Channels that have their DUAL ENABLE switch...

Страница 40: ...ed every 16 milliseconds by the monitor 4 2 1 FIELD STATUS INDICATORS There are 54 field status indicators one for each field input The display is logically organized into three columns and eighteen r...

Страница 41: ...icate that a Short Yellow or Short Clearance fault has been detected on the field inputs See Section 2 5 4 for more information on a Short Yellow fault and Section 2 5 5 for more information on a Shor...

Страница 42: ...ion change is identified the monitor will enter a configuration fault mode and the audible buzzer will start to beep at a one second rate This is an indication that a change to the current configurati...

Страница 43: ...display mode While in the diagnostic display mode a short press of the front panel RESET pushbutton will advance to the next diagnostic display The diagnostic display sequence is Tap RESET to move be...

Страница 44: ...Disable jumpers installed and Dual Indication is enabled for all channels 4 4 2 1 PERMISSIVE DISPLAYS The left display is the ID Display P1 The right display is the Data Display On the Data Display F...

Страница 45: ...onitoring and the feature is enabled Flashing Yellow Arrow monitoring is enabled 2010 mode of operation is selected LED Thresholds are enabled Watchdog switch is set to enabled Flashing Yellow Arrow I...

Страница 46: ...ally displaying the fault All LEDs except AC POWER and COM are displayed in the same state as they were when the prior fault occurred If the display reverts back to AC Line Voltage while trying to acc...

Страница 47: ...th the monitor to be upgraded by clicking on IDENTIFY in the menu and observing that the monitor is correctly identified by the program 6 On the CONFIG menu choose UPGRADE FIRMWARE 7 On the Code Loade...

Отзывы: