Avoid placing the device in an overly congested rack or directly next to another
equipment rack. Otherwise, the heated exhaust air from other equipment can enter the
inlet air vents and cause the device to overheat.
•
Maintain a minimum clearance of 3 inches (7.62 cm) on the left and right of the device for
the cooling air inlet and exhaust vents.
•
Find a space on the rack which is at least 7 empty square holes in height on the rack
posts.
The SCOPIA TIP Gateway takes up 3 holes (1U) on the posts. You need at least 2 additional
holes to slide the device into the rack.
See
.
Figure 3-3
Height of the SCOPIA TIP Gateway in the rack
•
To mount the SCOPIA TIP Gateway between two posts, the width between the inner sides
of the two posts must be at least 17.7 inches (45 cm). See
RADVISION | Deployment Guide for SCOPIA TIP Gateway Version 8.0
Preparing the SCOPIA TIP Gateway Setup | 11