1.7 CONDENSATION & DRAINAGE
Condensation is formed in the piping of a mitigation system when the air in the piping is chilled below its dew point.
This can occur at points where the system piping goes through unheated space such as an attic, garage or outside.
The system design must provide a means for water to drain back to a slab hole to remove the condensation. The RP,
GP and XP Series Fan MUST be mounted vertically plumb and level, with the outlet pointing up for proper drainage
through the fan. Avoid mounting the fan in any orientation that will allow water to accumulate inside the fan housing.
The RP, GP and XP Series Fans are NOT suitable for underground burial.
For RP, GP and XP Series Fan piping, the following table provides the minimum recommended pipe diameter and
pitch under several system conditions.
See p. 7 for detailed specifications.
Pipe
Diameter
Minimum Rise per Ft of Run*
@25 CFM
@50 CFM
@100 CFM
4”
1/8”
1/4”
3/8”
3”
1/4”
3/8”
1 1/2”
1.8 SYSTEM MONITOR & LABEL
A System Monitor, such as a manometer (P/N 50017) or audible alarm (P/N 28001-2, 28001-4 or 28421), is
required to notify the occupants of a fan system malfunction. A System Label (provided with Manometer P/N 50017)
with instructions for contacting the installing contractor for service and identifying the necessity for regular radon tests
to be conducted by the building occupants must be conspicuously placed in a location where the occupants frequent
and can see the label.
1.9 ELECTRICAL WIRING
The RP, GP and XP Series Fans operate on standard 120V, 60Hz AC. All wiring must be performed in accordance
with National Fire Protection (NFPA) National Electrical Code, Standard #70, current edition, for all commercial
and industrial work, and state and local building codes. All wiring must be performed by a qualified and licensed
electrician. Outdoor installations require the use of a UL Listed watertight conduit. Ensure that all exterior electrical
boxes are outdoor rated and properly sealed to prevent water penetration into the box. A means, such as a weep hole,
is recommended to drain the box.
1.10 SPEED CONTROLS
The RP, GP and XP Series Fans are rated for use with electronic speed controls; however, speed controls are generally
not recommended. If used, the recommended speed control is Pass & Seymour Solid State Speed Control (Cat. No.
94601-1).
RU N
R
ISE
120 VAC
Common
Ground
Capacitor
White
Black
Brn
Brn/Wht
Green
Motor
RP, GP, XP Series Fan Wiring Diagram