background image

Page 2 of 8 

IN007 Rev 

J

 

RadonAway Ward Hill, MA.

HS Series Fan Installation 

& Operating 

Instructions 

Please Read and Save These Instructions. 

DO NOT CONNECT POWER SUPPLY UNTIL FAN IS COMPLETELY 

INSTALLED. MAKE SURE ELECTRICAL SERVICE TO FAN IS 

LOCKED IN "OFF" POSITION. DISCONNECT POWER BEFORE 

SERVICING FAN. 

1. WARNING! 

Do not use fan in hazardous environments where fan electrical system could

provide ignition to combustible or flammable materials.

2. WARNING! 

Do not use fan to pump explosive or corrosive gases.

See Vapor Intrusion Application Note #AN001 for important information on VI applications. RadonAway.com/vapor-intrusion

3. WARNING! 

Check voltage at the fan to insure it corresponds with nameplate.

4. WARNING! 

Normal operation of this device may affect the combustion airflow needed for

safe operation of fuel burning equipment. Check for possible backdraft conditions on all
combustion devices after installation.

5

.

NOTICE! 

There are no user serviceable parts located inside the fan unit.

Do NOT attempt to open.

 Return unit to the factory for service.

6.

All wiring must be performed in accordance with the National Fire Protection

Association’s (NFPA)”National Electrical Code, Standard #70”-current edition for all

commercial and industrial work, and state and local building codes. All wiring must be

performed by a qualified and licensed electrician.

7.

WARNING

In the event that the fan is immersed in water, return unit to factory for service

before operating.

8.

WARNING!  

Do not twist or torque fan inlet or outlet piping as Leakage may result.

9.

WARNING!  

Do not leave fan unit installed on system piping without electrical power for

more than 48 hours. Fan failure could result from this non-operational storage.

10.

WARNING! 

TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO

PERSONS,   OBSERVE THE FOLLOWING:

a) Use this unit only in the manner intended by the manufacturer. If you have questions,
contact the manufacturer. 

b) Before servicing or cleaning unit, switch power off at service panel and lock the service
disconnecting means to prevent power from being switched on accidentally. When the 
service disconnecting means cannot be locked, securely fasten a prominent warning 
device, such as a tag, to the service panel. 

Содержание HS Series

Страница 1: ...The World s Leading Radon Fan Manufaturer HS Series Installation Operating Instructions RadonAway 3 Saber Way Ward Hill MA 01835 www radonaway com P N IN007 REV J 9 13 ...

Страница 2: ... open Return unit to the factory for service 6 All wiring must be performed in accordance with the National Fire Protection Association s NFPA National Electrical Code Standard 70 current edition for all commercial and industrial work and state and local building codes All wiring must be performed by a qualified and licensed electrician 7 WARNING In the event that the fan is immersed in water retu...

Страница 3: ...s than 32 degrees F or more than 100 degrees F The HS Series Fan is thermally protected such that it will shut off when the internal temperature is above 104 degrees F Thus if the HS Series Fan is idle in an area where the ambient temperature exceeds this shut off it will not restart until the internal temperature falls below 104 degrees F 1 3 ACOUSTICS The HS Series Fan when installed properly op...

Страница 4: ...densation can result in system failure and damage the HS Series Fan Condensation is formed in the piping of a mitigation system when the air in the piping is chilled below its dew point This can occur at points where the system piping goes through unheated space such as an attic garage or outside The system design must provide a means for water to drain back to a slab hole to remove the condensati...

Страница 5: ...Fan plugs into a standard 120V outlet All wiring must be performed in accordance with the National Fire Protection Association s NFPA National Electrical Code Standard 70 current edition for all commercial and industrial work and state and local building codes All wiring must be performed by a qualified and licensed electrician Outdoor installations require the use of a U L listed watertight condu...

Страница 6: ... outlet ducting Solvent weld all connections The muffler is normally installed above the roofline at the end of the vent pipe 2 5 OPERATION CHECKS ANNUAL SYSTEM MAINTENANCE ____ Make final operation checks by verifying all connections are tight and leak free ____ Insure the HS Series Fan and all ducting is secure and vibration free ____ Verify system vacuum pressure with Magnehelic Insure vacuum p...

Страница 7: ...proximately 18 lbs Size Approximately 15 W x 13 H x 8 D Minimum recommended inlet ducting greater diameter may always be used HS3000 HS5000 2 0 PVC Pipe HS2000 Main feeder line of 3 0 or greater PVC Pipe Branch lines if 3 or more may be 2 0 PVC Pipe Outlet ducting 2 0 PVC Storage temperature range 32 100 degrees F Thermally protected Locked rotor protection Internal Condensate Bypass ...

Страница 8: ...r attempted by others or if the unit has been abused or misused Warranty does not include damage in shipment unless the damage is due to the negligence of RadonAway RadonAway is not responsible for installation removal or delivery costs associated with this Warranty EXCEPT AS STATED ABOVE THE HS SERIES FANS ARE PROVIDED WITHOUT WARRANTY OF ANY KIND EITHER EXPRESS OR IMPLIED INCLUDING WITHOUT LIMIT...

Отзывы: