Installation Guide
2
Hardware installation
Install the AMC—optional
If an AMC will be added to the CPM, follow the steps in the
Promentum™ Advanced Mezzanine Card
(AMC) Installation Guide
.
Install the rear transition module—optional
The optional RTM can be hot swapped, so
it can be installed before or after the CPM
is installed and while power is applied to
the shelf. This procedure explains where
and how to install the RTM.
Prerequisite:
Install any components not
included with the RTM, such as a hard disk
drive and SFP transceivers. For installation
details, see the
ATCA-5400 Rear Transition
Module Reference
.
1. Identify placement in the back of the
shelf. For example, if the CPM is
installed in slot 1 in the front, the RTM
connects to the back of the shelf in
slot 1.
2. Remove the airflow management
panel, if present, from the back of the
shelf where the RTM will be installed.
3. Remove the RTM from its ESD
shielding bag.
4. Inspect the EMC gasket to make sure it
is free of debris. Lift the RTM ejector
latches to the open position and insert
the RTM into the back panel slot. Use
firm pressure to fully seat the RTM in
the backplane connector. Make sure
the EMC gasket seals the surfaces it
touches.
5. Once the RTM is seated,
simultaneously close both ejector
latches.
6. Tighten the retaining screws in the top and bottom of the RTM panel.
Zone 3
RTM
connector
Ejector
latch
(closed)
Ejector
latch
(closed)
Retaining
screw
Retaining
screw
EMC
gasket