D7024 Reference Guide
Copyright © 1997 Radionics, Inc.
Page 25
Appendix B: Defaults for PROG/0 (continued)
SELECT:
PROG/0
CMND/#
TEST
HISTORY
DISABLE
DRILL
5- PROG OUTPUTS
6- PROG ACCOUNTS
7- PROG FORMATS
8- HISTORY DEFAULTS
1- NACS
1- NAC #1
1- AUTOSILENCE?: YES
2- CONFIGURATION:
Pulsing
3- ZONE ASSIGNS
Zone A = 63
Zone B = 0
Zone C = 0
Zone D = 0
2- NAC #2
1- AUTOSILENCE? NO
2- CONFIGURATION:
Steady
3- ZONE ASSIGNS
Zone A = 62
Zone B = 0
Zone C = 0
Zone D = 0
2- RELAYS
1- LOCAL
1- RELAY #1:
Zone A = 62
Zone B = 0
Zone C = 0
Zone D = 0
2- RELAY #2
Zone A = 63
Zone B = 0
Zone C = 0
Zone D = 0
2- REMOTE 1 (D7035)
Relay1/Zone A = 63
Relay2/Zone A = 62
Relay3/Zone A = 61
Relay4/Zone A = 60
Relay5/Zone A = 58
Relay6/Zone A = 57
Relay7/Zone A = 56
Relay8/Zone A = 53
3- REMOTE 2
Relay1/Zone A = 1
Relay2/Zone A = 2
Relay3/Zone A = 3
Relay4/Zone A = 4
Relay5/Zone A = 5
Relay6/Zone A = 6
Relay7/Zone A = 7
Relay8/Zone A = 8
1- ACCOUNT NUMS
1- NUMBER 1: A8A8
2- NUMBER 2: A8A8
2- PHONE NUMS
1- PHONE #1: FFFF…
2- PHONE #2: FFFF…
3- COMPTR PHONE: FFFF…
3- PHON CONTROL
1- PHONE #1:
1- FORMAT: 4/2
2- MONITOR LINE: YES
3- PULSE RATE: 10PPS
4- TONE FREQ: 1900/1400
5- DIALING TYPE: Pulse Only
1- PHONE #1:
1- FORMAT: 4/2
2- MONITOR LINE: YES
3- TONE FREQ: 1900/1400
4- DIALING TYPE: Pulse Only
4- RPT STEERING
1- NONSUP ALRM: PHN 2 BCKUP
2- SUPVSRY ALRM: PHN 2 BCKUP
3- NONSUP RSTR: PHN 2 BCKUP
4- SUPVSRY ALRM: PHN 2 BCKUP
5- RESET: PHN 2 BCKUP
6- SILENCE: PHN 2 BCKUP
7- TESTS: PHN 2 BCKUP
8- TROUBLE: PHN 2 BCKUP
9- FIRE DRILL: PHN 2 BCKUP
5- RING COUNT: 15
6- COMM. TRIES: 10
7- MACH. BYPASS: YES
1- 4/2 POINT RPT
0- FIRE ALRM D1: 0
1- FIRE RSTR D1: 3
2- WATERFLOW D1: 0
3- SUPERVISE D1: 0
4- TROUBLE D1: 6
5- TRBL RSTR D1: 3
6- DISABLE D1: B
7- DSBL RSTR D1: 3
8- MONITOR D1: 0
9- MORE
1- POINT 1 D2: 1
2- POINT 2 D2: 2
3- POINT 3 D2: 3
4- POINT 4 D2: 4
5- POINT 5 D2: 5
6- POINT 6 D2: 6
7- POINT 7 D2: 7
8- POINT 8 D2: 8
9- MORE
2- 4/2 RPT CODS
0- SYSTM IN TST: F1
1- SYS TEST RST: E1
2- SILENCE: 9F
3- FIRE DRILL: F2
4- FIRE DRL RST: E2
5- OPEN RST RPT: 9F
6- LOW BATTERY: F9
7- LOW BATT RST: E9
8- AC FAILURE: FA
9- MORE
0- AC FAIL RST: EA
1- TEST REPORT: EE
2- OFF NORM TST: FD
3- PHONE 1 TRBL: FB
4- PN 1 TRB RST: EB
5- PNONE 2 TRBL: FC
6- PN 2 TRB RST: EC
7- SYSTEM TROUB: FD
8- SYS TRB RST: FD
3- BFSK RPT CDS
1- OFF NRM TST: FD
2- OPEN/RESET: FD
3- SILENCE: FD
4- FIRE DRILL: FD
5- FIR DRIL RSTR: ED
4- SIA SIL RPT
1- LEFT BYTE: 42 ‘K’
2- RIGHT BYTE: 42 ‘B’
1- CLEAR HSTRY
2- DEFAULT EE
3- ALT 4/2 CDES