Problems with Points

If you incorrectly set the switches on a POPIT you may create both a missing and extra
point. When you find a missing point, perform a Service Walk Test to search for extra
points. See the 

Owner’s Manual (71-06150-000) for test instructions.

Symptom

Diagnosis

Remedy

Point appears as
missing at
command centers
and in reports to
the receiver.

POPIT is not
connected or
incorrectly connected
to the data expansion
loop.

Verify that a POPIT module programmed for
the missing point number is connected to the
data expansion loop of the correct ZONEX
module. Points 9 to 127 connect to ZONEX
module 1. Points 129 to 247 connect to
ZONEX module 2.

Meter each POPIT to verify the polarity of the
data expansion loop. Voltage should be 9 to
13 VDC at each POPIT.

D8128C OctoPOPIT is
installed at the last
address on the
ZONEX bus.

Install a D8125 POPEX and D9127 POPITs
for points 121-127 on ZONEX 1 and for points
241-247 on ZONEX 2.

Sensor loop switch (1
to 8) is turned off on
OctoPOPIT.

If the sensor loop switch on an OctoPOPIT is
turned off for a programmed point, the point
reports as missing.

POPIT is not
programmed correctly.

Verify that the switches on the POPIT are set
for the missing POPIT number. Switches set
incorrectly can cause both missing and extra
POPITs.

Performing a Service Walk Test to search for
extra points may help diagnose the problem.

Points
intermittently
appear as
missing. Points
are erratic.

Problem with data
expansion loop.

See 

Problems with Data Expansion Loop.

Debounce Count
parameter set at 1. If
an off-board point is in
transition between
normal and faulted
conditions as the
panel scans it, it
appears as missing.

It is recommended that the Debounce Count
be left at the default of 2.

Decreasing the Debounce Count to 1 may
cause points to appear as missing. Increasing
the Debounce may cause missed alarms.

www.PDF-Zoo.com

firealarmresources.com

Содержание D7000 Series

Страница 1: ...nicator 12 D7212Control Communicator 13 QuickReferenceTerminalDescription 14 Introduction This reference contains the very basic information a trained installer needs to install and troubleshoot a D9000 D7000 Series Control Communicator system See the D9000 D7000 Series Operation and Installation Manual 74 07692 000 and the D9000 D7000 Series Approved Applications Compliance Guide 74 07693 000 for...

Страница 2: ...point tested for 60 seconds After 60 seconds the display returns to the points to test message Extra Points display default text If you incorrectly set the switches on a POPIT to a point number that is not in your program for the panel the default text for that point number PT displays when you fault the point The Program Record Sheet shows the default text for all points Faulting the point a seco...

Страница 3: ...UNTESTED N EXT SERVICE WALK 246 PTS TO TEST 245 PTS TO TEST 244 PTS TO TEST POINT TEXT POINT TEXT POINT TEXT 1 PTS TO TEST 0 PTS TO TEST IDLE TEXT POINT TEXT Test a device Text displays 60 seconds Test a device Text displays 60 seconds Test a device Test a device CLEAR CLEAR CLEAR www PDF Zoo com firealarmresources com ...

Страница 4: ...ed at the last address on the ZONEX bus Install a D8125 POPEX and D9127 POPITs for points 121 127 on ZONEX 1 and for points 241 247 on ZONEX 2 Sensor loop switch 1 to 8 is turned off on OctoPOPIT If the sensor loop switch on an OctoPOPIT is turned off for a programmed point the point reports as missing POPIT is not programmed correctly Verify that the switches on the POPIT are set for the missing ...

Страница 5: ...ores input from all points in the same area programmed for sensor reset during sensor reset Two points are programmed with the same address Points programmed with the same address do not function correctly Check to be certain that you have not duplicated point addresses Panel transmitts PT BUS TROUBLE reports Erroneous alarm and or trouble reports may follow PT BUS TROUBLE report Erroneous alarm a...

Страница 6: ...nd 24 share a common circuit breaker Check wiring and devices connected to these terminals for shorts or grounds If only one POPEX module is connected to the panel POPEX module may be incorrectly connected to the panel or Data Expansion Loop may be disconnected from POPEX module Check POPEX module for correct connections to the D9412 D9112 and the Data Expansion Loop If you find missing points the...

Страница 7: ... programmer connector J7 3 Check each conductor in the data power cord for continuity AC induction through the on board point sensor loops the DATA BUS or the ZONEX BUS 1 Verify a proper earth ground at terminal 10 2 Disconnect on board point sensor loops the DATA BUS terminals 30 31 and the ZONEX BUS terminals 25 26 27 28 After plugging in the programmer the panel transmits SDI trouble reports fo...

Страница 8: ... contact your telephone company repair service Communications Failure Follow the Phone Line Trouble procedure to verify that there is no problem with the phone lines at the installation If the phone lines are good monitor the lines preferably at the receiver for the symptoms listed below Symptom Diagnosis Remedy Panel does not connect to central station The D136 relay in J10 for ground start phone...

Страница 9: ...ts Can hear ring with test set at receiver location Line card in receiver may be faulty Review receiver manuals for trouble shooting procedures The D9412 D9112 reaches a busy signal for all ten attempts to reach the receiver Calls are not reaching the receiver 1 Verify that correct prefixes and phone numbers for the receiver have been programmed into the D9412 D9112 2 Verify that the phone lines a...

Страница 10: ...hor t 0 0 1 3V DC PER IPH ERAL DE VICE W IR ING Z ONE X O UT 1 ZO NEX IN 1 Z ONE X O UT 2 ZO NEX IN 2 ZON EX P OWE R Z ONE X CO MM ON O p eratio n Mo nito r Puls es W he n No rma l F licke rs W h e n Rin ging PROG CONN RE D Y ELLOW GRE EN B LA CK 17 0 582 3 00 2 3 2 P OW ER DAT A BU S A CO M MON RED GRO UND S TA RT YE L RE D Re set P in Dis able All E xce pt B atter y C harg ing An d Pro gram min ...

Страница 11: ... O UT 1 ZO NEX IN 1 ZO NE X O UT 2 ZO NEX IN 2 ZO NEX POW ER Z ON EX CO MMO N O p e ra tion M o n itor P uls es W he n N o rm al Fli cke rs W h en R ing ing PROG CONN RED YELLOW G RE EN B LA CK 1 7 0 582 3 002 3 2 POW ER DAT A BUS A CO MMO N R ED GR OU ND START YE L RE D R e se t P in D is abl e A ll E xce p t Ba tte ry C h arg ing An d Pro gr am mi ng GR N ST EADY O R PU LSE Charging Status N F P...

Страница 12: ...2 ZO NEX IN 2 ZO NEX PO WE R Z O NEX CO MMO N O p era tio n M o nit or P uls es W he n No rm al Fli cke rs W h e n R in gi ng PROG CONN RE D YELLO W GRE EN BLACK 1 7 058 23 0 02 3 2 PO W ER DATA BU S A CO MMO N RED GR OU ND STAR T Y EL R ED Re se t P in D is ab le A ll Ex ce pt Ba tte ry C h arg in g An d P rog ra mm in g GR N ST EADY O R PU LSE C harging Status N F P A Style 3 5 Signaling Line Ci...

Страница 13: ...Z ON EX IN 2 Z ON EX PO WE R ZO NEX CO MMO N Op erati on Mo nit or Pu lse s W h en No rm al F lick er s W h en Rin gi ng PROG CONN RE D Y EL LO W GREEN BLA CK 17 05 82 3 0 02 3 2 PO W ER DATA BU S A CO MMO N R ED G R OU ND S TART YEL RED Re se t P in Di sab le All Ex ce pt Ba tte ry C ha rg in g An d P ro gra mm in g GRN ST EADY OR PU LSE Char ging Status N F P A Style 3 5 Signaling Line Circuits ...

Страница 14: ... or alarm verification Shares circuit breaker with terminals 6 and 7 D136 Plug in Relay required Install a D136 in socket K1 for output at terminal 8 9 COMMON Terminal 9 is common for Auxiliary Power Steady or Pulsed Alarm Power Alternate Alarm Power and Switched Aux Power terminals 3 6 7 and 8 10 EARTH GROUND Connect to earth ground A cold water pipe or grounding rod is preferred Do not connect t...

Отзывы: