D2012 Installation Manual

Page 12

8/11/97   P/N 35122B

© 1997 Radionics

Battery Charging Circuit
Float Charge
The float voltage for the battery charging circuit is 13.9
VDC. Deduct any continuous load for devices connected
to the panel from 860mA to find the maximum current
available for charging. At 13.9 VDC the battery is fully
charged and is maintained with a trickle charge of approxi-
mately 5mA.

Battery Discharge/Recharge Schedule (No AC Power)

Discharge Cycle
AC OFF

The Keypad indicates trouble.
AC Fail reports if programmed.

13.9 VDC

Charging float level.

12.1 VDC

Low Battery reports.

10.2 VDC

Panel shuts down below 10.2 VDC

Recharge Cycle
AC ON

Panel restarts, battery charging begins,
AC restoral report sent.

13.0 VDC

Battery restoral reports sent, the keypad
returns to normal operation.

13.9 VDC

Battery float charged.

Power Outputs

D2012 Circuit Protection
Two self-resetting protection devices protect the panel
from short circuits on both the auxiliary and alarm power
outputs.

Bell circuit protection:  A short on the alarm power
output while the bell is ringing disables this output until it
times out or you perform a panel reset.

Extra Power for Keypads
You may need to add one or more D8132 Battery Charger/
Power Supply Modules for the number of keypads you
want to use. Figure 10 shows the D8132 powering
keypads in a stand-alone configuration.

For UL Certificated accounts, use a UL listed power
supply. The D8132 is not UL listed as a stand-alone power
supply for fire and burglary applications.

Figure 10:  Power for Keypads

Telephone

Dialing Format
You can program the panel to use DTMF or pulse dialing.
See 

Phone Parameters in the Program Entry Guide.

Communication Failure
After 5 attempts to reach the receiver (10 attempts if two
phone numbers are programmed), the panel goes into
communication failure. The panel clears any reports in its
phone buffer. The panel sounds a tone at the keypad
indicating trouble.

Pressing the Clear key silences the tone. When communi-
cation restores (a report is acknowledged by the receiver),
the keypad returns to normal operation.

D2012 and D8132 (or other power supply) must share
COMMON
:  Note that Figure 10 shows the common from
the D8132 module connected to both keypad’s common
and the Aux- (common) terminal on the panel. Do not
connect the stand-alone power supply to earth ground.

www.PDF-Zoo.com

firealarmresources.com

Содержание D2012

Страница 1: ...8 11 97 P N 35122B 1997 Radionics D2012 Control Communicator Installation Manual www PDF Zoo com firealarmresources com ...

Страница 2: ...so you will be advised of your right to file a complaint with the FCC if you believe it is necessary The telephone company may make changes in its facilities equipment operations or procedures that could affect the operation of the D2012 If this happens the telephone company will provide advance notice in order for you to make the necessary modifications to maintain uninterrupted service If you ex...

Страница 3: ...uxiliary Power 8 Checking Continuous Current Draw 8 External Relays 8 Connect the Points 8 Point 1 8 Points 2 to 6 9 Point Wiring Diagram 9 Make the Telephone Connections 10 Power Up 10 Program the Panel 10 Unlock the Standby Switch 10 Fill out the Delay Chart 11 Test the System 11 Detailed Description 11 Primary AC Power Circuit 11 Secondary DC Power 11 Power Outputs 12 Telephone 12 Points 13 Key...

Страница 4: ...5 Keypad Installation Sheet 31945 Security System User s Guide 71 07117 000 Getting Started with Your Security System 71 07372 000 Three wire data cable assembly 15 07032 000 D206 Keypad Each D206 includes the following D206 Keypad Installation Sheet 31946 Security System User s Guide 71 07117 000 Getting Started with Your Security System 71 07372 000 Three wire data cable assembly 15 07032 000 D2...

Страница 5: ...es into the enclosure Do not make any connections yet Wire Length Wire Length for points is limited only by the resistance on the loop and potential EMI Electro Magnetic Interference problems Wire resistance on the Point 1 sensor loop must be less than 50Ω Measure the wire resistance before installing smoke detectors Short the end of line resistor before metering the wire Resistance on the sensor ...

Страница 6: ...y required for fire and combined fire burglary systems In order to meet standby battery requirements use the Radionics D126 12v 7 0Ah battery for fire and combined fire burglary systems Charge the Battery as You Work Lock the Standby Switch Locking the pin in the standby position allows you to charge the battery as you install the detection devices and keypads Lock the pin down now See Figure 2 Wi...

Страница 7: ...stems 1 Add together the current draws for all devices connected to the negative alarm output terminal This total is the current required for the Normal Standby Condition NSC This total must be less than 140mA 2 Subtract the NSC current required calculated in step 1 from the Primary Alarm Current 860mA The difference is the Alarm Current available for the Alarm Output terminals In formula format P...

Страница 8: ...812 is a powered supervised point The panel monitors the Point 1 sensor loop for normal shorted or open conditions Programming determines how the panel responds to those conditions See the D2812 Program Entry Guide Terminal 11 provides positive voltage to 2 wire detection devices Terminal 12 the loop return is isolated from earth ground The Keypad Reset function interrupts power to this sensor loo...

Страница 9: ...oute the power for the detectors through a D133 or D134 Relay Module The relay module must be connected to one of the panel s external relay outputs programmed for the reset function See RELAYS in the Program Entry Guide for programming instructions Heat Detectors and Other Dry Contact Initiating Devices Connect any number limited by the Authority Having Jurisdiction Burglary Devices Connect any n...

Страница 10: ...e keypad or using the D5200 make sure the Standby Switch is locked down See Figure 8 If you re using the D5200 Figure 9 shows the location of the programming jack See the D5200 Programming Operation Manual for instructions on using the program mer Unlock the Standby Switch When you re finished programming move the Standby Switch to the normal position See Figure 8 The panel sends a RE BOOT report ...

Страница 11: ...ailure The panel indicates an AC power restoral 60 seconds after power restores to the terminals labeled 16 5VAC Secondary DC Power A 12V 4 0 Ah sealed lead acid rechargeable battery Radionics D1240 supplies secondary power for auxiliary and alarm outputs The battery also powers the system during interruptions in primary AC power Lead Acid Batteries Only The panel charging circuit is only calibrat...

Страница 12: ...his output until it times out or you perform a panel reset Extra Power for Keypads You may need to add one or more D8132 Battery Charger Power Supply Modules for the number of keypads you want to use Figure 10 shows the D8132 powering keypads in a stand alone configuration For UL Certificated accounts use a UL listed power supply The D8132 is not UL listed as a stand alone power supply for fire an...

Страница 13: ...the POINT CODES Group in the Program Entry Guide for the correct programming for points used for keyswitches Installation Connect the end of line resistor for the point at the keyswitch so that the switch shorts the resistor when it operates An open on the circuit produces an alarm if the area is armed and a trouble if it is disarmed See Figure 12 Keyswitch Operation Shorting and restoring the poi...

Страница 14: ...uctions You must use a 12 VDC option for the Easikey installation See Easikey Installation and Operation Instructions Easikey is not for use in UL installations Connect the Easikey door controller to the panel using a D133 Relay Module as shown in Figure 13 Make certain to connect the common for the Easikey s 12 VDC supply to the terminal labeled Aux on the panel Figure 13 Keyswitch www PDF Zoo co...

Страница 15: ...llation documents to determine suitability When using four wire smoke detectors install a suitable power supervision unit according to the manufacturer s instructions Use the D133 or D134 Relay Module to provide reset capability In fire applications with one 7 0Ah 12 VDC battery the panel supports an auxiliary output of 140mA and a bell output of 720mA configured as necessary For additional loadin...

Страница 16: ...otection must be provided The D2012 control panel is suitable for Central Station Grade C applications It is suitable for Central Station Grade B applications when the Model D2012 DACT unit is installed with a UL listed Local sounding device Also suitable for Central Station Mercantile Grade AA applica tions when installed with the Model D8122 derived channel subscriber terminal unit The D2012 con...

Страница 17: ...res 24 hours of standby plus four minutes 067 hrs of alarm operation at the end of the 24 hour period You must use battery ampere hour Ah calculations to verify compliance The formula in the next column includes a 10 contingency factor for depletion of battery capacity with age NFPA 72 Chapter 2 Ampere Hour Calculation Formula Total B ___ x 24 Hrs Total C ___ x 067 Hrs 10 Contingency Total Ah requ...

Страница 18: ... 30 _____ 125 _____ D223 _____ 30 _____ 30 _____ 140 _____ _______ _____ ___ _____ ___ _____ ___ _____ _______ _____ ___ _____ ___ _____ ___ _____ _______ _____ ___ _____ ___ _____ ___ _____ _______ _____ ___ _____ ___ _____ ___ _____ _______ _____ ___ _____ ___ _____ ___ _____ _______ _____ ___ _____ ___ _____ ___ _____ _______ _____ ___ _____ ___ _____ ___ _____ _____ Total A _____ Total B _____...

Страница 19: ...32 122 F 0 50 C Relative Humidity 5 85 at 86 F 30 C non con densing Arming Stations D202A Keypad D205 Keypad D206 Keypad D220A Keypad D223 Keypad Keyswitch Easikey Compatible Enclosures D2803 Standard Enclosure D8103 Universal Enclosure D8109 Fire Enclosure D8108A Attack Resistant Enclosure Compatible Accessories See the Radionics Product Catalog for complete list D126 12V 7 Ah Rechargeable Batter...

Страница 20: ...for continuously powered devices 500mA at 10 2 to 13 9 VDC Protected against overcurrent by self resetting device 8 Aux Aux Power Negative common for Aux Power and Relay Outputs 9 Ext1 External Relay 1 Connect D133 or D134 relay for Form C Dry Contact 10 Ext2 External Relay 2 Connect D133 or D134 relay for Form C Dry Contact 11 1 Positive Point 1 Positive Power for Point 1 Switched for sensor rese...

Отзывы: