Radio Thermostat CT50 Скачать руководство пользователя страница 6

PG

 6

• “Fan out” wires as illustrated with CT50 below the wall 

opening.  As in the example: fan out the wires so that the 

C wire is above the C terminal, the W above the W. This 

allows the CT50 to fit snugly to the wall.

Caution

 

Do not allow wires to touch each other or parts on thermostat. 

• Wires will position behind the CT50 and up over the 

terminal area.

• Do not bunch wires behind the CT50.  Feed any slack 

back into the wall opening.

Connect Your Wires

   

• Connect labeled wires only to a terminal with the same letter label.

• Insert the wire in the terminal well and tighten the screw securely.

NOTE: If you wish you can mount the CT50 to the wall first, and then connect the wires.

• The CT50 can be externally powered with a power source rated from 18V to 24V, AC or DC, at 
100ma or greater. If used, connect to the C and RH terminals (no polarity).

C B O WW2 YY2RHRCG A

 

R

H

Y

G

C

W

from HEAT/COOL system

Содержание CT50

Страница 1: ...ned for use with 24 volt AC and millivolt systems with a separate 24VAC power adapter This thermostat requires 24VAC power at the C terminal Each thermostat relay load should be limited to 1 0 amp higher amperage may cause damage to the thermostat Caution To avoid electrical shock and to prevent damage to the furnace air conditioner and thermostat disconnect the power supply before beginning work ...

Страница 2: ...re are unusual heating conditions such as in direct sunlight near a lamp radio television radiator register fireplace near hot water pipes in a wall or near a stove on the other side of a wall Do not locate in unusual cooling conditions such as on a wall separating an unheated room or in a draft from a stairwell door or window Do not locate in a damp area This can lead to corrosion that will short...

Страница 3: ... carefully before removing any wiring from existing thermostat Wires must be labeled before they are removed THERE IS NO STANDARD COLOR CODE When remov ing wires from their terminals ignore the color of the wires and LABEL THEM by the lettered terminal where they were screwed Label the wires one at a time You must label all the wires before you proceed With all wires labeled remove them from the o...

Страница 4: ...tandard 18 24V AC or DC wall transformer A constant power source is required when using a radio module IMPORTANT If you have both RH and RC you need to remove the jumper wire between these 2 terminals Prepare Wires Please follow these guidelines for safe and secure wire connections You will need at least 2 6 of wire for each of your connections to the CT50 If you do not have enough wire splice add...

Страница 5: ...rom Furnace RC C Y RH W C W Y RH G 4 Wire Heat Cool From Furnace G C Y RH W C W RH G 3 Wire Heat From Furnace C RH G W From Furnace C W C W RH RH 2 Wire Heat From Furnace W RH A W RH A 3 Wire Zoned Hot Water WIRES WIRES WIRES WIRES WIRES G RH C W2 W Y Y2 RH G 2 stage Cool 2 stage Heat From Furnace Y2 C W Y W2 C B or O W2 Y RH G 5 Wire Heat Pump w Aux Heat From Furnace RH C O or W2 B G Y G C B or O...

Страница 6: ...nal area Do not bunch wires behind the CT50 Feed any slack back into the wall opening Connect Your Wires Connect labeled wires only to a terminal with the same letter label Insert the wire in the terminal well and tighten the screw securely NOTE If you wish you can mount the CT50 to the wall first and then connect the wires The CT50 can be externally powered with a power source rated from 18V to 2...

Страница 7: ...he CT50 to the wall with the screws provided 4 If you are mounting the CT50 to sheet rock or if you are using the old mounting holes use the plastic anchors provided 5 Mark first and drill a 3 16 in 4 8mm hole for the insert at each screw location then mount the unit Screw to wall Place wires like this C B O WW2 YY2RHRCG A from HEAT COOL system C B O WW2 YY2RHRCG A C W Y RH G Wall Wires Wall ancho...

Страница 8: ...HVAC switch selections changes Install 3 AA Batteries This is a 24VAC thermostat the 3 AA batteries are for memory backup only and are not required for operation Install 3 AA alkaline batteries required following the marked polarity in the battery compartment Put the lower battery in negative end first against the spring then push the positive end in Then insert the last 2 batteries as shown With ...

Страница 9: ...ome for a month or more you should replace the batteries as a precaution against battery failure in your absence Always use new alkaline batteries Failing to replace the batteries when necessary could cause the thermostat to lose power or malfunction If the thermostat loses power then the thermostat will not control the temperature which could result in your HVAC system not functioning as you inte...

Страница 10: ...e COOL select 3 If you want efficient but slower recovery 2 stage HEAT 1 stage COOL select 4 2 stage HEAT 2 stage COOL select 5 NOTE For 2 stage systems your CT50 can recover from a temperature setback in 2 ways 1 Fast Recovery This uses your 2nd stage to bring the house to Target Temperature This may use slightly more energy 2 Efficient Recovery This uses the 2nd stage to bring your house to with...

Страница 11: ... Touch the icon and raise the Target Temperature to 90 o F allow the system 2 minutes to respond Verify that heat is blowing from the system Return the Target Temperature to a nomal setting Return mode to OFF by pressing the mode button If you have a heat pump leave in off for 4 minutes before checking COOL TO CHECK COOL do not operate AC if the outside temp is below 65 o F Set the mode to COOL by...

Страница 12: ...ermostat is digital and your desired heat or cool temperatures can easily be set on the large touch screen with the buttons A minimum 4 minute off time protects the compressor from damage The CT50 must be externally powered with a power source rated from 18V to 24V AC or DC at 100ma or greater Connect 24VAC to the C and RH terminals no polarity The 24VAC C wire is the other side of the 24VAC heati...

Страница 13: ... RH wire to the RH terminal This connects the heat power STEP 2 Connect the W wire to the W terminal This connects the heat STEP 3 Connect the G wire to the G terminal on the thermostat This connects the fan STEP 4 Set HVAC selection switches to NORMAL and If you have gas or oil heat set the HEAT TYPE to GAS If you have electric heat set the HEAT TYPE to ELEC Your system is now connected to the CT...

Страница 14: ...RC G WIRES 5 Wire Heat Cool STEP 1 Connect the W wire to the W terminal This connects the heat STEP 2 Connect the Y wire to the Y terminal This connects to the cooling compressor STEP 3 Disconnect the jumper between RH and RC terminals STEP 4 Connect the RH wire to the RH and the RC wire to the RC terminals This connects power STEP 5 Connect the G wire to the G terminal This connects the fan STEP ...

Страница 15: ...nal or B wire to the B This connects the change over valve If you have both O and B connect only the O wire to the O terminal and DO NOT connect B to B terminal see wire reference under Trane for B wire terminal STEP 2 Connect the W2 wire to W2 terminal This connects the auxiliary heat STEP 3 Connect the Y wire to Y terminal This connects the compressor STEP 4 Connect the R wire to RH terminal Thi...

Страница 16: ...l This connects the fan STEP 7 Set HVAC selection switches to NORMAL and If you have gas or oil heat set the HEAT TYPE to GAS If you have electric heat set the HEAT TYPE to ELEC Your HVAC system is now connected to the CT50 Please Go To Page 6 W RH A WIRES 3 Wire Zoned Hot Water For Solenoid valve or Motor valve connect the wires based on diagrams below to the correct terminal on the CT50 USE ONLY...

Страница 17: ...ge COOL control or 2nd stage compression for a heat pump G or F G FAN control C or X C 24VAC power to power thermostat NOTE TRANE uses B for this connection H H External Humidifier DH DH External De Humidifier EX EX external fresh air baffle B B Heat pump changeover cool to heat powered in heat O O Heat pump changeover heat to cool powered in cool B and O IMPORTANT If there are both B and O wires ...

Страница 18: ...power thermostat W or W1 W2 2nd stage HEAT X2 Emergency heat do not connect tape off Zoned Hot Water 2 wire Your Wires Thermostat Terminal R RH W W 3 Wire Motor Driven Valves R or 5 RH power W or 4 W heat ON Y or G or 6 the 3rd wire A heat OFF 3 Wire Solenoid Valves R RH power W A heat ON Y or G the 3rd wire W heat OFF Customer support support radiothermostat com 888 607 5824 or www radiothermosta...

Отзывы: