Wiring Diagrams
Installation Guide CT100
Accessory Wiring
Zoned Hot Water Heat
For Solenoid or Motor valves,
connect the wires based on the
diagrams to the correct terminal on
the CT100.
• USE ONLY IN HEAT MODE.
• The CT100 must be powered by
24v ac.
The third wire on your valve may be called 6, Y, or G (see the Wire
Reference Table on page 23.
CT100
RH
A
W
MOTOR VALVE
RH
W
A
CT100
RH
A
W
SOLENOID VALVE
RH
A
W
Wiring Diagrams
Installation Guide CT100
Wire Reference Table
Possible Wires What They Control
R or V or VR
RH and RC Single power for HEAT and COOL
RH or 4
RH Power for HEAT (RH not connected to RC jumper clip
removed)
RC
RC Power for COOL (RH not connected to RC jumper clip
removed)
W
W Heat control
W2
W2 2nd stage HEAT or heat pump auxiliary heat
W3
W3 3rd stage HEAT or 2nd stage of 2 stage auxiliary heat
Y
Y COOL control or 1st stage compression for heat pump
Y2
Y2 2nd stage COOL control or 2nd stage compression for
a heat pump
G or F
G FAN control
C or X
C 24VAC power (to power thermostat) NOTE: TRANE uses B
for this connection
H
H External Humidifi er
DH
DH External De-Humidifi er
EX
EX external fresh air baffl e
B
B Heat pump changeover (cool to heat, powered in heat)
O
O Heat pump changeover (heat to cool, powered in cool)
B and O
IMPORTANT: If there are both B and O wires (Trane pump
products) DO NOT CONNECT B to B terminal. Instead,
connect B to C terminal. If not a Trane product, tape off B.
E
n/a Emergency heat (do not connect, tape off )
L
n/a System monitor (do not connect, tape off )
T
n/a Outdoor sensor (do not connect, tape off )
23
Содержание CT100
Страница 3: ...Radio Thermostat Getting Started 3 ...
Страница 11: ...Radio Thermostat Setup 11 ...
Страница 17: ...up 00 r 4 ain l e is o t Radio Thermostat Wiring Diagrams 17 ...
Страница 26: ...Product Overview 26 ...
Страница 34: ...Customization 34 ...
Страница 42: ...Thermostat Schedule 42 ...
Страница 48: ...CT100 THERMOSTAT Z WAVE REFERENCE ...