MAINTENANCE INSTRUCTIONS

 

 

 

40 

6.7 Diagnostics 
 
 

 

Error codes: 

 

E01 

Ionisation Lock Out  

E02 

Safety Thermostat Tripped 

H2O  Low Water Pressure Alarm                          
E05 

Heating Sensor Malfunction 

E14 

Air Pressure Switch Tripped  

E22 

Parameter Programming Request  

 

 
 
 
 
 
 

 

Function codes : 

 

Code  

Function  

Description 

07 

Flue test function active 

(Chimney-Sweeper)  

Pressing the “service” button for 7 seconds 
activates the Flue test function. Pressing the 
boiler off button deactivates the function. 
The Flue test function operates the boiler at the  
maximum heating pressure for 15 minutes 
without any modulation. The function is useful 
for combustion testing. 

08 

Frost Protection             

Central heating circuit 

The function is activated when the heating 
sensor senses a temperature of 5 °C. The 
boiler operates at minimum gas pressure with 
the 3-way diverter valve in the winter position. 
The function is deactivated when the 
temperature detected by the sensor reaches 
30°C.   

31 

Incompatible Remote Control  

Function active when the remote control 
connected is not compatible with the printed 
circuit board . 

 

Содержание RS 30 E

Страница 1: ...maintenance instructions CE 0694 RS 30 E RAD ING MAN INST 1205 1 DIGITECH AUSTRALIA Technical specification RADIANT BRUCIATORI S p A Montelabbate PU ITALY ENGLISH Instruction Manual for model RS 30 E...

Страница 2: ...llation requirements pag 9 3 3 Unpacking pag 10 3 4 Installation boiler pag 11 3 5 Water connections pag 12 3 6 Gas connection pag 13 3 7 Electrical connections pag 14 3 8 Flue connections pag 16 4 Co...

Страница 3: ...rised personnel 6 1 General warnings pag 30 6 2 Boiler inspection pag 30 6 3 Accessing the boiler pag 31 6 4 Draining the central heating system pag 32 6 5 Wiring diagrams pag 33 6 6 Troubleshooting p...

Страница 4: ...ples plastic bags polystyrene etc must not be left within reach of children in that these items represent a potential hazard and must be disposed of in a responsible manner Before carrying out any cle...

Страница 5: ...ndards This fundamental safety requirement must be checked and verified In case of doubt have the electrical system checked by a qualified electrician The manufacturer will not be held liable for any...

Страница 6: ...its simplicity the wall mounted appliance is equipped with all the appropriate accessories required to make it a fully independent boiler capable of satisfying domestic hot water production and centra...

Страница 7: ...ssure heating bar 3 Min working pressure heating bar 0 3 Dimensions Boiler casing size Width mm 450 Height mm 800 Depth mm 320 Weight net kg 43 Hydraulic connections Central Heating Flow connection Ce...

Страница 8: ...GENERAL INFORMATION 5 55 5 G 64 5 HR 80 CWI 102 HF 9 320 720 85 82 280 85 286 82 35 800 130 148 450 2 2 Dimensions HR HEATING RETURN 3 4 HF HEATING FLOW 3 4 G GAS 3 4 CWI COLD WATER INLET 1 2...

Страница 9: ...MBER 6 IGNITION ELECTRODE 7 MAIN BURNER 8 CIRCULATING PUMP WITH AIR VENT 9 ELECTRONIC GAS VALVE 10 3 bar PRESSURE RELIEF VALVE 11 SYSTEM DRAIN VALVE 12 ISPECTION FLUE 13 HEATING SENSOR 14 HEATING SAFE...

Страница 10: ...VENT 9 AUTOMATIC AIR VENT VALVE 10 3 bar PRESSURE RELIEF VALVE 11 PRESSURE GAUGE 12 FLUE HOOD 13 WATER PRESSURE SWITCH 14 HEATING SENSOR 15 AUTOMATIC BY PASS 16 AIR PRESSURE SWITCH 17 ELECTRIC FAN LEG...

Страница 11: ...r Temperature display When the boiler is switched off at the switch on the control panel the word OFF appears on the display The central heating frost protection system nevertheless remain enabled If...

Страница 12: ...tallation and should be left with the appliance but do not over ride in anyway statutory obligations 3 2 Installation requirements Please refer to local and national standards in force in the Country...

Страница 13: ...of the product Packing materials plastic bags polystyrene nails etc must not be left within reach of children in that these items represent a potential hazard A Place the packed appliance on the floor...

Страница 14: ...1 2010 In order to allow access to the interior of the boiler for maintenance purposes it is important that the necessary clearances indicated in figure 1 are respected To make the installation easier...

Страница 15: ...and noise coming from the system do not use pipes of reduced diameter short radius elbows or severe reductions in the cross sections of the water passages To facilitate the installation the boiler is...

Страница 16: ...inimum of a 22 mm diameter pipe with an uninterrupted supply from meter to boiler and comply with current standards and regulations Check the internal and external seals of the gas supply system A gas...

Страница 17: ...nnection to the mains electricity supply must be via a single pole switch with at least 3 millimetres gap between open contacts mounted upstream of the appliance Make sure that the positions of the li...

Страница 18: ...connect the wires to the terminal board B as follows Connect the earth wire normally coloured green yellow to the terminal marked with the earth symbol Connect the neutral wire normally coloured blue...

Страница 19: ...ies to prevent the penetration of foreign bodies or atmospheric agents ONLY for use with Horizontal concentric flue kit 60 100 mm as per manufacturer s kit No 82101LP ONLY for use with manufacturer s...

Страница 20: ...nds to that of the mains supply networks gas electricity water Check that the power supply voltage to the boiler complies with the data plate 230 V 50 Hz and that the live neutral and earth wires are...

Страница 21: ...al to 1 2 bar see fig 3 and that the code H2O does NOT appear on the control panel display On completion make sure that the filling tap R is perfectly closed 4 3 Flushing the system Failure to flush a...

Страница 22: ...alues The device comes into operation in the following cases The heating water temperature goes below 5 C the burner starts automatically until the water temperature reaches the 30 C The room temperat...

Страница 23: ...r ignited if the system still emits noises the operations must be repeated until all the air has been removed Check the pressure in the system If the pressure has fallen re open the filling tap until...

Страница 24: ...ry set at 36 x 5 180 8 D H W pump overrun timer Not applicable 00 90 default 18 The overrun timer can be modified Expressed in steps of 5 sec factory set at 18 x 5 90 9 Minimum gas pressure setting 00...

Страница 25: ...n 2 Activate the On Off switch while keeping buttons and pressed Wait for P00 to appear on the display 3 Release buttons and 4 Keep button S pressed and use button to select the parameter to modify 5...

Страница 26: ...TER 2 GAS SUPPLY 6 Use buttons and to modify the value of the parameter 00 natural gas 01 lpg 7 Press and release button S to confirm The parameter number P02 will appear on the display 8 Switch off t...

Страница 27: ...k on again to render the new parameter operative PARAMETER 5 WATER HAMMER PREVENTION Not applicable PARAMETER 6 CENTRAL HEATING TIMER 6 Use buttons and to modify the value of the parameter within the...

Страница 28: ...ack on again to render the new parameter operative PARAMETER 8 D H W PUMP OVERRUN TIMER Not applicable 5 3 Regulating the gas pressure PARAMETER 9 MINIMUM GAS PRESSURE SETTING NATURAL GAS 0 22 KPA UNI...

Страница 29: ...8 Switch off the appliance and switch it back on again to render the new parameter operative 9 Press button Press button S for 7 seconds until the number 07 flashes on the display chimney sweep funct...

Страница 30: ...If a remote control is installed an extra interface board must be installed to control the zone valves Then set the parameter at 01 7 Press and release button S to confirm The parameter number P15 wil...

Страница 31: ...MAINTENANCE INSTRUCTIONS 28 5 4 Gas Data Refer to page 4 ADJUSTING POWER OUTPUT GAS PRESSURES KW 19 21 23 25 27 29 NG kpa 0 3 0 37 0 45 0 52 0 6 0 68 ULPG kpa 1 08 1 3 1 55 1 78 2 02 2 25...

Страница 32: ...reassembled 6 select the new gas type by changing parameter no 2 see Parameters table 5 1 7 to convert the appliance from L P G to Natural Gas proceed with the min and max gas pressure adjustment 8 in...

Страница 33: ...the condition of the combustion chamber and flame When required check that the combustion is correctly regulated and if necessary proceed in line with section Commissioning the boiler Remove and clea...

Страница 34: ...ds fig 1 and then up fig 1 Left and right side panel Remove the fixing screws at the front and lower edge of the side panel to remove Grasp the bottom of the panel move it sideways and then upwards to...

Страница 35: ...n point and locate the other end of the hose in a suitable drainage system Open the system drain valve see fig 1 Open the air vents on the radiators starting with the highest and moving down the syste...

Страница 36: ...e blue brown white black black brown blue orange PRINTED CIRCUIT BOARD DIGITECH SM20019 COD 76677LA blue Key IG Main Switch PA Air Pressure switch TS Safety thermostat SR Heating sensor EV Fan ER Ioni...

Страница 37: ...connected place plate A back to position and then the front case panel Connecting the outside temperature sensor Option Connect the wires to the terminal board inside the instrument panel as follows...

Страница 38: ...connect the remote controller wires When the wires have been connected place plate A back to position and then the front case panel Connecting the remote controller and the telephone control option C...

Страница 39: ...option remote controller board cod 65 00030 Option remote lock out indicator Remote control and zone valves wiring For the installation of a zone valve p c b it is necessary to access the main p c b f...

Страница 40: ...HERM Telephone control Terminal block Outside temperature sensor option Option remote lock out indicator Zone valve management option remote controller board cod 65 00030 cod 40 00017 Remote control z...

Страница 41: ...overning the correction is reported in figure 1 The selection of the compensation curve is determined by the maximum delivery temperature Tm and the minimum outdoor temperature Te N B The y axis value...

Страница 42: ...g REPLACE PART h CONNECT THE IONISATION ELECTRODE WIRE E02 SAFETY THERMOSTAT TRIPPED 95 C i THERMOSTAT MALFUNCTION OR OUT OF CALIBRATION j THERMOSTAT CABLE DISCONNECTED i REPLACE PART j CHECK THE WIR...

Страница 43: ...tton deactivates the function The Flue test function operates the boiler at the maximum heating pressure for 15 minutes without any modulation The function is useful for combustion testing 08 Frost Pr...

Страница 44: ...THE COMPANY RESERVES THE RIGHT TO APPLY VARIATIONS WITHOUT PRIOR NOTIFICATION NEITHER WILL THE COMPANY BE HELD RESPONSIBLE FOR ANY INACCURACIES IN THIS HANDBOOK DERIVING FROM PRINTING OR TRANSLATION...