R2KA 34 /20 - RAD - ING - Inst.Manual - 2002.1_CSA
2. FIRST START-UP
SUPPOR
T CENTER
PARAMETER
DESCRIPTION
RANGE
FUNCTION
P19
MINIMUM HEATING SETPOINT
THROUGH THIS PARAMETER YOU CAN SET THE USER-
ADJUSTABLE MINIMUM HEATING TEMPERATURE.
68 - 104
THE VALUE IS EXPRESSED IN °F
P20
MAXIMUM HEATING SETPOINT
THROUGH THIS PARAMETER YOU CAN SET THE USER-
ADJUSTABLE MAXIMUM HEATING TEMPERATURE.
104 - 190
THE VALUE IS EXPRESSED IN °F
P21
MAXIMUM DOMESTIC SETPOINT
THROUGH THIS PARAMETER YOU CAN SET THE USER-
ADJUSTABLE MAXIMUM DOMESTIC TEMPERATURE.
113 - 167
THE VALUE IS EXPRESSED IN °F
P22
SET POINT
∆
T DELIVERY-RETURN
(ONLY WITH MODULATING PUMP AND RETURN PROBE CONNECTED)
THROUGH THIS PARAMETER YOU CAN SET THE TEMPERATURE
DIFFERENCE BETWEEN DELIVERY AND RETURN.
32
32 = DISABLED
18 - 72
THE VALUE IS EXPRESSED IN °F
P23
MODULATING PUMP MINIMUM SPEED
(ONLY WITH MODULATING PUMP AND RETURN PROBE CONNECTED)
THROUGH THIS PARAMETER YOU CAN SET THE MINIMUM SPEED
VALUE OF THE MODULATING PUMP DURING A REQUEST TO
OPERATE IN HEATING MODE.
50 - 70
THE VALUE IS EXPRESSED IN
PERCENTAGE
P24
MODULATING PUMP MAXIMUM SPEED
(ONLY WITH MODULATING PUMP AND RETURN PROBE CONNECTED)
THROUGH THIS PARAMETER YOU CAN SET THE MAXIMUM
SPEED VALUE OF THE MODULATING PUMP DURING A REQUEST
TO OPERATE IN HEATING MODE.
70 - 100
THE VALUE IS EXPRESSED IN
PERCENTAGE
P25
D.H.W STORAGE TANK TEMPERATURE SETPOINT
(FOR STORAGE BOILERS ONLY)
THROUGH THIS PARAMETER YOU CAN SET THE PRIORITY
STARTING VALUE OF THE STORAGE TANK, COMPARED TO THE
USER ADJUSTABLE D.H.W SETPOINT.
37 - 48
THE VALUE IS EXPRESSED IN
°F
(PRE-SET AT
48
°F
)
P26
MODBUS ADDRESS
BY MEANS OF THIS PARAMETER, IT IS POSSIBLE TO SET THE
ADDRESS OF THE BOARD ON MODBUS IN ORDER TO PERFORM
A CASCADE SYSTEM.
0
0 = DISABLED (PRE-SET BY
DEFAULT)
1 - 16
BOILER
NUMBERING
FOR
MODBUS