38
R1KG 24 - RAD - ING - Manuale - 1806.1_SK.2
2 T
a
bell
a p
a
r
a
metr
i_
MI
A
H
4
_
fir
m
.L
1
8
1
E
_
E
N
2. FIRST START-UP
SUPPOR
T
C
ENTRE
PARAMETER
DESCRIPTION
RANGE
FUNCTION
P13
HEATING FAN MAXIMUM SPEED ADJUSTMENT
THROUGH THIS PARAMETER YOU CAN SET THE FAN MAXIMUM
SPEED IN HEATING PHASE, THAT CORRESPONDS TO THE
MAXIMUM BURNER POWER DURING A REQUEST TO OPERATE
IN HEATING MODE [SEE CHAPTER ‘HEAT CAPACITY DIAGRAM
(KW) –ELECTRIC FAN FREQUENCY (HZ)’].
THE VALUE IS PRE-SET BASED ON THE SET POWER (SEE
PARAMETER P00) AND ON THE GAS TYPE (SEE PARAMETER
P02)
VALUE SET FOR
PARAMETER P12
- 203
THE VALUE IS EXPRESSED IN
HERTZ
(1HZ = 30 RPM)
P14
STARTING STEP ADJUSTMENT
THROUGH THIS PARAMETER YOU CAN SET THE FAN SPEED
DURING START-UP
THE VALUE IS PRE-SET BASED ON THE SET POWER (SEE
PARAMETER P00) AND ON THE GAS TYPE (SEE PARAMETER
P02)
VALUE SET FOR
PARAMETER P10
- 203
THE VALUE IS EXPRESSED IN
HERTZ
(1HZ = 30 RPM)
P15
ANTI-LEGIONELLA FUNCTION
(FOR STORAGE BOILERS ONLY)
THROUGH THIS PARAMETER YOU CAN ACTIVATE/DEACTIVATE
THE “ANTILEGIONELLA” HEAT TREATMENT OF THE STORAGE
TANK. EVERY 7 DAYS THE WATER TEMPERATURE INSIDE
THE STORAGE IS HEATED BEYOND 60 °C THUS GENERATING
A BURNING HAZARD. KEEP UNDER CONTROL SUCH
DOMESTICH HOT WATER TREATMENT (AND INFORM THE
USERS) TO AVOID UNFORSEEABLE DAMAGES TO PERSONS,
ANIMALS AND PROPERTY. A THERMOSTATIC VALVE SHOULD
BE INSTALLED AT THE DOMESTIC HOT WATER OUTLET TO
AVOID ANY BURNS.
0 - 1
0 = DISABLED
1 = ENABLED (PRE-SET
BY DEFAULT ON STORAGE
BOILERS ONLY)