22
R1K 25 RAIN - RAD - ING - Man.Inst. - 1901.1_SK.2_firm.L224C_AHS
1 Coll
egamenti
el
ettrici
opzionali_SE_T
A_CR_MIAH4
- R2K_EN
1. INSTALLATION
INST
ALLER
1.1.17. OPTIONAL ELECTRICAL
CONNECTIONS
The cables should be inserted inside the boiler
using the cable glands ‘P1’ and ‘P2’ placed under
the board (see fig. 1). Make a hole on the cable
gland, smaller than the cable diameter, to make
sure that the air cannot pass through.
To wire the optionals below:
• (SE) EXTERNAL TEMPERATURE PROBE COD.
73518LA
• (TA) ENVIRONMENT THERMOSTAT
• (CR) REMOTE CONTROL OPEN THERM COD. 40-
00017
use the terminal placed inside the control panel as
follows:
DANGER
Cut off the voltage from the main switch.
› remove the front casing of the boiler (see chapter
ACCESSING THE BOILER); unscrew the screws
and remove plate “A” (see fig. 2).
› After removing the plate, connect the electrical
cables to terminal “B” (see fig. 2):
· For the external temperature Probe connect
the two non-polarized conductors to the Se-
Se contacts.
· For the environment Thermostat or Remote
control, first remove the bridge on the Ta-
Ta contacts and then connect the two non-
polarized conductors to the Ta-Ta contacts.
After performing these operations, remount plate
“A” and the front casing.
NB:
In case of simultaneous presence of external probe and remote
control, the modulation board only sends the external temperature
value to the remote device without using it for modulation.
The communication between board and remote control takes
place independently from the boiler's operating mode and after
establishing the connection, the used interface on the board is
disabled and the display shows the symbol ‘
’.
P1
P2
L
N
Se
Se
A
Ta
Ta
B
SE
TA
CR
fig. 2
fig. 1
Содержание R1K 25 RAIN
Страница 59: ......