75
Appendix A. Changing the Control Unit IP address
1.
Turn ON Zond-12e Control Unit, computer configured according to p. 10 of
present User’s Manual, start up the Prism2 software.
2.
Enter
Radar / Connection settings
Menu option. The Ethernet connection
settings dialog box appears.
Fig. A1. Ethernet connection settings dialog box.
3.
In IP address section will be Control Unit present IP address of. As default it is
192.168.0.10
4.
Click the
Unit settings
button. The Zond-12e Ethernet settings dialog box
appears.
Note:
Please use the
Connection troubleshooter
if the error message
appears.
Fig. A2. Zond-12e connection settings dialog box.
5.
Enter the new desirable Control Unit IP address in the
IP address
section.
6.
Enter the new desirable Control Unit subnet mask in the
Subnet mask
section.
7.
Press the OK button.
Note:
Please use the
Connection troubleshooter
if the error message
appears.
8.
Press the OK button of Ethernet connection setting dialog box.