background image

 
 
CONNECTION DIAGRAM FOR DETECTOR PART CSA-SGA / CSA-FUV 

 
Alternatively, you may connect up to 5 detectors (mixed CSA-SGA and CSA-FUV) to any single 
zone by connecting them as follows. By this method, you may use 1 controller for up to 5 different 
zones. 
 
 

SENSITIVITY ADJUSTMENT FOR CSA-SGA / CSA-FUV 
 

 
Adjustment for the CSA-SGA is by DIP 
switches located on the back of the detector. 
Switches 1 & 2 select the sensitivity; switch 3 
adds a transient delay and switch 4 is only 
used on model CSA-SGA/R to incorporate a 
470

 resistor. 

 

 

 
Adjustment for the CSA-FUV is by DIP 
switches located on the back of the detector. 
Switches 1 & 2 select the sensitivity; switch 3 
is not used and switch 4 is only used on model 
CSA-FUV/R to incorporate a 470

 resistor. 

 
 

 
 
OPERATING FEATURES 
 
 

On the fascia of the controller, are two red buttons, and a series of lamps that warn of the 

specific functions of the controller. The ‘Power’ lamp will flash green once every five seconds to 
instruct the user that all is well. Each of the five ‘Zone’ lamps has two colours - Red for Alarm; 
Yellow for Fault. In the event of an alarm from a Detector connected to that zone, the lamp will 
illuminate Red and a buzzer will sound continuously, indicating the location of the alarm. Pressing 
the ‘Silence’ button, followed by the ‘Reset’ button can reset this. 
 

 

In the event of a zone fault, the specific zone lamp will flash yellow once every five seconds and 
the buzzer will beep with each flash. Again pressing the ‘Silence’ button, followed by pressing the 
‘Reset’ button can reset this. 
 
 
The final ‘Fault’ lamp will illuminate to indicate a fault condition with the Controller. The lamp will 
flash once every five seconds and the warning buzzer will beep with each flash. In the event that 
the ‘Power’ lamp is extinguished, and the ‘Fault’ lamp continues to show fault, this indicates that 
the batteries are in a low condition and should be replaced as soon as possible. 
 

 

Each Cig-Arrête Smoke Detector is fitted with an integral red LED lamp, visible once the Detector 
has been installed. Immediately after power up, the LED on each of the Detectors will flash for a 
period of two minutes. This indicates that the Detector is learning its environment and as such is 
functioning correctly. If an alarm is sensed, the Detector transmits the condition to the controller 
and then repeats the two-minute flash period again, thus allowing the location of the alarm to be 
visually confirmed. The Detectors will reset themselves automatically once the cause of the alarm 
has been removed. 
 

 

Under normal conditions, a set of batteries should operate for up to 12 months, although this will 
be affected by the number of alarms, and the length of the alarm condition being allowed to 
remain for a continued period of time. 
 
EXTERNAL POWER SUPPLY (CSA-SMPSU) 
 

 

 
The system may be powered from 
a 6-Volt D.C. power source, which 
may be connected to the external 
supply terminals provided on the 
terminal block on the controller 
back-plate. 
 
In addition, a Remote Alarm 
Indicator (part no. CSA-RAI), may 
be connected to allow remote 
monitoring of the system 
controller. 
 

 

The controller has been fitted with 
a selector switch on the back of 
the main printed circuit board. The 
removal of this jumper will 
facilitate the use of a ‘Silent Mode’ 
of operation, when used in 
conjunction with the Remote 
Alarm Indicator. 
 
 

 
 

NOTE: 

ONCE THE SYSTEM IS POWERED, SHOULD THE BATTERIES OR THE 

POWER SUPPLY BE REMOVED, IT IS NECESSARY TO WAIT FIVE MINUTES BEFORE 
RE-POWERING THE SYSTEM. FAILURE TO DO SO MAY RESULT IN INACCURATE 
OPERATION OF THE SYSTEM. 

Отзывы: