INSTRUCTIONS
SWISH® FA INSTALLATION
RAB Lighting is committed to creating high-quality, aff ordable, well-designed and energy-effi cient LED lighting and controls that make it easy for electricians to install
and end users to save energy. We’d love to hear your comments. Please call the Marketing Department at 888-RAB-1000 or email: [email protected]
SWISH FA-IN-1122
RAB WARRANTY:
RAB’s warranty is subject to all terms and conditions found at rablighting.com/warranty
WIRING
OPERATION
MAINTENANCE
TROUBLESHOOTING
CAUTION: FOR BATTERY BACKUP FIXTURE.
Voltage can be present
in
BATTERY.
To prevent high voltage from being present on
output leads, Inverter connector must be open. Do not join
BATTERY
connector until installation is complete and AC
power is supplied to the emergency driver
(Fig. 7).
NOTE:
Make sure that the necessary branch circuit wiring
is available. An UNSWITCHED AC source of power is required.
The emergency driver must be fed from the same branch
circuit as the LED driver.
CAUTION:
Do not use any supply voltage other than 120-277V
50/60 HZ.
Although no routine maintenance is required to keep the
emergency driver functional it should be checked periodically to
ensure that it is working. The following schedule is recommended:
1. Visually inspect the charging indicator light monthly. It should
be illuminated.
2. Test the emergency operation of the fi xture at 30-day intervals
for a minimum of 30 seconds.
3. Conduct a 90-minute discharge test once a year. Fixture would
operate at reduced illumination for a minimum of 90 minutes.
1. Is the fi xture grounded properly?
2. If the charging indicator light does not illuminate after pressing
the test button, check if battery is connected properly.
Note: These instructions do not cover all details or variations in equipment
nor do they provide for every possible situation during installation, operation
or maintenance.
1. Connect
UNSWITCHED HOT
fi xture lead to
HOT AC
supply line.
2. If using an
UNSWITCHED
circuit, connect
UNSWITCHED
and
SWITCHED
lines together.
3. If using a
SWITCHED
circuit, connect
SWITCHED HOT
AC fi xture
lead to the external.
4.
For 0-10V dimming connect
DIM
(+) purple and
DIM
(-) pink
leads to dimming connections.
5. All unused leads must be capped and insulated.
6. After installation is complete, supply AC power to the fi xture and
connect the
BATTERY.
7.
When power is on, the fi xture should be on and the Charging
Indicator Light should illuminate to indicate the battery is
charging.
8. Once the BATTERY has charged for at least one hour a short
duration test may be performed by pressing the test button.
9.
After the battery has charged for 24 hours a long duration test
can be performed by shutting power to the fi xture.
1. When AC power is applied, the charging indicator light is
illuminated indicating that the
BATTERY
is being charged.
2. When power fails the standby power automatically switches
to emergency power
(internal battery)
operating at reduced
illumination. The emergency driver supplies standby power for
a minimum of 90 minutes.
3. When AC power is restored the emergency driver
automatically returns to charging mode.
Easy Answers
rablighting.com
Visit our website for product info
Tech Help Line
Call our experts: 888 722-1000
Answered promptly - [email protected]
Free Lighting Layouts
Answered online or by request
© 2021 RAB LIGHTING Inc.
BATTERY BACKUP MODELS
73657-RAB
FIG. 7
LIGHT
FIXTURE
INSIDE FIXTURE
BATTERY
Pink/DIM–
Black/Switched Line
Green/Ground
White/Neutral
Black/Unswitched Line
Purple/DIM+
BACKUP
DRIVER
BATTERY
CONNECTOR:
CONNECT
ONLY AFTER
AC SUPPLY
POWER IS
CONNECTED