background image

INSTRUCTIONS

HIGH BAY - EMERGENCY BATTERY BACKUP

RAB Lighting is committed to creating high-quality, affordable, well-designed and energy-efficient LED lighting and controls that make it easy for electricians to install 

and end users to save energy. We’d love to hear your comments. Please call the Marketing Department at 888-RAB-1000 or email: [email protected]

IMPORTANT

READ CAREFULLY BEFORE INSTALLING FIXTURE. RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE.

Fixtures must be wired in accordance with the National Electrical Code and all applicable local codes. Proper grounding is required for 
safety. THIS PRODUCT MUST BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE INSTALLATION CODE BY A PERSON FAMILIAR WITH 
THE CONSTRUCTION AND OPERATION OF THE PRODUCT AND THE HAZARDS INVOLVED. 

WARNING: Make certain power is OFF before installing or maintaining fi xture. No user-serviceable parts inside.

PLEASE READ AND FOLLOW ALL SAFETY INSTRUCTIONS
WARNING: 

AC power must be off  before proceeding with assembly or installation of emergency LED driver.

IMPORTANT: 

An unswitched AC power source of 120VAC to 277VAC is required. This device is designed for use in fi xtures listed for dry, 

damp and wet locations.

IMPORTANT: 

Emergency LED driver should be charged for 24 hours every 6 months during storage.

CAUTION: 

• 

Make sure all electrical connections confi rm to the National Electrical Code and all applicable local regulations. 

• 

Do not let power supply cords touch hot surfaces. 

• 

Do not mount near  gas or electric heaters. 

• 

Use with grounded UL Listed dry, damp or wet location rated fi xtures.

• 

The equipment is intended for ordinary locations and for permanent installation into one or more listed emergency luminaires.

• 

Battery is rechargeable Li-ion type and must be recycled or disposed of properly.

Do not use this emergency driver with accessory equipment other than recommended by manufacturer; failure to follow this may 

cause an unsafe condition. Servicing should only be performed by qualifi ed service personnel. Do not use this emergency driver for 

other than intended use. 

IMPORTANT: 

Indicator

 (LED light)

 illuminated indicates battery in charge mode when AC power is applied. It is recommended and 

required by applicable code to test emergency LED driver to ensure proper function of the system; push the test switch every thirty

 (30)

days to ensure the emergency driver is functioning by illuminating the light source. Conduct a ninety (90) minutes discharge test one 

(1)

time per year; LED light source should be illuminated for 90 minutes.

TESTING SYSTEM: 

The emergency battery requires a charge minimum of one 

(1) 

hour before testing the circuit. A full charge requires 

twenty-four

 (24)

 hours.

EMHB30

Содержание EMHB30

Страница 1: ...d be charged for 24 hours every 6 months during storage CAUTION Make sure all electrical connections confirm to the National Electrical Code and all applicable local regulations Do not let power supply cords touch hot surfaces Do not mount near gas or electric heaters Use with grounded UL Listed dry damp or wet location rated fixtures The equipment is intended for ordinary locations and for permanen...

Страница 2: ... indicating the batter is charging A short term discharge test may be conducted after the backup nano inverter has been charging for 1 hour charge for 24 hours before conducting a long term discharge test Select a suitable location on the ceiling for hangable device Install the hook to backup nano inverter and fix it with the screws Install the ring bolt to the backup nano inverter and fix it with t...

Страница 3: ...TE AC N WHITE AC N Pink Driver Dim Purple Driver Dim 0 10V Dimming Output AC Input 0 10V Dimming Input 0 10V DIMMER Red SWITCH HOT Wall Switch Purple DIM Pink DIM Dimmer Dimmer Blue Driver N Brown Driver L Cap off if not connected EMERGENCY DRIVER IMPORTANT Dimming wires must be connected to Fixture LED Driver dimming wires for EM to function properly RECOMMENDATION Emergency output power 20 outpu...

Страница 4: ...een Earth Purple Dim Pink Dim Test Switch Indicator Light Green Ground Green Ground Red 12Vdc Out 12V AUX BLACK UNSWITCH HOT WHITE AC N Pink Driver Dim Purple Driver Dim 0 10V Dimming Output AC Input 0 10V Dimming Input Red SWITCH HOT Wall Switch Purple DIM Pink DIM Blue Driver N Brown Driver L EMERGENCY DRIVER 12VDC EMHB30 IN 0822 Easy Answers rablighting com Visit our website for product info Te...

Отзывы: