8W Emergency Exit
Box
Installation
Instructions p.2
For models: EBM
T: 0800 195 0006 F: 0870 043 3946
E: [email protected] www.redarrowtrading.com
Red Arrow Trading
Elsworth House, Herries Road South
Sheffield, S6 1QS
Maintenance
1.
Failed lamps should be replaced promptly to avoid damage to the luminaire.
2.
Repairs should only be carried out by a qualified electrician. Only replacement components authorised by Red Arrow should
be used. Disposal of replaced components should be in accordance with the component manufactures instructions.
3.
Special care should be taken if it is required to open the fitting beyond that which is necessary for re-lamping the fitting
may still be live even though the mains supplies have been disconnected. In these circumstances disconnect the battery
supply immediately.
4.
Servicing, cleaning, lamp replacement etc. Should only be carried out after the fitting has been made electrically safe.
5.
Cleaning of luminaires should be carried out at regular intervals not only to ensure good optical performance but also to
ensure that dirt does not accumulate to impair the electrical or thermal safety of the fitting.
6.
To avoid damage to the luminaire failed lamps should be replaced promptly with a lamp of the recommended type and
rating, and of the same manufacture following these instructions.
7.
The rated life of miniature T5 fluorescent tubes operating continuously on emergency maintained / sustained circuits is
some 5,000 hours. Therefore all lamps operating continuously in maintained / sustained fittings should be replaced on a 4
to 6 monthly maintenance schedule to maintain maximum system integrity.
8.
NB Due to the small diameter of T5 fluorescent tubes manufacturers are unable to fit electrode shields as fitted to larger
T12 tubes and therefore some blackening of the tube ends is to be expected as a normal characteristic.
9.
Batteries are the Nickel Cadmium type and have a normal service life of approximately 4 years.
10.
Battery replacement should be carried out after 4 year period.
Month
Test
Year 1
Year 2
Year 3
Year 4
Year 5
signed
date
signed
date
signed
date
signed
date
signed
date
1
Functional
2
Functional
3
Functional
4
Functional
5
Functional
6
1 hour
7
Functional
8
Functional
9
Functional
10
Functional
11
Functional
12
1 hour
3 hour
Product complies with
all relevant European
standards
Product is suitable for
mounting on flammable
material
F
Guarantee
This product is guaranteed for a period of 1 year from the date of purchase. The guarantee is invalid in the case of improper use, tampering, removal of the Q.C. date label, installation in
an improper working environment or installation not according to the current edition of the I.E.E. Wiring Regulations (BS7671). The guarantee is also invalidated if the luminaire has
been Mega tested. Should this product fail during the guarantee period it will be replaced free of charge, subject to correct installation and return of the faulty unit. We do not accept
responsibility for any installation costs associated with the replacement of this product. e reserve the right to alter specifications without prior notice.