background image

Page 6 

CO2 CONTROL 

 

OVERVIEW

  

 

 “Pound for pound, dollar for dollar, the CGC-1e offers one of the most advanced environmental / light / hydro and 
CO

2

 control system on the market”. 

 
 
“SUPPLEMENTAL CO

2

 

 

 

Let's talk about ... Carbon Dioxide. CO

2

 is present in relatively low quantities, (300-600 PPM) in your normal, generic, run of 

the mill everyday air. But plant growth can be increased and accelerated if the level of CO

2

 is increased to, let’s say... 1000 -

1500 PPM. For this reason, the CGC-1e can control CO

2

 distribution for those people who prefer to use supplemental CO

2

.  

There are some inherent dangers associated with using CO

2

. Here are some of the rules to remember when using CO

2

A)  

Cylinders (bottles) of compressed CO

2

 should never be stored inside the growing area or anywhere else where the 

temperature may rise above 100’f. 

B)  

The growing area should not be occupied while CO

2

 is in operation. (Get out!) 

C)  

Do not enter the growing area until the CO

2

 has been exhausted. (Stay out!) 

D)  

CO2 is heavier than air and will accumulate towards the ground.  (Don’t lie down on the job!) 

E)  

In high enough concentrations CO

2

 can kill!!!  The OSHA maximum “Personal Exposure Level” is 5000 PPM. 

 

*Note: 

The CGC-1e CO

2

 control system can be used for both compressed CO

2

 cylinders, and generators. The CO

2

 receptacle is 

120vac. Compressed CO

2

 cylinders require an approved regulator / flow gage and a valve.  

 

 If  optimum  CO

2

 “mileage” is desired, a self contained air conditioner or other “Closed loop” cooling method is highly 

recommended. A closed loop system will regulate temperatures within the zone allowing you to extend the CO

2

 maximum 

cycle time thus reducing CO

2

 use dramatically. 

  

 Another method of reducing heat build up includes utilizing “Ventilated light hoods”. Just be sure to make the ventilation 
system of the hood as airtight as possible so that your precious CO

2

 is not being drawn out of the area by the ventilated hood 

exhaust fan. 
 If sufficient CO

2

 is provided and the proper level of nutrients and light is available, a 35% increase in growth rate is possible. 

However if you suspect the higher temperatures are adversely affecting the plants, a shorter CO

2

 cycle may produce better 

results. Remember that a shorter CO

2

 cycle duration translates to increased CO

2

 usage. Each application is different, so there is 

some work involved in finding the optimum set-up.  

 
 

CO2 CONTROL MODES

 

 

 The CGC-1e provides both a standard timed CO

2

 mode and an optional integrated CO

2

 PPM control mode. Of course, the time 

clock will ensure CO

2

 is only used during the “day”. The optional PPM-1c sensor is one of the most precise and efficient 

method of distributing CO

2

. The PPM-1c control will be described later, but first, let me explain how to operate the standard 

timed CO

2

 system.  

*Note: The pre-wired “jumper-plug” is used to bypass the PPM controller functions when the PPM-1c is not used.  
           Make sure it is properly connected when running the timed CO

2

 sequence.    

 
 

TIMED CO

2

 CONTROL MODE 

 

1)

 

The CO

2

 Inject Duration timer can be set from 1 second to 40 minutes. When the CGC-1e’s standard 24-hour timeclock 

switches to “daytime”, the CO

2

 cycle begins. The CO

2

 outlet is energized for a predetermined amount of time using the 

CO

2

 Inject Duration timer.  

 
2)

 

The CO

2

 Frequency timer works in conjunction with the CO

2

 Injection timer. This timer can be set from 1 minute -  

8 hours. During the CO

2

 cycle, the CO

2

 outlet will be turned off for the amount of time set on this timer. The CO

2

 Inject 

Duration timer and the Frequency timer continue to recycle until the thermostat or humistat turns on the fans. When the 
exhaust is turned back off, the CO

2

 cycle is re-started. 

 

Note: These two timers continue to function in harmony with the optional PPM-1c sensor. The PPM-1c simply tells the 
CGC-1e whether the CO

2

 level being measured is above or below the adjustable set point on the PPM-1c. The timers still 

control the CO

2

 “ON” and “OFF” time. 

 
 

Содержание CGC-1e

Страница 1: ...arranty All components are warranted by R M Supply against defects in workmanship and materials under normal use for 3 years from the date of purchase The CGC 1e is 100 maintenance free and does not r...

Страница 2: ...ller CO2 ON timer Optional PPM 1c quick connect Hydro OFF timer 2 Light outlets CO2 OFF timer Hydro mode selector switch Temperature controller 2 Hydro pump outlets Fuse protected 15 amps 120 volts Co...

Страница 3: ...t control the CGC 1e refer to the Timers section of this manual Set the Hydro and CO2 timers to your desired settings before continuing Refer to Timers 8 The 24 hour timeclock can now be set Push in t...

Страница 4: ...reatest accuracy provide the CGC 1e with plenty of fresh air The enclosure is designed to allow air to pass over the humidity sensor HUMIDITY CONTROLLER The CGC 1e utilizes a de humistat to control ve...

Страница 5: ...t the Hydro and CO2 timers correctly HYDROPONICS TIMERS The Hydroponic outlet can be configured to cycle one of two ways 24 hours a day or during the daytime only Simply moving the Hydro Mode selector...

Страница 6: ...t being drawn out of the area by the ventilated hood exhaust fan If sufficient CO2 is provided and the proper level of nutrients and light is available a 35 increase in growth rate is possible However...

Страница 7: ...e PPM 1c controller consists of an infrared detector capable of measuring atmospheric CO2 levels from 0 to 5000 PPM The PPM 1c is powered by an 18 vdc to 24vac power supply When it is connected it wil...

Страница 8: ...ation to the CGC 1e The PPM 1c is powered by a 18 24volt power supply MASTER LIGHTING CONTROLLER MLCs The MLC 4 and MLC 4a Master Lighting Controllers are the best devices for controlling up to 4 HID...

Страница 9: ...ems to be quite high Make sure your area is sealed You may want to install a motorized damper to seal your exhaust fans when they are OFF Even though the CGC 1e operates a standard timed release seque...

Страница 10: ...lbs Relay operations Minimum 100 000 electrical 10 000 000 mechanical MAINTENANCE 1 Consult the troubleshooting chart for a listing of the most common problems 2 DO NOT open the enclosure There are no...

Отзывы: