7. Technical data
Material:
Glass fibre reinforced polyester black RAL 9005
R
Surface
< 10
9
Ω
Stainless steel 1.4404(V4A); 316L,
Mild steel, varnished
Aluminium
Lid screws:
captive stainless steel screws, +-profile or hexagon M4/M6
Sealing:
according requirement of temperature range
Impact resistance:
according EN 60079-0: Impact energy 7 Joule
Protection Type:
Maximum IP66, according EN 60529 / IEC 60529
Terminals:
Certified connecting and/or series-terminals can be used
with maximal rated voltage of 2200V AC/DC.
Cable glands:
Certified cable glands which allow the connection of
cables with IP66 protection shall be used.
Metallic cable glands must be connected to the grounding
system.
Holes for cable entries which are not used shall be closed
by Ex certified blind plugs of minimum protection IP66.
Rated voltage:
Max. 2200V AC/DC
Rated current:
Max. 500A AC/DC
Cross-section:
Max. 300mm²
Ambient temperatures:
Max. -
60°C ≤ Ta ≤ +50°C (T6)
Max. -
60°C ≤ Ta ≤ +55°C (T5)
Max. -
60°C ≤ Ta ≤ +60°C (T4)
Specific data, please see type label
Storage temperature range:
-60...+80°C
For additional information please read EC-Type Examination Certificate