PART
“B”
THIS PART “B” OF THE INSTRUCTIONS MANUAL IS RESERVED FOR
PROFESSIONALLY SKILLED PERSONNEL APPROVED THE MANUFACTURER.
16.0 PARTIAL ROUTINE MAINTENANCE
BEFORE CARRYING OUT ANY MAINTENANCE JOBS IT IS OBLIGATORY TO STOP THE MACHINE AND DISCONNECT IT FROM THE
POWER MAINS AND FROM THE COMPRESSED AIR DISTRIBUTION NETWORK.
16.1 MAINTENANCE SCHEDULE
These maintenance intervals are recommended for work environments that are not dusty and are will ventilated. For
particularly dusty environments, double the frequency of controls.
Every week
◼
◼
Brush/blow off the finned surface of the condenser
◼
◼
Clean the filter of the automatic condensate drain
Every 2000 hours / 1 year
◼
◼
Replace the filter of automatic condensate drain (2902016102)
Every 4000 hours / 2 year
◼
◼
Replace drain kit (2200902017)
16.2 CLEANING OF THE AUTOMATIC CONDENSWATER DISCARGER FILTER (Fig. 10)
Clean the filter of the steam trap.
Proceed as follows:
- Close the cock Ref. 1 Fig. 10
-
Release the pressure in the dryer by pressing the condensate drain “TEST” pushbutton locate on the
steam trap
Ref. 2 Fig. 10.
- Switch off the machine. Turn the switch in position STOP Ref. 3 Fig. 10
- Turn on the supply automatic differential switch Ref. 4 Fig. 10
HOT PARTS INSIDE
- To use the hole Ref. 5
- Remove the stopper Ref. 6
- Remove the filter Ref. 7
- Clean the filter Ref. 5 with a jet of air, working from inside to outside
- Install the filter, fix the plug Ref. 7 - 6
- Close the panels Ref. 5
1
5
FIG. 10
2
3
4
6
7