Quietside QVM 9-090W1-NG Скачать руководство пользователя страница 44

 

QVM 9 

Series

 

42

 

 

 

QVM 9-090W1-NG

 

/

 

QVM 9-125W1-NG 

QVM 9-150W1-NG 

MODEL RANGE : 90,000

 

~

 

135,000 BTU  

 

 

THE CONDENSING GAS, WALL

 

-

 

MOUNTED, MULTI-PURPOSE, HYDRONIC HEATING SYSTEM

 

 

----

 KEY FEATURES 

z

  Full, Dual Function Heating Design 

z

  Provides Hi-Temp Water for Heating the Home

z

  Natural to Propane Gas Conversion Kit 

z

  Provides Warm Water for Bathing & Washing

z

  Sealed Combustion 2-Pipe Venting System 

z

  On-Demand Hot Water Delivery. 

z

  Modulating Gas Valve Control 

z

  Compact, Space-saving Design. 

z

  Built-in Circulator Pump Assembly 

z

  Quiet, Vibration-free Operation. 

z

  Built-in Expansion Tank 

z

  Limited lifetime Warranty on Heat Exchanger 

z

  Built-in Freeze Protection 

with 1-Year on Parts. 

z

  Digitally Controlled, Full-Logic Thermostat 

 

 

 

QUIETSIDE MODEL NUMBER 

QVM 9 

090W1-NG 

QVM 9 

125W1-NG 

QVM 9 

150W1-NG 

    (Old model number)      

(KC-201) 

(KC-251) 

(KC-301) 

    Function 

Combo Water heater 

CENTRAL HEATING WATER 

 

Construction of Heat Exchanger 

Stainless Steel / Copper 

 

Heat Input

 

(BTU/hr) 

46,000∼90,000 

55,000∼115,000 

65,000∼135,000 

 

Max. Efficiency (%) 

90 

 

Temperature setting range

 

(

o

F) 

104

 

 

176 

 

Maximum working pressure

 

(psi) 

42.7 

 

Pre-Charged Expansion Tank

 

(gal) 

1.82 

1.82 

2.24 

 

Circulator Pump    

self priming 

 

Freeze Protection device  

Thermistor 

DOMESTIC HOT WATER   

 

Heat Output

 

(BTU/hr) 

40,000∼78,300 

50,000∼100,000 

60,000∼117,400 

 

Max. Temperature Setting (

o

F) 

176 

 

Continuous DHW production @ 45F delta-T

 

(gpm) 

3.5 

4.4 

5.3 

 

Continuous DHW production @ 60F delta-T

 

(gpm) 

2.6 

3.3 

4.0 

 

Continuous DHW production @ 72F delta-T

 

(gpm) 

2.2 

2.8 

3.3 

 

Continuous DHW production @ 90F delta-T

 

(gpm) 

1.8 

2.2 

2.6 

 

Maximum Working Pressure

 

(psi) 

249 

OTHER DATA

 

 

Gas Type 

Liquefied Petroleum

 

(L.P.), or Natural gas 

 

Gas Consumption 

 LP

 

(lbs/hr) 

4.23 

5.13 

6.01 

 

Gas Consumption

 

(natural gas)

 

(cu. ft/hr) 

77.34 

94.29 

110.18 

 

Gas Inlet Supply Pressure

 

(natural

 

:

 

inch W.C.)

 

(min

 

-

 

max)

5.82″∼9.70″ 

 

Manifold Pressure

 

(inch W.C.) 

0.71″∼2.36″ 

0.87″∼3.00″ 

0.87″∼2.92″ 

 

Usage

 

(Heating & Hot Water) 

Dual 

 

Water Storage Capacity

 

(gal) 

0.18 

0.18 

0.21 

 

Power

 

(volts/cycle) 

AC 115V

 

/

 

60Hz 

 

Power Consumption

 

(watts) 

120

 

 

160 

 

Ignition  

ELECTRONIC 

 

Nox Emissions

 

(Ref

 

:

 

0%, O2 in flue gas natural gas

 

ppm)

20

 

(less than) 

 

Temp. of Exhaust Gas

 

(

o

F) 

185

 

(less than) 

WEIGHT AND DIMENSIONS

 

 

Net Weight

 

(lbs) 

75 

79 

84 

A  Physical Dimensions:    Height

 

(inch) 

27 ⅜″ 

27 ⅜″ 

28 ⅛″ 

Width

 

(inch) 

19 ½″ 

19 ½″ 

20 ¼″ 

Depth

 

(inch) 

8 ½″ 

8 ½″ 

9 ⅝″ 

D  Connection : Gas Inlet

 

(inch)    

3/4″

 

E  Connection : Heating Water Supply / Return

 

(inch) 

3/4″

 

F  Connection : Domestic Hot Water Supply / Return

 

(inch)

1/2″

 

G  Connection : Primary Power

 

(120 Volts) 

1/2″

 

H  Flue Diameter

 

(Intake / Exhaust) (inch) 

2.75″

 / 2.95″

 

Specifications subject to change without prior notification 

 

 

 www. quietside.com

                      NORTH AMERICA 2865 PELLISIER PLACE WHITTIER CA 90601 : QUIETSIDE CORPORATION

  

QUIETSIDE WATER HEATER 

Specifications

 

Содержание QVM 9-090W1-NG

Страница 1: ...arranty Does Not Cover 1 Installations by other than qualified heating contractors 2 Installations of equipment for other purposes than those intended by the instructions supplied with this equipment...

Страница 2: ...guish any open flame y Do not try to light any appliance y Do not touch any electrical switch do not use any phone in your building y Immediately call your gas supplier from a neighbor s phone Follow...

Страница 3: ...16 y Installation of the Flue 18 y Draining Condensed Water 21 y About the FR 5 Thermostat 22 y Installation of the Thermostat 23 y Using the Thermostat FR 5 24 y Test Operation and Checks 28 y Routin...

Страница 4: ...QVM 9 Series 2 Model QVM 9 090W1 NG 125W1 NG 150W1 NG Identifying the Components...

Страница 5: ...THE BURNER BY HAND 5 TURN KNOB OF GAS VALVE TO OFF POSITION 6 WAIT A FEW MINUTES TO CLEAR OUT ANY GAS THEN SMELL FOR GAS INCLUDING NEAR THE FLOOR IF YOU DON T SMELL GAS GO TO THE NEXT STEP 7 TURN KNOB...

Страница 6: ...ater level in the heat exchanger is continuously monitored to prevent the water heater from operating if there is no water or a restricted flow of water in the unit The water heater will be automatica...

Страница 7: ...he Check Lamp is LIT during the operation it means that the gas supply has run out Check the lamp frequently For other troubleshooting see page 35 and 38 CAUTION Do not use the water heater for other...

Страница 8: ...prolonging the life of the unit Setting the water heater temperature at 120 F will reduce the risk of scalds Some states require settings at specific lower temperatures The table below shows the appr...

Страница 9: ...it instantaneously The modulating gas burner allows water to heat up evenly as it is being used The QVM 9 will continue to heat the water until the source or sources are shut off This on demand use al...

Страница 10: ...cally restart In cold weather climates manual resets could cause freeze damage 12 Safety Protection During Power Outages When the power fails the gas valve is automatically shut down 13 Automatic Fill...

Страница 11: ...lways monitored and the water heater will not start when there is no water in the exchanger 8 Thermostat Safety Protection If the thermostat fails combustion will be stopped and the gas supply is auto...

Страница 12: ...a heating cycle The unit will switch over from heating to provide domestic hot water When the use of hot water is stopped The unit automatically converts back to the heating mode If hot water is to b...

Страница 13: ...thermostats drain valve and relief valve As the gas water heater is to be installed indoors they shall not be installed outdoors such as in the porch Do not install water heater on a combustible wall...

Страница 14: ...e brass male connectors below the unit Allow fittings to cool before attaching to unit Use only approved coupling unions with O rings to attach field piping to unit The heating pipe should be 3 4 and...

Страница 15: ...plumbing supplier Mixing type valve Controls the desired hot water temperature and ensures constant hot water temperature in the faucets accuracy 2 Ensures safety through the built in anti burn scald...

Страница 16: ...ater heater WARNING For safe operation an ample supply of air must be provided for proper combustion and ventilation in accordance with the national fuel gas code ANSI Z223 1 or CAN CGA B149 1 or B149...

Страница 17: ...ce the risk if location in such an area cannot be avoided Flammable items pressurized containers or any other potential fire hazardous articles must never be placed on or adjacent to the water heater...

Страница 18: ...ockage These are parts of the gas supply system not the water heater Vent blockage may occur during ice build up or snow storms When local codes require a main manual shut off valve outside the water...

Страница 19: ...mmediate and severe damage to the gas valve and its internal pressure regulating device and could result in property damage and or personal injury Set DIP switch 1 to the ON position priority fill The...

Страница 20: ...urn back to the water heater Do not place the outdoor termination kit in an area where discharge gases will be directed towards evergreen shrubbery Assemble the flue using the following illustration a...

Страница 21: ...connection of the air supply hose must be sealed by the wire clamp to prevent any air loss In the connection of the flue duct and the flue elbow an O ring must be inserted to prevent leaks Do not use...

Страница 22: ...QVM 9 Series 20 Schematic of SCF 9 Installation Installation of the Flue...

Страница 23: ...inimum diameter of 1 2 inch is to be used IMPORTANT The siphon reservoir in the water heater should be filled with water If no water is available do not operate the water heater The condensed water sh...

Страница 24: ...ore than others could find that setting the thermostat to the water temperature sensing function will provide the best comfort We suggest trying them both The Air Temperature Mode The QVM 9 hydronic h...

Страница 25: ...ge colored stranded wires from unit to the 2 screws located on the FR 5 thermostat 4 Mount the back plate to the wall using either of the above techniques depending on the construction of the wall Rec...

Страница 26: ...QVM 9 Series 24 Thermostat Model FR 5 Using the Thermostat FR 5...

Страница 27: ...ion in this mode set the temperature control below 104 Rad The unit will stop but the freeze prevention function will stand by 1 Press the Away From Home Saving button The room temperature will be ind...

Страница 28: ...emperature will be indicated on the temperature display and the Set Temperature lamp and In Use light will go on 2 Turn the Set Temperature dial to select the desired room temperature the temperature...

Страница 29: ...t recommended to use this unit for making hot beverages 1 If the water heater cannot run due to a failure in the temperature control call for service The two wires at the back of the room thermostat m...

Страница 30: ...of gas does not match the one specified on the unit rating plate modification and re adjusting will be required Consult your heating dealer or a qualified technician with the gas utility company Test...

Страница 31: ...heater refer to page 21 Turn 1 DIP switch to ON position Trial Operation mode Install the room thermostat FR 5 Power lamp will flash 1 second ON 1 second OFF during trial operation Open the manual wat...

Страница 32: ...t water provided from the water heater If the power supply to the water heater is shut off after the test operation completely drain water from the system heating hot water to prevent possible freeze...

Страница 33: ...H OR OTHER STATIC CREATING MATERIAL TO CLEAN DUST AND CARBON DEPOSITS FROM HEATING SURFACES AND VENT SUCH DEPOSITS ARE FLAMMABLE AND MAY BE IGNITED BY STATIC ELECTRICITY USE A METAL BRUSH TO MINIMIZE...

Страница 34: ...ub or faucets Check the pressure of the incoming water supply If the pressure is lower than the minimum hot water pressure install a separate pressurizing pump 6 Check for external contamination Stop...

Страница 35: ...me applications the flat plate heat exchanger may be subjected to severe conditions including high temperature and or hard water conditions causing accelerated scaling and corrosion rates which will i...

Страница 36: ...ties from the system When heating performance is decreased clean the filter by removing clip washing out and re inserting the filter Replace the clip CAUTION THE WATER FLOWING OUT OF THE PRESSURE RELI...

Страница 37: ...er 5V DC 09 Fan RPM Failure y Fan failure y Check speed control y Check fan for operation Input voltage 7 40V DC Red Black wires 10 Air Pressure Switch Failure y Fan failure y Air flow switch failure...

Страница 38: ...QVM 9 Series 36 Wiring Diagram Error Codes FR 5 Thermostat DIP S W Setting on Main Controller Wiring Connecters...

Страница 39: ...37 QVM 9 Series Wiring Diagram...

Страница 40: ...pipe If the pipe is clogged contact the unit installer Clean the heating strainer Check the circulation pump After removing the cause press the HEAT ON button again Low or no gas pressure Contact for...

Страница 41: ...39 QVM 9 Series Models QVM9 090W1 NG 125W1 NG 150W1 NG Exploded Views...

Страница 42: ...Air Vent 1 All QVM9 20 C21708268A BH2507143A Air Vent Inlet Pipe 1 C1220T All QVM9 21 C20901011B BH1301010A Heating Strainer 1 All QVM9 22 C21708255B BH2507097A Heating Return Connection 1 C3712 All...

Страница 43: ...M9 125W1 C21708382A BH2507041A 1 STS304 QVM9 150W1 48 C21708252A BH2507057A Gas Control Valve Outlet Connection 1 ALDC All QVM9 49 C21708269B BH2507164A Heat Exchanger Outlet Pipe 1 C1220T QVM9 090W1...

Страница 44: ...put BTU hr 40 000 78 300 50 000 100 000 60 000 117 400 Max Temperature Setting o F 176 Continuous DHW production 45F delta T gpm 3 5 4 4 5 3 Continuous DHW production 60F delta T gpm 2 6 3 3 4 0 Conti...

Отзывы: