15 minutes before quitting time – turn off the water pump and let the fan run 10 – 15 minutes – to dry out the cooling pads 

before leaving. Inspect the cooling pads to make sure they are thoroughly dry (this action helps to reduce mold and mildew) 

when pads are completely dry then turn-off fan. 

 

7.4  Periodic maintenance 

Depending upon your environment and how often you operate your QuietCool will depend on how dirty your water gets in 

the reservoir and how often you will need to clean it. If you begin to detect an 

algae smell

 coming from your unit – it’s time 

to flush your QuietCool reservoir with fresh water. Refer to and follow the steps above in 7.2 and remove 1 of the cooling 

pads  from  the  left  side  of  the  unit  to  gain  access  to  your  water  reservoir.  Take  a  small  sponge  and  clean  out  your  water 

reservoir  with  a  light  cleaner  and  wipe  it  down  completely  and  let  the  unit  dry.  (You  may  want  to  use  a  wet  /  dry  shop 

vacuum to clean out unit). When unit is clean add ½ Evap-O-Matic tablet to reservoir and replace your cooling pads (make 

sure flutes are facing correct direction – see photo) retaining bar and bolts and add fresh, clean water back to the units’ water 

reservoir.  Note:  You  can  get  the  tablets  by  ordering  from  the  QuietCool  order  form  found  in  section  9.0.  Simply  follow 

instructions on the label. You may want to consider a Water Stabilizer to remove harmful calcium, scale build-up and algae 

– see section 9.0. 

Warning! Do not run pump without water in the reservoir.

 This action will burn up your QuietCool’s water pump. 

 

7.5 QuietCool Trouble Shooting Guide 

 

Problem                                       

 

 
1.  Water on the Floor 
A.  Front of unit . . . 
       
 
B.  Back of unit 
 
 
 
 
 
 
 
 
 
2. Found water on floor after 
overnight shut off. 
 
 
 
 
 
 
 

 

 
 
3.  Foul odor from fan 
 A.  New Unit . . .  
 
     
 

Problem 

(continued)

 

 

 

Cause

 

 
Damage to polyethylene housing. Note: 
Check for possible cracks in the blue 
polyethylene. 
 
Excess water at top or bottom of pads. 
 
 
Damage to blue polyethylene housing. 
 
 
Leaking from bottom of pads. 
 
 
 
Excessive water pressure.  
 
 
 
 
Float valve maybe stuck in open position. 
 
 
 
 
 
 
 
New pad may have a temporary odor (this 
is normal) – you may be smelling the 
thermosetting resin – it will pass. 
 
 

Cause 

(continued)

 

 

Solution

 

 
Repair as necessary. 
 
 
 
Very gently move pads slightly with your finger 
tips. 
 
Search for leaks and repair as necessary. 
 
 
Push bottom of cooling pads gently inside to 
stop leaking. 
 
 
Check your water pressure. Max water pressure 
is 60 p.s.i., by adding a water pressure regulator 
found at local hardware store. 
 
 
Contaminants in water; drain cooler, sump and 
refill. If float remains stuck remove pads and 
examine float for debris or damage. Wash out 
debris and replace float. Continue. 

 

 
 

 
Drain and refill several times in first week to 
remove thermosetting resin smell. 
Add Evap-O-Matic Tablet to reduce smell –  
and algae. 
 

Solution 

(continued)

 

Содержание QC18DVS

Страница 1: ...he QC18DVS QuietCool Portable Evaporative Cooler QC18DVS QuietCool 18 Direct Drive Variable Speed with Deep Base Shown QC18D3 QuietCool 18 Direct Drive 3 Speed with Deep Base Optional Cover for storag...

Страница 2: ...er voltage frequency configuration See manufacturer s label on cooler A ground fault circuit interrupter protected circuit is strongly recommended WARNING Check your units electric power cord for insu...

Страница 3: ...Operating procedures 6 1 Turn on pump 6 2 Turn on fan 6 3 Turn off unit 7 0 Maintenance 7 1 Access inside of unit 7 2 Removing the cooling media 7 3 Daily maintenance 7 4 Periodic maintenance 7 5 Qui...

Страница 4: ...me temperature air same humidity your QuietCool portable evaporative cooler takes that same existing air combines it with evaporating water which dramatically lowers the temperature immediately reliev...

Страница 5: ...s between your QuietCool and the people area you need to cool 5 1 Filling the units reservoir with water Once your water hose is connected turn water on and fill the reservoir with water Listen carefu...

Страница 6: ...cooling pads are thoroughly dry about 10 15 minutes Once your cooling pads are completely dry you may turn off fan Now unplug electricity to unit to avoid unnecessary shock Next using a 7 16 wrench r...

Страница 7: ...ply follow instructions on the label You may want to consider a Water Stabilizer to remove harmful calcium scale build up and algae see section 9 0 Warning Do not run pump without water in the reservo...

Страница 8: ...water filter pull out filter screen and clean Replace and try again Use Evapo O Matic Tablet or add a Water Stabilizer at the discharge side of the pump See Accessories section 9 0 Flush water from u...

Страница 9: ...s scale and calcium deposits associated with hard water Adds life to vital cooler equipment increases cooling efficiency and ends swampy odors Treatment 1 2 tablet for18 units EPA registered protectio...

Страница 10: ...er form QC18PUMP Replacement Pump for all 18 units Simply replace the new pump with the old pump List 81 00 each TR798 Float Valve for all 36 units Automatically adjusts water level in units reservoir...

Страница 11: ...s water level TR798 List 16 00 each Inline filter Catches large debris in water line to cooling pads 12Filter List 23 00 each Replacement Casters Straight Swivel Wheel Sold in set of 4 QC18CK 4 Wheels...

Страница 12: ...12 12 0 Wiring Diagrams for 18 unit...

Страница 13: ...the defective product or part damages due to removal or any expenses incurred in shipping the product of part to or from Quietaire Cooling plant or the installation of the repaired or replaced produc...

Отзывы: