3.4 On/Off and display items
Press the “ON/OFF” button to turn the system ON or OFF.
When the system is ON, the setpoint, fan status, operation mode (RUN or
HOLD), and fresh air vent status is displayed.
When the system is OFF, the control will display the time, day, %RH, and
temperature.
When the unit is shipped, it is in manual (hold) mode.
3.5 Setting Clock Time
1. Press and hold the “CLOCK” button. The hour display will flash. Release
the button.
2. Use the up/down “RH” buttons to change the value.
3. Press the “CLOCK” button again and the minute display will flash. Use
the “RH” buttons to change the value.
4. Press the “CLOCK” button again and AM or PM will flash. Use the “RH” buttons to change the value.
5. Press the “CLOCK” button again and the day display will flash. Use the “RH” buttons to change the value.
6. Don’t touch any buttons for several seconds until the display stops flashing, this will save your settings. If you
need to change anything go back to step #1.
3.6 Adjusting the relative humidity “SETPOINT”
The Quest DEH 3000 senses the ambient relative humidity (%RH) of the space in which it is located, it comes
factory preset to hold 50% relative humidity.
The relative humidity “SETPOINT” (desired RH to be maintained) operates
the dehumidifier function of the Quest dehumidifier. It has no effect on the
optional VENT (fresh air ventilation) or FAN ( air recirculation) functions if
they are being used.
Operation
The standard range that the dehumidifier holds around your “SETPOINT”
is 3%. With a setpoint of 50%, the dehumidifier will run until the relative
humidity reaches 47%. The dehumidifier will then switch off until the
relative humidity reaches 53%.
If the setpoint is higher than the ambient relative humidity, the space does not need to be dehumidified so the
dehumidifier will not run.
Example: Setpoint: 50% RH
Current condition: 45% RH –The dehumidifier will be off (no “O” indicator will be displayed).
If your setpoint is below the ambient condition, the dehumidifier will be on and “O” will display.
Example: Setpoint: 50% RH
Current condition: 55% RH –The dehumidifier will be on (“O” displayed).