3.4 Natural Gas Burner and Fuel Specifications
(Fig. 3)
• The “gas burner” is a power, forced-draft, type with direct spark ignition, manufactured by Riello Burners.
• A CSA/UL version gas train is factory installed in units equipped for either natural gas or propane. The gas train
works with either burner.
• Two gauges are mounted to pressure-tap ports on the gas train for use in setting the burner and monitoring
performance (Fig. 24).
3.5 Circulation Pump
(Fig. 4)
• The HTF circulation pump is a stainless steel, direct drive centrifugal type.
• The pump is located inside the enclosure at the opposite end to the burner and can be accessed through a
hinged lockable door (Fig. 1).
• A panel-mounted pressure gauge is connected to the output side of the HTF pump by means of a 1/8” ID
hydraulic hose and fittings (Fig. 23).
3: Gas Burner, LP or Natural Gas Train
Riello Burner Model
Natural Gas
40-G400-NG
Operational Mode
single stage
Electrical Characteristics
V / A / Hz / Ph
120 / 2.2 / 60 / 1
Orifice: factory equipped
#
2.2
Diaphragm: factory equipped
#
C4
Gas Supply Pressure: Minimum
“WC (KPa)
7 (1.74)
Gas Supply Pressure: Maximum
“WC (KPa)
10.5 (2.61)
Gas Manifold Pressure ( P): factory set
“WC (pascals)
3.8 (946)
Heat Setting: factory set
#
1
Air Gate Setting: factory set
#
3.5
Heat Input
B/tu/H (Watts)
300,000 (87.9)
Heat Output: @ 80% net efficiency
B/tu/H (Watts)
240,000 (70,320)