Installation, Operation and Maintenance Instructions

  

1-877-420-1330

 

8

www.QuestHydro.com

[email protected]

The evaporator operates in a flooded condition, which means that all the evaporator tubes contain liquid refrigerant during normal 

operation. A flooded evaporator should maintain constant pressure and temperature across the entire coil, from inlet to outlet.
The mixture of gas and liquid refrigerant enter the accumulator after leaving the evaporator coil. The accumulator prevents any 

liquid refrigerant from reaching the compressor. The compressor evacuates the cool refrigerant gas from the accumulator and 

compresses it to a high pressure and temperature to repeat the process.

4.3 Troubleshooting

No dehumidification, neither hour meter display nor compressor run and POWER button does not turn ON.
1.   Unit unplugged or no power to outlet
2.   Defective control board
3.   Loose connection in internal wiring
No dehumidification, neither hour meter display nor compressor run with POWER button ON.
1.   Defective control board
2.   Loose connection in internal wiring
Some dehumidification, air mover runs continuously but compressor only runs sporadically.
1.   Unit is in defrost cycle, DEFROST light on
2.  Check to make sure humidistat is set high enough
3.   Defrost thermistor defective or loose
4.   Loose connection in compressor circuit
5.   Defective compressor overload
6.   Defective compressor
7.   Defective relay
8.   Low refrigerant charge
No dehumidification, air mover runs but compressor does not.
1.   Bad connection in compressor circuit
2.  Check to make sure humidistat is set high enough
3.   Safety float switch closed, check pump reservoir
4.   Defective compressor capacitor
5.   Defective compressor overload
6.   Defective compressor
7.   Defective control board
8.  Low refrigerant charge

Содержание CDG 174

Страница 1: ...oceed successfully Ultimate satisfaction depends on the quality of installation and a thorough understanding of this equipment The dehumidifier is built around tested engineering principles and has pa...

Страница 2: ...5 2 5 Ducting 5 2 6 POWER Button 5 2 7 PURGE Button 5 2 8 Humidistat 6 2 9 HOURS Button 6 2 10 DEFROST Light 6 2 11 Defrost Cycle 6 2 12 Low Pressure Control 6 3 Maintenance 7 3 1 Air Filter 7 3 2 Sto...

Страница 3: ...nd service DO NOT INSTALL UNIT WITH THE SERVICE PANELS INACCESSIBLE Avoid directing the discharge air at people or over the water in pool areas If used near a pool or spa be certain there is NO chance...

Страница 4: ...sate hose into a drain or a very large container and turn on To decrease drying times make sure all windows and doors are closed to the outside and seal off the wet area from any unaffected areas 2 1...

Страница 5: ...it overlaps the outside of the collar The duct and collar may then be quickly attached to the Quest CDG 174 by snapping the collar over the four screws at the blower outlet 2 6 Power Button Press the...

Страница 6: ...evaporator temperature does not reach the desired temperature the compressor will start after 15 minutes The system will start a timed defrost cycle The timed defrost cycle ensures the unit will cont...

Страница 7: ...evel in the reservoir 5 Flush with water 4 Service CAUTION Servicing the Quest CDG 174 with its high pressure refrigerant system and high voltage circuitry presents a health hazard that could result i...

Страница 8: ...d POWER button does not turn ON 1 Unit unplugged or no power to outlet 2 Defective control board 3 Loose connection in internal wiring No dehumidification neither hour meter display nor compressor run...

Страница 9: ...ycle 5 Air filter dirty 6 Defective defrost thermistor 7 Low refrigerant charge 8 Air leak such as loose front cover 9 Defective compressor 10 Restrictive exhaust or inlet ducting Unit runs but does n...

Страница 10: ...ure in reverse 4 6 Thermistor Replacement The defrost thermistor probe is inserted into the coil measuring coil temperatures and reacts accordingly To replace thermistor 1 Remove top cover and filter...

Страница 11: ...the plastic plug on the right side see Fig 4 out from inside the unit 3 Locate the heavy vinyl hose that connects the drain pan to the condensate pump Pull the end out of the pump 4 Remove tie wrap h...

Страница 12: ...4 1 COMPRESSOR RELAY LOW PRESSURE SWITCH COMPRESSOR R C S PUMP NC NO YEL TERMINAL BLOCK WIRE CAPACITOR COMPRESSOR CAPACITOR IMPELLER SAFETY PROBE IMPELLER CAPACITOR 2 6 20 BLK 13 16 19 WHT 12 WHT 9 1...

Страница 13: ...citor Impeller 15mfd 371V 1 4035235 07 14 Thermistor not shown 1 4034716 01 15 Cord 14ga 25 1 4037569 16 Compressor 11 9KBTU R410a 1 4034763 17 Overload Compressor 1 4034033 18 Evaporator Coil 1 40344...

Страница 14: ...The end user is responsible for normal care This warranty does not cover any defect malfunction etc resulting from misuse abuse lack of normal care corrosion freezing tampering modification unauthori...

Отзывы: