Rev 2.1 10/21/21
- 20 -
TELSEC
©
MP2X User Guide
Input values as counts from the adc output - Use for 0-6VDC or 0-20mA Transducers
Function Code
Register
Description
Read/Write Notes
Input Register (FC4)
224
Input 1 Raw Counts
RO
0-4095 Counts. 667 counts per 1VDC.
For 0-20mA transducers
196 counts per mA with 301-ohm load resistor
163 counts per mA with 249-ohm load resistor
147 counts per mA with 225-ohm load resistor
66 counts per mA with 100-ohm load resistor
*Load resistor to be installed between input
and ground
225
Input 2 Raw Counts
226
Input 3 Raw Counts
227
Input 4 Raw Counts
228
Input 5 Raw Counts
229
Input 6 Raw Counts
230
Input 7 Raw Counts
231
Input 8 Raw Counts
232
Input 9 Raw Counts
233
Input 10 Raw Counts
234
Input 11 Raw Counts
235
Input 12 Raw Counts
236
Input 13 Raw Counts
237
Input 14 Raw Counts
238
Input 15 Raw Counts
239
Input 16 Raw Counts
240
Input 17 Raw Counts
241
Input 18 Raw Counts
242
Input 19 Raw Counts
243
Input 20 Raw Counts
244
Input 21 Raw Counts
245
Input 22 Raw Counts
246
Input 23 Raw Counts
247
Input 24 Raw Counts
248
Input 25 Raw Counts
249
Input 26 Raw Counts
250
Input 27 Raw Counts
251
Input 28 Raw Counts
252
Input 29 Raw Counts
253
Input 30 Raw Counts
254
Input 31 Raw Counts
255
Input 32 Raw Counts
Содержание TELSEC MP2x