NetApp® E-Series Storage Systems: Replacing a Power Canister in the DE6600 Drive Tray

1. Gather support data about your storage array by using one of these methods:

Use the storage management software to collect and save a support bundle of your storage array. From the Array 

Management Window, select 

Advanced >> Troubleshooting >> Support Data >> Collect

. Then name and 

specify a location on your system where you want to store the support bundle.

Use the command line interface (CLI) to run the 

save storageArray supportData

 command to gather 

comprehensive support data about the storage array. For more information about this command, refer to 

Command 

Line Interface and Script Commands

. Running this command can temporarily impact performance on your storage 

array.

2. Did the Recovery Guru direct you to replace a failed power canister?

Yes

 – Go to step 

3.

No

 – Run the Recovery Guru to identify the failed component, and then go to step 

3.

3. Put on antistatic protection.
4. Unpack the new power canister.

a. Set the new power canister on a flat, static-free surface near the drive tray.
b. Save all packing materials in case you need to return the power canister.

5. Make sure that the Power switch on the new power canister is turned off. 
6. Check the Power Service Action Required LED to locate the failed power canister (

Figure 2

).

Figure 2  LEDs on a Power Canister

1.

Standby Power LED (Green)

2.

Power Output DC Power LED (Green)

3.

Power Service Action Allowed LED (Blue)

4.

Power Service Action Required LED (Amber)

5.

Power Input AC Power LED (Green)

If a fault is detected, the amber Power Service Action Required LED is on. If you can safely remove the power canister, 

the blue Power Service Action Allowed LED is on.

Содержание StorNext QD7000

Страница 1: ...Replacing a Power Supply Unit PSU StorNext QD6000 QD7000 Expansion Unit 6 68486 01 Rev A 6 68486 01 Rev A...

Страница 2: ...nit PSU 6 68486 01 Rev A July 2016 Product of USA 2016 All rights reserved Quantum the Quantum logo DXi Scalar and StorNext are registered trademarks of Quantum Corporation and its affiliates in the U...

Страница 3: ...ion Intended audience Prerequisites NetApp to Quantum Naming Decoder Intended audience This guide is intended for storage customers and technicians Prerequisites Prerequisites for installing and using...

Страница 4: ...dules ESMs E5600 Code Name Titan RAID controller Four 16Gb s FC SFP host ports E5500 Code Name Soyuz RAID controller Four 16Gb s FC SFP host ports E5400 Code Name Pikes Peak RAID controller Four 8Gb s...

Страница 5: ...r your particular hardware configuration If you are performing a hardware reconfiguration make sure you have the correct replacement power canister to support the particular controller tray or control...

Страница 6: ...storage array 2 Did the Recovery Guru direct you to replace a failed power canister Yes Go to step 3 No Run the Recovery Guru to identify the failed component and then go to step 3 3 Put on antistatic...

Страница 7: ...ve tray Figure 2 ATTENTION Possible loss of power To avoid taking the wrong power canister offline and causing thedrive tray to lose all power contact your Technical Support representative before perf...

Страница 8: ...blem Yes Go to step 17 No If the problem has not been resolved contact your Technical Support representative 17 Check the status of all of the trays in the storage array 18 Does any component have a N...

Отзывы: