Quantum Scalar LTFS Appliance: Rail Replacement
6-68096-01 Rev A
December 2013
6
Reinstalling the Chassis in the Rack
WARNING:
The Scalar LTFS Appliance weighs 37.3 lbs (16.9 KG). Two people
are required to lift the chassis.
1
Pull the inner slide rails out of the rack until they lock into place.
2
Locate the rear rail standoff on each side of the Scalar LTFS Appliance and
lower them into the rear J-slots on the slide assemblies.
3
Rotate the Scalar LTFS Appliance downward until all the rail standoffs are
seated in the J-slots.
4
Push the Scalar LTFS Appliance inward until the lock levers click into place.
5
Press the slide-release lock button on both rails and slide the system into the
rack.
Note:
Figure
4
shows nodes with the bezel; however, the bezel is actually
added after the components are installed in the rack.
Figure 4 Installing the Chassis
in a Rack
Chassis Rails
Front
Back
Server-to-rail latch
Slide Release
Lock button
6
Insert and tighten the PHILLIPS screws that secure the Scalar LTFS Appliance
to the front of the rack.