INSTALLATION and WIRING

IMPORTANT:  

Provide each unit with a DC power supply from a 5V through 30V (at 10C to 40C) or 7V through 30V (at -30C to 

40C) 

as applicable circuit used for emergency lighting.

WARNING:  

During installation of remotes, input wires from main unit to remote units must 

NOT be connected to each other 

or 

connected to ground.  Failure to due so will lead to failure of the main unit.

NOTE: The maximum mounting height with tilt and swivel lamp heads are shown below to meet the minimum illumination 

requirements of NFPA 101 (Current Life Safety Code).

A. 

Use code-approved connectors to connect input leads inside 

J-box

[See label on wire pair for positive and negative 

polarity colors].
B

. On the mounting plate, open the desired keyhole junction-

box knockouts.

C

. Route input connector through center hole in mounting plate.

D

. Taking care not to pinch wires or connectors dressed inside 

junction box, secure mounting plate to junction box screws. 
NOTE: to ensure proper engagement of the mounting plate 
latches to the housing, DO NOT OVER-TIGHTEN THE 
SCREWS.

Junction box mounting:

-Some details shown below may vary-

1

Housing attachment to mounting plate:

A

. Plug the input connector to the receptacle on the lamp 

driver board.

B

. Ensure that wires are routed to avoid interference with 

other components, and push housing straight onto mounting 
plate, making certain both latches are fully engaged.

2

Push housing straight onto mounting plate

Junction boxes accommodated:

4” Square

4” Octagon

3-

1/2” Round or Octagon

Single Gang Box                                                  

Part # 912-00028-001 

Rev. C, 05/2020

© 2020, Acuity Brands Lighting,  Inc. 

All Rights Reserved.

ELMRE LP220L SGL/T

8.7/11.8 ft

ELMRE SP640L SGL/T

24.4/31.9 ft

ELMRE SP1100L  SGL/T

30.8/43.4 ft

LIFE SAFETY SOLUTIONS

TEL:  800-334-8694  

www.lithonia.com

Содержание ELMRE SP1100L

Страница 1: ...AY DAMAGE FIXTURE WHICH MAY RESULT IN PERSONAL INJURY WARNING RISK OF PERSONAL INJURY This product may have sharp edges Wear gloves to prevent cuts or abrasions when removing from carton handling inst...

Страница 2: ...LP220L Twin Remote LP220L Single Remote SP1100L Twin Remote SP640L Single Remote page 2 REMOTE EMERGENCY LAMP...

Страница 3: ...t connector through center hole in mounting plate D Taking care not to pinch wires or connectors dressed inside junction box secure mounting plate to junction box screws NOTE to ensure proper engageme...

Страница 4: ...the remote units See label on wire pair for positive and negative polarity colors Remote Lamp Twin Driver Board page 4 INSTALLATION and WIRING DC input to the remote units See label on wire pair for p...

Страница 5: ...ONALES ADVERTENCIA RIESGO DE LESIONES PERSONALES este producto puede tener bordes afilados Use guantes para evitar cortes o abrasiones al extraer el producto de la caja manipularlo instalarlo o repara...

Страница 6: ...Control remoto doble LP220L Control remoto nico LP220L Control remoto doble SP1100L Control remoto nico SP640L page 2 L MPARA DE EMERGENCIA REMOTA...

Страница 7: ...rav s del orificio central en la placa de montaje D Con cuidado de no presionar los cables o conductores organizados dentro de la caja de conexi n fije la placa de montaje a los tornillos de la caja d...

Страница 8: ...de Acuity Brands Lighting que est n marcadas con el s mbolo est n registradas en los EE UU y pueden estar registradas en otros pa ses Diagrama del cableado L mpara remota Entrada CC a las unidades rem...

Страница 9: ...I PEUT ENTRA NER DES BLESSURES CORPORELLES AVERTISSEMENT RISQUE DE BLESSURE CORPORELLE Ce produit peut avoir des bords tranchants Portez des gants pour viter des coupures ou des raflures lors du retra...

Страница 10: ...LP220L distance double LP220L distance simple SP1100L distance double SP640L distance simple page 2 LAMPE D URGENCE DISTANCE...

Страница 11: ...de raccordement C Passez le connecteur d entr e par le trou au centre de la plaque de montage D En prenant soin de ne pas pincer les fils ou les connecteurs dispos s dans le bo tier de raccordement fi...

Страница 12: ...commerce d Acuity Brands Lighting qui arborent le symbole sont d pos es aux tats Unis et peuvent l tre dans d autres pays Sch ma de c blage Lampe distance Entr e CC vers les unit s distance Voir l tiq...

Отзывы: