SECTION 7 - OPERATION
FORM QTC4-NM1
ISSUE DATE: 4/2/2018
The start inhibit thresholds for each sensor are shown
in the following table.
TABLE 20 -
START INHIBIT SENSOR THRESHOLDS
SENSOR
LOW
THRESHOLD
HIGH
THRESHOLD
Suction
Transducer
0.3VDC
4.7VDC
Oil
Transducer
0.3VDC
4.7VDC
Discharge
Transducer
0.3VDC
4.7VDC
Motor Temp.
Sensor
0°C (0ºF)
116°C (240ºF)
* The Unit Setup Mode allows a specific motor temperature sensor
to be ignored, if it fails.
High Motor Temperature Cutout Fault
The High Motor Temperature Cutout prevents a com-
pressor from running when its motor temperature is too
high. A system will fault and shut down when any com-
pressor motor temperature sensor rises above 121°C
(250°F). The system will be inhibited from starting if
its motor temperatures sensors indicate temperatures
above 116°C (240°F). If any single temperature sen-
sor is being ignored under the Unit Set-up Mode, that
sensor will not be utilized when evaluating motor tem-
perature.
Below is a sample Status display fault message:
SYS X YYYYYYYY HIGH MOTOR TEMP
The X indicates the system and YYYYYYY indicates
the system is in a “FAULT” condition and will restart
when the fault clears or “LOCKOUT” and will not re-
start until the operator clears the fault using the keypad.
System Control Voltage Cutout Fault
The System Control Voltage Cutout alerts the operator
the 115VAC Control voltage to one of the systems is
missing. This could be due to a system fuse that has-
been removed or is blown. The affected system will
fault and shut down immediately when the 115VAC
supply is lost.
The safety will “not” shut down a system if the UNIT
switch is OFF, which electrically removes the 115VAC
to “all” systems. The safety is only used to indicate a
situation where a single system is missing the 115VAC.
The safety will not cause a lockout and the system fault
will reset when power is returned. A sample message
is shown below:
SYS X YYYYYYYY CONTROL VOLTAGE
The X indicates the system and YYYYYYY indicates
the system is in a “FAULT” condition and will restart
when the fault clears or “LOCKOUT” and will not re-
start until the operator clears the fault using the keypad.
Eductor Clog Fault
To sense a loss of oil return to the compressor, an educ-
tor clog detection safety is utilized. The safety moni-
tors the temperature of the line between the eductor
and the suction line.
The control algorithm looks at the eductor line temper-
ature once a second. At start, a clog timer is set at 600
seconds. If the eductor line temperature is less than the
saturated suction temperature plus 5.5°C (10°F) each
time the control circuit looks at the temperature, the
clog timer is reset to 600 seconds.
If the eductor line temperatures is greater than the satu-
rated suction temperature plus 5.5°C (10°F), the clog
timer is decremented one second.
If the temperature remains above the saturated suc-
tion temperature plus 5.5°C (10°F) for 600 seconds,
the clog timer will count to “0” and the system will
shut down and lock out. The status fault will indicate
an eductor clog fault.
EDUCTOR CLOG FAULT
Whenever this fault occurs, the eductor filter should be
changed.
The clog timer resets to 600 seconds whenever the con-
trol algorithm sees the eductor line temperature is less
than the saturated suction pressure plus 5.5°C (10°F).
This prevents nuisance eductor clog faults.
Содержание QTC4 STYLE A Series
Страница 22: ...QUANTECH 22 FORM QTC4 NM1 ISSUE DATE 03 07 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 34: ...QUANTECH 34 FORM QTC4 NM1 ISSUE DATE 03 07 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 56: ...QUANTECH 56 FORM QTC4 NM1 ISSUE DATE 03 07 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 77: ...SECTION 5 TECHNICAL DATA QUANTECH 77 FORM QTC4 NM1 ISSUE DATE 03 07 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 90: ...QUANTECH 90 FORM QTC4 NM1 ISSUE DATE 03 07 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 148: ...QUANTECH 148 FORM QTC4 NM1 ISSUE DATE 03 07 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 160: ...QUANTECH 160 FORM QTC4 NM1 ISSUE DATE 03 07 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 163: ...QUANTECH 163 FORM QTC4 NM1 ISSUE DATE 4 2 2018 NOTES...